SPECIAL CONDITIONS FOR SAFE USE (as stated in the 

EC Type Examination Certificate SIRA 05ATEX2269X)

 

Conditions for Syrex IS-XN Beacon 

 
The  equipment  has  an  ingress  protection  rating  of  IP65. 

However, if it has been supplied without cable entry devices, 

then the user shall ensure that the devices that are fitted will 

provide  an  ingress  protection  that  is  appropriate  to  the 

environment in which it is installed i.e. IP20 or better. If only 

one of the two cable entries are used, then the unused entry 

'knockout' shall be  left intact or fitted with  a blanking  device 

that  ensures  ingress  protection  appropriate  to  the 

environment in which it is installed i.e. IP20 or better. 

 
The  equipment  shall  not  be  directly  installed in  any  process 

where its enclosure might be electro-statically charged by the 

rapid flow of a non-conductive media. 

 

4.2  Zones, Gas Groups and T Rating

 

The  Syrex  IS-XN  beacon  has  been  certified  EEx  ia  IIC  T4.   

When connected to  an  approved system it may  be installed 

in: 

 

 

Zone 0 

explosive gas air mixture 

 

continuously present. 

 

 

Zone 1 

explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

 

 

Zone 2 

explosive  gas  air  mixture  not  likely  to  occur, 

and if it does, it will only exist for a short time. 

 

 

Be used with gases in groups: 

  

 

Group 

propane 

 

Group 

ethylene  

 

   

Group 

hydrogen 

 

 

Having a temperature classification of: 

 

T1 

450ºC 

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

 

4.3  Ter and -  power supply 

Power is supplied to the beacon via ter and - which 

have maximum input safety parameters of: 

 

 

Ui 

28V 

 

Pi 

 

1.2W 

 

 

Ci = 0   

Li = 0 

 

Syrex  IS-XN  beacons  may  be  powered  from  ATEX  certified 

Zener  barriers  or  galvanic  isolators  certified  by  an  EC 

Approved  Body  which  have  output  parameters  equal  to  or 

less than 28V and 1,2W 

 

Up  to  three  Syrex  IS-XN  beacons  can  be  connected  in 

parallel  and  be  powered  from  a  common  barrier  or  isolator.   

Parallel  connection  of  beacons  will  significantly  reduce  the 

brightness of each device.  

 

The  maximum  permitted  cable  parameters  defined  by  the 

barrier or isolator certificate must not be exceeded. 

 

S

yr

ex

 IS

-X

N

 

B

ea

co

n

 +

   

-

2H

  1

H

   

Fl

as

R

at

e

Input Terminals

Flash Rate

Header Pins

'O' Ring Seal

 

 

Fig 1  Location of field terminals and controls. 

 

5. INSTALLATION 

In addition to the certification requirements shown in section 

4.2,  the  environmental  conditions  must  be  within  the  limits 

shown  on  the  product  specification.    The  beacon  enclosure 

provides IP65 protection and is suitable for installation in an 

exterior location if an appropriate sealed cable entry is used. 

Syrex  IS-XN  beacons  should  only  be  installed  by  trained 

competent personnel. 

 

5.1 Mounting

 

The Syrex IS-XN beacon may be secured to any flat surface 

by  inserting  two  mounting  screws  through  the  back  of  the 

round  base  (see  figure  2).  The  enclosure  provides  IP65 

protection and is suitable for installation in exterior locations 

provided  that  the  area  around  the  two  mounting  screws 

through the back of the base moulding has been sealed and 

that  suitable  cable  glands  with  the  required  IP  rating  have 

been  used.  The  lens  should  be  aimed  towards  the  area 

where maximum visibility is required. 

 

5.2  Installation procedure 

 

a.  Unscrew  the  beacon  unit  security  screw  and  remove 

the  beacon  section  from  the  base  by  turning  it  anti-

clockwise.  Ensure  that  the  ‘O’  ring  seal  remains  in 

place. 

  

b.  Remove  the  required  20mm  knockout  section(s) 

depending on system wiring and mount the base to a 

flat surface by inserting two screws through the back 

of the base.  

 

c.  Fit  the  required  number  of  20mm  cable  glands  or 

conduit  entries  into  the  base  and  connect  the  field 

wiring to the appropriate beacon terminals as shown 

in section 6 and Fig 1 of this manual.  

 

d.  Check that the ‘O’ ring seal is correctly located on the 

beacon  section  (see  Fig.  1)  and  insert  the  beacon 

section  into  the  base.  Push  it  fully  home  and  turn  it 

clockwise to align the mouldings before tightening the 

security screw. 

Fit mounting screws 

through base

20mm knockouts

 

 

Fig 2 Mounting Beacon Base. 