Function 

 
The Wrist strap-cables are plugged into the measuring instrument. Then press and hold the Test 
-Plate on the appliance with a finger.  
When starting the measurement, a short acoustic signal sounds.  
It is tested whether the resistance values are within the lower and upper limits.  
If the resistance values are between the lower and upper limits, a short acoustic signal sounds 
and the green LED lights up.  
If the resistance values is outside of the lower or upper limit, no acoustic signal sounds, only the 
appropriate red < or > LED lights up.  

Expiry of  wrist strap test  

 

 

If the  „<“ LED shines the resitor in the cable is defect.  Exchange the cable ! 

If the „>“ LED shines the resitor in the cable ist o high or the wrist strap is defect or dirty. In this 
case test the cable separat 

  

Expiry of cable test 

 

 

 

If the green LED shines the wrist starp is o.k.

Wait until the result appears

Press and hold the plate with your finger

Connect the wrist strap cable to one of the lower connection sockets 

Put on the wrist strap

Shines the > LED again excange the cable

Shines the o.k. LED the cable is ok

Hold it until the result appears

Press the snap faster of the cable on the plate

Disconnect the cable from the wrist strap

 

 

Содержание WST 50

Страница 1: ...MANUAL Wrist Strap Tester WST 50 performance test for Electrostatic Wrist Straps ...

Страница 2: ... The WST 50 is a reliable and advantageous solution for this The appliance is portable and because of its battery power employable everywhere Specific feature The setting of the limits and the calibration can be done by the customer himself very simply The limits values can be opposed by external resitors Doing this with calibrated resitors it is also a calibration of the instrument By changing th...

Страница 3: ...g Power supply 4 x Mignon AA Alkaline Batteries Alternativ Plug power supply 7 5V 300mA with 4 x Mignon NiMH Batteries Display 1 LED 8mm green 3 LEDs 5mm red 1 Buzzer Principle of Measurement Current Voltage Converter Measuring voltage 20V 5 Connection Power socket and 3 5mm Socket Limits The limits are separate adjustable for the wrist strap test and the shoe test Lower Limit 0 2MOhm Upper Limit ...

Страница 4: ... sounds only the appropriate red or LED lights up Expiry of wrist strap test If the LED shines the resitor in the cable is defect Exchange the cable If the LED shines the resitor in the cable ist o high or the wrist strap is defect or dirty In this case test the cable separat Expiry of cable test If the green LED shines the wrist starp is o k Wait until the result appears Press and hold the plate ...

Страница 5: ...er limits are possible without extra charge The limits can be changed by the customer anytime see adjustment of the limits Evaluation lower limit Calibrated Value LCV LED Calibrated Value LCV 10 LED o k upper limit Calibrated Value UCL 10 LED o k Calibrated Value UCL 10 LED Exchange Batteries The appliance possesses battery supervision If the battery voltage is below the limit the red low Battery ...

Страница 6: ... Plug power supply Important Before using the power supply replace the alkaline batteries with rechargeable NiMH types WST 50 RE Reference Resitor modul RE 50 Reference Resitor ypu need one fort he lower and one for the upper Limit each with Calibration certification The reference Resitor is mounted in a 3 5mm Plug The standard values are A lower Limit 750kΩ B upper limit 35MΩ We can deliver each ...

Страница 7: ...LED shines and the buzzer appears for 1 second LED shines Connect the resitor modul for the upper limit into the 3 5mm socket Press button H shortly If o k the green LED shines and the buzzer appears for 1 second The new limit are stored By pressingb the plate the instrument will switch off Error If a connected calibration resistor is out of these ranges all 6 red LEDs flash 5 x Error Calibration ...

Страница 8: ...nce In order to return to the normes the calibrated resistors can be calibrated by the manufacturer annually With these calibrated resistors all appliances of the customer can then be calibrated again Suggested calibration cycles of the Reference Resitor moduls annual 2016 Kleinwächter GmbH Kleinwächter GmbH Krummattstraße 9 79688 Hausen Germany Tel 49 7622 6863 0 Fax 49 7622 6863 40 www kleinwaec...

Отзывы: