KLAY-INSTRUMENTS PERAMIC Скачать руководство пользователя страница 2

 
H/US/PERAMIC/05-2018/00   

 

 

 

Klay Instruments 

Page 2/4 

 

WIRING 

The figure left shows the wiring connection of the PERAMIC.

 

The 2-wires must be connected to connectors 3 (-) and 4 (+).

 

In most circumstances the load should be placed in the negative  
side of the 2-wire loop, although this it is not necessary.

 

 

TEST FUNCTION 

Without interrupting the loop, the actual output (mA) of the transmitter 
can be measured by connecting a multimeter to 2 (+) and 3 (-). 

 

The transmitter must always be connected to earth. 

The  transmitter  must  be  connected  with  standard  two-wire  shielded 
cable. 

Do  not

  run  signal  wiring  in  open  trays  with  power  wiring,  or 

near  heavy  electrical  equipment  (Frequency  controllers  or  heavy 
pumps). Shielding must always be connected at the side of the power 
supply. In case the mounting position is already connected to ground 
(by tank or pipe line) do not connect the instrument to ground. 

Please 

ensure  that  the  instrument  is  not  connected  to  ground  twice  to 
prevent the occurrence of an Earth loop.

 

 

Reversing the polarity will not damage the transmitter, but the 
transmitter will not function until the wires are properly connected. 

 

POWER SUPPLY / EXTERNAL LOAD

 

The minimum power supply is based on the total circuit resistance. 
The maximum permissible load (Ri max.) in case of 24 Vdc will be 600 
Ohm. By increasing the power supply, the external load can be higher,  
till 1200 Ohm / 36 Vdc. (see figure left). 
 

Ri max =

  

  Power Supply

  

-

 

13 Vdc 

(

min. power supply

)

20 mA

 

 

CALIBRATION

 

All transmitters are fully calibrated at the factory, to customer specified range. When no calibration is requested, 
the transmitter will be calibrated at the lowest span. It is advisable to recalibrate the transmitter after shipment. 

 

The calibration sequence is as follows:  
 1. 

The output of the transmitter must be set at 4 mA (Zero-potentiometer). 

 2. 

Air pressure in accordance with the process pressure must be applied to the test nipple. 

 3. 

The output of the transmitter must be set at 20 mA (Span-potentiometer). 

 4. 

Remove the air pressure. 

 5. 

Check if the output of the transmitter is 4 mA. (Otherwise repeat steps 1 till 4) 

 6. 

Install transmitter (See above).    

 7. 

The output must be set at 4 mA (Dependable on mounting position). 

 

COMPOUND RANGE (Combination overpressure and under pressure) 

For  example:  if  the  transmitter  is  adjusted  at   

–1.45  …+1.45  psi  the  output  of  the  transmitter  at  atmospheric 

pressure must be 12 mA. If not this must be corrected at 12 mA by turning the ZERO potentiometer. After this a 
test pressure of 100 mbar should be put on the transmitter and the output should show 20 mA. If not this must 
be set at 20 mA by turning the SPAN potentiometer. When the test pressure is removed the transmitter should 
show 12 mA at atmospheric pressure. If not the above sequence should repeated. 

 

INSTALLATION 

When mounting the PERAMIC, use the same principles as used for manometers (gauge). We recommend 
using shut-off valves and water trap pipes according to BS/DIN standards, especially on steam applications  
and those applications where the process temperature will be higher than 212°F. 

 

Содержание PERAMIC

Страница 1: ...C The PERAMIC has no oil filling system so the process pressure is applied directly to the ceramic pressure cell The voltage signal from the ceramic cell is connected directly to the Integrated Circuit that converts this signal into 4 20 mA Therefore the PERAMIC has a perfect linearity and is fully temperature compensated This means that various process temperatures have no effect on the accuracy ...

Страница 2: ...dc min power supply 20 mA CALIBRATION All transmitters are fully calibrated at the factory to customer specified range When no calibration is requested the transmitter will be calibrated at the lowest span It is advisable to recalibrate the transmitter after shipment The calibration sequence is as follows 1 The output of the transmitter must be set at 4 mA Zero potentiometer 2 Air pressure in acco...

Страница 3: ... mA Ci 1 nF Li 1 2 mH Pi 0 9 W 30 C Tamb 70 C 22 F Tamb 158 F All certifications are in compliance with IECEx scheme rules and the International Standards IEC 60079 0 2011 IEC 60079 11 2011 IEC 60079 26 2007 and IEC 17050 1 They are certified for use in hazardous areas by DEKRA B V DO NOT REMOVE THE SCREW COVER WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT FUNCTIONAL SAFETY SIL The device is certifi...

Страница 4: ...ater jets on the diaphragm take necessary steps to avoid this Guarantee will not be granted As soon as the wiring is brought inside through the PG9 Cable gland and connected to the terminal board make sure the cable gland is tightly fixed so that moisture cannot enter into the electronic housing Never remove the venting 3 because it is especially designed to prevent moisture from entering into the...

Страница 5: ...A 12ATEXQ0041 Issue 3 Delivered by the DEKRA Meander 1051 6825 MJ Arnhem The Netherlands Notified Body No 0344 Date February 12 th 2018 E Timmer Managing Director Klay Instruments B V Signature The marking of the equipment is as follows II 1G Ex ia IIC T4 Ga II means that the equipment has been built for use in surface industries and not in mines endangered by firedamp 1 equipment for use in Zone ...

Отзывы: