Filtering unit

 

HARD-1000-S

 

16.10.2019 

 

 

ASSEMBLY  AND  STARTUP 

Before the use, install the ERGO LUX extraction 
arm or a hose on the HARD-1000-S filtering unit.  
For 

this 

purpose 

are 

implemented 

two 

connections 

Ø125  mm  or  one  connection  Ø160 

mm  (see  Fig.  No.3).    After  suitable  connection 
fitting pieces are installed, it is possible to fasten 
flexible hoses. 
 
Flexible  hose should  be fastened by means of a 
DC  coupling. 

Brackets,  ERGO  LUX  extraction 

arms  and  hoses  do  not  belong  to  the  acces-
sory  set  of  the  filtering  unit

  (they  should  be 

ordered as additional equipment).

 

 

Subsequent steps before the startup

             Fig. No.3  

–  Connections  

1

.  remove two cover discs from the device top; 

2

.  slide out the 

HEPA

 high-efficiency filter and the 

FK

 pocket filter; 

3

.  screw out (inside the filtering unit) the blocking bolts of the activated carbon cassette (the  wrench is enclo-

sed to the delivery); 

4

.  slide out the cassettes with activated carbon; 

5

.  fill  out  the  cassettes  with  activated  carbon    (delivered  along  with  the  filtering  unit),  up  to  the  level 

–  of 

approx.10  mm  below  the  upper  edge  of  the  cassette;  important  is  that  the  activated  carbon  is  distributed 
evenly along the side walls of the cassettes and gently pressed down to make it more dense; 

6

.  load the cassettes  back into the device. Handle  with care, as the  fragile sealings would not get  damaged 

while  sliding  the  cassettes  in. Mind  that  the  carbon  would  not  get  displaced  aside,  showing  empty  places 
within the cassettes; 

7

.  insert back the 

HEPA

 high-efficiency filter and the 

FK

 pocket filter; 

8

.  close the covers. 

At that point, the filtering unit is ready for operation. To start the device connect the plug into socket 230V/50Hz 
and turn on the motor protective switch. 

 

 

 

Fig. No.4  

–  HARD-1000-S  –  Connection diagram  

Содержание HARD-1000-S

Страница 1: ...ND STARTUP 4 OPERATIONAL USE 5 TROUBLESHOOTING GUIDE 6 MAINTENANCE AND REPAIR 6 OCCUPATIONAL HEALTH AND SAFETY 6 TRANSPORT AND STORAGE 7 TERMS OF WARRANTY 7 DECLARATION OF CONFORMITY 8 16 10 2019 Prod...

Страница 2: ...60204 1 2018 12 Safety of machinery Electrical equipment of machines Part 1 General requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from being reached by up...

Страница 3: ...ssette with granulated activated carbon weight 20 kg carbon is delivered in bulk two pressure controls pressostats activating the signalling lamp upon excessive flow resistance of the pocket filter an...

Страница 4: ...screw out inside the filtering unit the blocking bolts of the activated carbon cassette the wrench is enclo sed to the delivery 4 slide out the cassettes with activated carbon 5 fill out the cassette...

Страница 5: ...rs H3 yellow lamp signalizes the replacement necessity of the pocket filter upon limit resistance of the filter 500 Pa the lamp is coordinated with B1 pressure control pressostat H4 yellow lamp indica...

Страница 6: ...H1 lamp is on 3 the fan flow capacity decreases high efficiency filter is excessively replace the high efficiency filter whereby the H3 lamp is on polluted 4 unpleasant smell odour is percep activate...

Страница 7: ...otected from overturn knocking down and uncontrolled displacement slide Store the device in dry rooms and areas of efficient ventilation TERMS OF WARRANTY The period of warranty for the purchased devi...

Страница 8: ...for use within certain voltage limits Official Journal EC L96 of the 29 03 2014 2009 125 EC ErP Directive of the European Parliament and of the Council of 21 October 2009 establishing a framework for...