Klinkmann Unitronics EX-A2X Скачать руководство пользователя страница 5

12/09

EX-A2X 

 

 

I / O   E x p a n s i o n   M o d u l e   Ad a p t e r ,   I s o l a t e d

Unitronics

 

5

Wiring Power Supply 

1.

Connect the "positive" cable to the "+V" terminal, and the “negative” to the "0V" terminal.

Always connect the functional earth pin to the earth ground. Use a dedicated wire for this purpose; it must
not exceed 1 meter.
Do not connect the neutral or line signal of the 110/220VAC to the device’s 0V pin.
In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the
device to a regulated power supply.
A non-isolated power supply can be used provided that a 0V signal is connected to the chassis.
Note that both the OPLC and the EX-A2X must be connected to the same power supply.
The EX-A2X and the OPLC must be turned on and off simultaneously.

POWER

0V

V

EX-A2X Technical Specifications 

I/O module capacity 

Up to 8 I/O modules can be connected to a single adapter. 

Power supply 

12VDC or 24VDC  

Permissible range 

10.2 to 28.8VDC 

Max. current consumption 

650mA @ 12VDC; 350mA @ 24VDC 

Typical power consumption 

4W 

Current supply for  
I/O modules 

1A max. from 5V (see Note 1) 

Galvanic isolation  

EX-A2X power supply to: 

 OPLC port  Yes 

Expansion module port  No 

Status indicators 

(PWR) 

Green LED—Lit when power is supplied. 

(COMM.) 

Green LED—Lit when communication is established. 

Environmental

IP20/NEMA1 

Operating temperature 

0

°

to 50

°

C (32 to 122

°

F) 

Storage temperature 

-20

°

to 60

°

C (-4 to 140

°

F) 

Relative Humidity (RH) 

10% to 95% (non-condensing) 

Dimensions (WxHxD) 

80mm x 93mm x  60mm (3.15” x 3.66” x 2.362”) 

Weight  

125g (4.3oz.) 

Mounting 

Either onto a 35mm DIN-rail or screw- mounted. 

Содержание Unitronics EX-A2X

Страница 1: ... and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of this equipment as defined by the European directives for machinery low voltage and EMC Only a technician or engineer trained in the local and national electrical standar...

Страница 2: ...Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during i...

Страница 3: ...PLC to the EX A2X Use the communication cable to connect the module s PLC expansion port to the PLC Take care to connect the correct cable The connectors of this cable are housed in yellow insulation Note that one end is marked To PLC and the other To Adapter insert accordingly The module is supplied with a 1 meter cable part number EXL CAB100 Other cable lengths are also available Use only an ori...

Страница 4: ...e turning on the power supply Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Double check all the wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12AWG wire 0 13 mm 2 3 31 m...

Страница 5: ...same power supply The EX A2X and the OPLC must be turned on and off simultaneously POWER 0V V EX A2X Technical Specifications I O module capacity Up to 8 I O modules can be connected to a single adapter Power supply 12VDC or 24VDC Permissible range 10 2 to 28 8VDC Max current consumption 650mA 12VDC 350mA 24VDC Typical power consumption 4W Current supply for I O modules 1A max from 5V see Note 1 G...

Страница 6: ...utput on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be addressed as I 67 67 32 2 16 3 Output 4 located on expansion module 3 in the system will be addressed as O 84 84 32 3 16 4 EX90 DI8 RO8 is a stand alone I O module Even if it is the only module in the configuration the EX90 DI8 ...

Отзывы: