 Air Conditioner Service Manual 

                                                

 

     

Room Temp. 

Set TEMP. 

1.8

 

Set TEMP. 

1.8

 

     

Time  

More than 2 min 

More than 2 min

More than 2 min

More than 2 min 

More than 2 min

Indoor Fan 

Set Speed 

Set Speed 

Set Speed 

Set Speed 

Set Speed 

C

  ompressor 

ON 

OFF 

ON 

OFF 

ON 

Outdoor Fan 

ON 

OFF 

ON 

OFF 

ON 

 

4.  “DRY” Mode Operation 

(1)  The system for DRY operation used the same refrigerant circle as the cooling circle. 

(2)  When the system operates in DRY mode ,at first it operates in cooling mode at 

60.8℉

  or 

64.4℉

  for 3 minutes. 

And then, the system operates in cooling mode with low speed that regards the temperature of the room 

temperature sensor reads decrease 35.6

  as the set temperature. During the course of this, the fan speed 

set operation is failing but the vane motor can be controlled. 

5.  “HEATING” Mode Operation (Only available for Heat Pump) 

(1)  When the HEATING mode is selected without setting temperature, the system will set the temperature at 

73.4℉

  automatically with the AUTO FAN speed. 

(2)  When  selecting  the  HEATING  mode  operation,  the  system  will  operate  according  to  the  setting  by  the 

remote controller and the operation is as following: 

 

      

Set Temp. 

1.8

 

Set Temp. 

1.8

 

Room Temp.     

 

Time  

More than 2 min 

More than 2 min

More than 2 min

More than 2 min 

More than 2 min 

Compressor  

ON 

OFF 

ON 

OFF 

ON 

Outdoor fan 

ON 

OFF 

ON 

OFF 

ON 

 

(3)  In HEATING mode, the indoor fan motor speed is controlled by Cold Air Prevention Control. 

(4)  Cold Air Prevention Control 

The function is intend to prevent cold air from being discharged when the heating operation starts or 

when defrosting. 

The indoor fan speed will be controlled as following. 

The vane angle is at the angle C(100

°

). 

  

                            Set Speed               SetS

  peed 

                    

                              

9 3 . 2

℉ 

                   

        Low Speed

 

                                                     

80.6℉ 

                  

                               Low Speed

 

                   

          7 7

℉ 

                   

        Stopt he fan 

                                                   

73.4

℉ 

                                                 Stopt he fan 

 

During the heating operation, if the compressor stops that it will adjust the indoor fan speed, after 30 

seconds to stop the fan.

 

T

emperature

raise

T

emperature

d

rop

Содержание KSWS009-H113

Страница 1: ...ls KSWS009 H113 KSWS012 H113 KSWS018 H213 KSWS024 H213 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 5 3 OPERATION DETAILS 9 4 ELECTRICAL SCHEMATIC DIAGRAM 12 5 EXPLOSION VIEW 14 6 PARTS LIST 17 WALL MOUNTED SPLIT TYPEAIR CONDITIONERS CONTENTS ...

Страница 2: ...le for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior notice The accurate specifications are presented on the nameplate label How to order spare parts To have your order filled promptly and correctly please furnish the ...

Страница 3: ...e controller 6 2 5 3 7 1 1 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time after the remote controller replace batteries or is energized the arrowhead will flash on the front of Heat or Cool on LCD of the remote controller User can preset the remote controller type depending...

Страница 4: ...fan OFF when the indoor pipe temperature is 122 Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is 143 6 Compressor ON when the indoor pipe temperature is 118 4 2 I Feel Mode Operation 1 When the I Feel mode is selected the operation mode and initial set temperature are determined by the initial room temperature at start up of the operation ...

Страница 5: ...is selected without setting temperature the system will set the temperature at 73 4 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the setting by the remote controller and the operation is as following Set Temp 1 8 Set Temp 1 8 Room Temp Time More than 2 min More than 2 min More than 2 min More than 2 min More than 2 min Compr...

Страница 6: ... the IPT is less than 95 for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT is less than 73 4 or from the last time of defrosting operation is 50 minutes or more interval When the defrosting operation time on this condition exceeds 10 minutes it will terminate When the JC isn...

Страница 7: ...et temperature will be raised by 1 8 1 hour later and by 3 6 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 8 1 hour later and 3 6 2 hour later After the System operates in SLEEP mode for 8 hours it will stop automatically 9 Fan motor control 1 Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency ...

Страница 8: ... the standard position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished When the test run starts When the power supply turns ON 3 The auto vane changes as follows by pressing the VANE CONTROL button 4 VANE AUTO mode In vane auto mode the microprocessor automatical...

Страница 9: ...ssed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor electric control PCB The AUTO RESTART function sets to work the m...

Страница 10: ...l of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the compressor is stopped the outdoor fan and indoor fan is stopped and display the failure The system doesn t receive the signal of remoter controller except the signal of shut it off d Display Of The Co...

Страница 11: ...Air Conditioner Service Manual Wiring diagram Model KSWS009 H113 KSWS012 H113 Indoor unit Outdoor unit ...

Страница 12: ...Air Conditioner Service Manual Wiring diagram Model KSWS018 H213 Indoor unit Outdoor unit ...

Страница 13: ...Air Conditioner Service Manual Wiring diagram Model KSWS024 H213 Indoor unit Outdoor unit ...

Страница 14: ...Air Conditioner Service Manual Explosion view Model KSWS009 H113 KSWS012 H113 Indoor unit 15 6 11 12 8 10 9 7 5 4 3 2 18 17 16 22 21 19 20 24 23 25 26 27 1 14 13 ...

Страница 15: ...Air Conditioner Service Manual Explosion view Model KSWS018 H213 Indoor unit 24 14 13 25 22 20 19 21 23 17 16 15 18 2 3 1 5 6 4 7 9 10 12 11 8 ...

Страница 16: ...Air Conditioner Service Manual Explosion view Model KSWS024 H213 Indoor unit 13 14 26 25 27 22 23 19 18 17 16 21 20 24 2 1 3 5 7 6 4 15 9 10 12 11 8 ...

Страница 17: ...lay PCB 1 11 Display PCB Box 1 12 Air Filter 2 13 Front Panel 1 Option 14 Display PCB Cover 1 15 Power Supply Cord 1 16 Vane 1 17 Drainage Hose 1 18 Cable Clamp 1 19 Main PCB 1 20 Electrical Box 1 21 Vane Motor 1 22 Sensor Holder 1 23 Indoor Motor 1 24 Indoor Motor Clamp 1 25 Transformer 1 26 Indoor Sensor Assembly 1 27 In And Out Pipe Fixer 1 28 Remote Controller 1 Not shown in Explosion view 29 ...

Страница 18: ... 11 Display PCB Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB cover 1 option 15 Vane 1 16 Drainage Hose 1 17 Vane Motor 1 18 Sensor Holder 1 19 Main PCB 1 20 Indoor Motor Cover 1 21 Indoor Motor 1 22 Electrical Box 1 23 Transformer 1 24 Indoor Sensor Assembly 1 25 In And Out Pipe Fixer 1 26 Remote Controller 1 Not shown in Explosion view 27 Remote Controller Support...

Страница 19: ...PCB Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB Cover 1 15 Electrical Box Cover 1 16 Vane A 1 17 Vane B 1 18 Drainage Hose 1 19 Cable Clamp 1 20 Vane Motor 2 21 Sensor Holder 1 22 Main PCB 1 23 Indoor Motor Cover 1 24 Indoor Motor 1 25 Electrical Box 1 26 Transformer 1 27 Indoor Sensor Assembly 1 28 Remote Controller 1 Not shown in Explosion view 29 Remote Control...

Страница 20: ...Air Conditioner Service Manual Explosion view Model KSWS009 H113 Outdoor unit 1 25 2 3 4 20 21 22 23 24 19 18 16 15 14 17 5 7 6 8 9 13 12 11 10 ...

Страница 21: ...Air Conditioner Service Manual Explosion view Model KSWS012 H113 Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 ...

Страница 22: ...Air Conditioner Service Manual Explosion view Model KSWS018 H213 Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 ...

Страница 23: ...Air Conditioner Service Manual Explosion view Model KSWS024 H213 Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 ...

Страница 24: ...uard 1 10 Capillary Assembly 1 11 Compressor And It Accessories 1 12 Discharge Pipe 1 13 Suction Pipe 1 14 Base 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Right Plate 1 19 Electrical Box Cover 1 20 Capacitor Strip 1 21 Cable Clamp 1 22 Terminal 1 23 Compressor Capacitor 1 24 Fan Motor Capacitor 1 25 Electrical Parts Box 1 26 Base Carton 1 Not shown in the Explosion view 27 C...

Страница 25: ...4 way Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor Base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor cable Clamp 1 20 Outdoor cable Clamp 1 21 Outdoor terminal 1 22 Outdoor Fan Motor Capacitor 1 23 Compressor Capacitor 1 24 Compressor capacitor Strip 1 25 Outdoor electrical Parts Box 1 26 Capillary Assembly 1 27 Parti...

Страница 26: ... And It Accessories 1 12 Discharge Pipe 1 Optional 13 Suction Pipe 1 Optional 14 Outdoor Base 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Right Plate 1 19 Electrical Box Cover 1 20 Capacitor Strip 1 21 Outdoor Cable Clamp 1 22 Outdoor Terminal 1 23 Compressor Capacitor 1 24 Fan Motor Capacitor 1 25 Outdoor electrical Parts Box 1 26 Partition plate 1 27 Base Carton 1 Not shown...

Страница 27: ... way Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor Cable Clamp 1 20 Outdoor Cable Clamp 1 21 Outdoor terminal 1 22 Fan Motor Capacitor 1 23 Compressor Capacitor 1 24 Capacitor Strip 1 25 Outdoor Electrical Parts Box 1 26 Capillary Assembly 1 27 Partition plate 1 28 Outd...

Страница 28: ......

Отзывы: