Klimawent STRONG-5000-S Скачать руководство пользователя страница 20

                                   20 

                                                     

filtering unit

  STRONG

-

5000

-

S

        

                      

 

       

15.10.2019

 

   

 

 inputs 

DI4

DI5

DI6

 response to the rising edge  (emulation of the elevation keyboard)   

 inputs 

DI8

 and 

DI9

 response to the level (the functions of inputs are activated from the  

   level of the controller menu) 

 inputs 

DI0-DI3

DI7

 are alarm inputs

  

(masking of the alarms for 

DI0-DI3

 activated from  

   the level of the controller menu) 

 

Digital outputs 

 

All digital outputs are relay outputs. 

DOUT0 

separable output of the control system of the fan contactor 

DOUT1 

switchable output, collective signal of the alarm 

DOUT2  

switchable output, indication of the fan work 

DOUT3  

switchable output, indication of the filters regeneration  

DOUT4 

switchable output, indication of the correct supply 

of the

 board 

and of the

 elec- 

tromagnetic valves 

DOUT5 

switchable output,

  

control with the cooling  or heating in the function of mode, 

applied temperature  and  temperature  measured by the sensor on the board  
of the controller 

(Screen 

MODES 2/6

, Screen 

SETTINGS 6/6

Screen

 INPUTS

  

OUTPUTS 1/3

 and 

3/3

 

 
States of emergency 

(

alarm

)

 

The alarm from the inputs of the pressure controls

 (pressostats) 

DI0

 up to 

DI3

 (additional signal- 

ling by means of 

H3 

lamp): 

Appearance of any of the alarms 

ALPR1 

– 

ALPR4 

activates the alarm lamp 

H3

 lighting pulsati- 

vely, as well as switches on the acoustic signal (buzzer). 
 
To confirm the alarm, press the 

S2

 (

STOP

) button. The occurrence of the alarm blocks the sys- 

tem function 

– until the alarm stops.

  

After the alarm reason is fixed

, press the 

S2

 (

STOP

) button 

one more time 

– this will delete the 

H3 

lamp. 

 
In case of the adjusted parameter {

Cons. STOP = ON

}

 

the alarm 

can 

be confirmed

, and 

subse- 

quently deleted by means of the input 

DI5

 

CAUTION

: The activated alarms 

ALPR1

 

– 

ALPR4

  can be blocked by a parameter {

ALPR akt. 

=

 NIE

} on the Screen 

MODES 4/6

 

The alarm from the input  

(

that confirms the function  of the motor disconnector

– 

addi- 

tional signalling by means of H1

): 

All the time, the system controls the status of the disconnector of the fan motor.  In case of the  
signal of contact opening  

– occurs an immediate 

interruption of the system 

function. The alarm 

is signalised by the 

H1

 lamp lighting in blinking.   

Whereas, when the alarm 

appears

 

on the con- 

troller display (on the 

Master Screen

– a message 

ALRS

 emerges. 

The 

ALRS

 alarm activates the 

H3

 alarm lamp  lighting pulsatively.  The alarm has to be confir- 

med with the button 

S2 

(

STOP

). The alarm causes blockage of the system, until the alarm dis-

appears. 

After the alarm reason has vanished,

  press the 

S2 

(

STOP

) one more time  

–  this will 

switch off the lamp 

H3

In case of the adjusted

 parameter 

CONS. STOP 

=

 ON

 the alarm can be confirmed, 

and subse

quently it can be deleted with input 

DI5

 
The alarm indicating the lack of supply of the electro-valves  

(

additional signalling with  

H3

).

 

The signal controlling the correctness of power supply 

24VAC 

is for operating the electromag- 

netic valves.

 

The controller indicates on display

 

the

 lack 

of

 supply

  

in

 case when for example the  

fuse is burned out. 
 

 

Содержание STRONG-5000-S

Страница 1: ...nt klimawent com pl www klimawent com pl 804U59 STRONG 5000 S 01 10 2019 EN Contents 1 Introductory Remarks 2 2 Application 2 3 Reservations of Producer 2 4 Technical Data 3 5 Structure and Function 4...

Страница 2: ...rective of the European Parliament and of the Council with regard to ecodesign requirements for fans driven by motors with an electric input power between 125W and 500 kW Journal of Laws L No 90 of 06...

Страница 3: ...ining viscous and aggressive contaminants as this would cause damage of the filters or forwarding the madia of temperature exceeding 60 C H Sources of ignition e g glowing parts cigarette butts embers...

Страница 4: ...nd electromagnetic valves hopper discharge underneath the housing waste container connected with the hopper discharge equipped with castor wheels four legs as a base for the housing connection fitting...

Страница 5: ...5 01 10 2019 filtering unit STRONG 5000 S Fig No 2 STRONG 5000 S Structure and dimensions...

Страница 6: ...e the appliance is protected with foil and placed on a transport pallet Having removed the protective foil put the filtering unit exactly on the foreseen place of use it is advised to use a fork lift...

Страница 7: ...nt that the locks can be bent fully aside and User can open the door widely to the right angle Insert the subsequent filter cartridges onto the slide guides and push them to the wall of the electro va...

Страница 8: ...lamp lights continuously to the moment when the failure is fixed Press the S2 STOP button one more time to stop the H3 light yellow lamp H4 signalling of the regeneration of the filters green button S...

Страница 9: ...rom short circuit overload and not complete phases function effects over current disconnector F1 protection for the transformer circuit and of the controller over current disconnector F2 protection fo...

Страница 10: ...FT higher level of the menu How to change the editable parameter OK marking illumination of the parameter RIGHT LEFT displacing the cursor between the fields that are possible to be marked UP DOWN cha...

Страница 11: ...ation stage of the filters STOP the device is being stopped after the alarm vanishes operator needs to delete it ALPR1 alarm signal of low pressure 1 ALPR2 alarm signal of low pressure 2 ALPR3 alarm s...

Страница 12: ...1 Sub menu of the settings COMMUNICATION 1 The function is not active in the program version 2 0 up to 2 2 INPUTS OUTPUTS Screen INPUTS OUTPUTS Sub menu of the settings INPUTS OUTPUTS Day Tu hour 10 0...

Страница 13: ...activated initial regeneration SWF TEMP REG NONE AL24V akt OFF Screen MODES 2 6 TEMP REG NONE I HEAT I COOL NONE disconnected the controlling with output OUT5 in function of temperature HEAT activated...

Страница 14: ...the status at inputs DI0 up to DI3 ALPR akt OFF Cons START OFF Screen MODES 4 6 ALPR AKT OFF and ON OFF blocking of the occurring alarm ALPRi at the inputs DI0 up to DI3 ON alarm ALPRi at the inputs D...

Страница 15: ...ve Input DI6 fulfils the same function as the button FILTER S3 on the elevation console DI8 START OFF DI8 STOP OFF Screen MODES 6 6 DI8 START OFF I ON OFF blocking of the possibility of activation by...

Страница 16: ...ectro magnetic valves during the status SWF Lsekwen Lon 0 9 cycles Lsekwen Lon number of sequences 4 cycles of pulsing each Time T12 0 5s Ton PowPause 10s Screen SETTINGS 2 6 Time T12 0 1 5 sec Time T...

Страница 17: ...lectromagnetic valves StanZas 24V state of the fuse of the transformer 24VAC of the power supply of the electromagnetic valves Time T22 0 5s Lsekwen Loff 02 Screen SETTINGS 4 6 Time T22 1 99sec Time T...

Страница 18: ...ro valves AktPoziomWe LO I HI AktPozimWe the level of signal from the input of pressure control is activated Tset 21 0 C Screen SETTINGS 6 6 Tset 10 60 Tset the applied temperature for the controlling...

Страница 19: ...atus of the analogue input 0 10V TO status of the outputs of impulses T1 T4 Tb 25 5 0 C StanZas 24 OK Screen INPUTS OUTPUTS 3 3 Tb measuring of temperature on the controller StanZas 24V the state of t...

Страница 20: ...larm blocks the sys tem function until the alarm stops After the alarm reason is fixed press the S2 STOP button one more time this will delete the H3 lamp In case of the adjusted parameter Cons STOP O...

Страница 21: ...Close the dewatering valve when exclusively clean and dry air is discharging from the installation The construction of the extraction fan and motor guarantees the work of the unit without the routine...

Страница 22: ...MPa Repair should be carried out after the fan is switched off and the device is disconnected from the power supply mains 11 Transport and Storage STRONG 5000 S filtering unit has to be transported i...

Страница 23: ...energy related products Journal of Laws L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Par liament and of the Council with rega...

Страница 24: ...24 filtering unit STRONG 5000 S 15 10 2019 NOTES...