18 / 82
83000602.Ke
2.17.
Water quality
The following limit values must be adhered to, to ensure safe operation of the units:
Table 7: Water quality
Property /
component parts
Unit
Value range
Standard version
Value range
Non-ferrous metal-free version
pH value (20°C)
-
7-9
6-9
Saturation index
-
-0.2 < 0 < +0.2
-0.2 < 0 < +0.2
Conductivity
µS/cm
80-500
5-500
Water hardness
°dH
<5.6
<5.6
Carbonate
hardness
mol/m³
<0.5
<0.5
Total
bacterial
count
K/ml
<10,000
<10,000
Particle size
µm
< 250
< 250
Glycol
fraction
(AFN)
% by
vol
20-40
20-40
Oil fraction
% by
vol
0
0
Chloride (Cl-)
mg/l
<50
<50
Sulphate
mg/l
<50
<50
Nitrate
mg/l
<100
<100
Copper
mg/l
<0.1
<0.1
Iron
mg/l
<0.2
<0.2
Free
carbon
dioxide
mg/l
<20
<20
Manganese
mg/l
<0.1
<0.1
Ammonia
mg/l
<2
<2
Free chloride
mg/l
<0.5
<0.5
Sulphide
mg/l
<0.03
<0.03
The specified limit values must always be complied with in order to avoid blockaging of the plate
heat exchanger.
Furthermore, slime-forming bacteria must be prevented in the cooling water. If this is not possible,
KKT chillers can recommend or provide an appropriate inhibitor to remove the slime forming agents
on the basis of a biological water analysis carried out in advance.
Содержание vBoxX 10
Страница 1: ...Vario Line vBoxX 6 vBoxX 8 vBoxX 10 vBoxX 12 vBoxX 15 vBoxX 18 vBoxX 24 vBoxX 28 Instruction Manual ...
Страница 16: ...16 82 83000602 Ke ...
Страница 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Страница 66: ...66 82 83000602 Ke Status ...
Страница 67: ...67 82 83000602 Ke Parameters ...
Страница 68: ...68 82 83000602 Ke ...
Страница 69: ...69 82 83000602 Ke hidden ...
Страница 70: ...70 82 83000602 Ke ...
Страница 71: ...71 82 83000602 Ke ...
Страница 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...