![Kleenmaid FEG 900 X Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/kleenmaid/feg-900-x/feg-900-x_instructions-for-use-manual_1976849034.webp)
34
PRIMARY AIR ADJUSTMENT OF THE BURNERS
By operating the screw “M”, reset the air adjuster “A” according to the instructions (see
“Table for the choice of the injectors”), where the distance between injector and air adjuster
is recommended (in mm).
Before refixing the hob top, replace the burners on their sites and light them in order to check
whether the flames are correct, as per the specifications given below.
In case of incorrect flame, lift or lower the air adjuster.
IMPORTANT: when replacing the burners on their sites special attention has to be
paid in order not to exchange the housing of the two small burners shown in figure 13
at page 19.
MINIMUM BURNER SETTING ADJUSTMENT
In the minimum position the flame must have a length of about 4mm and must remain lit even
when turned quickly from the maximum position to minimum.
The flame adjustment is done in the following way:
[
Turn on the burner.
[
Turn the tap to the MINIMUM position.
[
Take off the knob.
[
With a small flat screwdriver turn the screw “F” (fig. 34) to the correct regulation.
Normally for LPG-Propane, the regulation screw is tightened up.
M
A
J
Fig. 33
F
Flame faulty in
primary air
long, yellow and trembling
CAUSE
air regulating tube,
too closed
Flame correct
clear interior blue cone
correct distance
of the tube
Flame with excess
primary air
short and sharp
too blue interior cone
tending to detach
air regulating tube,
too open
Fig. 34
Содержание FEG 900 X
Страница 1: ...DUAL FUEL COOKER Instructions for Use and Warranty Details Model FEG 900 X THE WORLD S BEST ...
Страница 25: ...25 Fig 19 ...
Страница 37: ...37 ...
Страница 38: ...38 ...