Preparing for Installation 

Typical Wiring block diagram of the Power Inverter: 
 
 
 
 
 
 
 
 
 
 
12V Battery Bank: 

  The use of a deep cycle battery is highly recommended for power inverter application 

  For battery size, you need to identify what you wish to operate, and for how long. It is 

recommended that you purchase as much battery capacity as possible. See more on Battery 
Run Time in Section 4. 

 
DC Fuse or Circuit Breaker:   

  DC-rated fuse or DC-rated circuit breaker connected along the DC positive line is required. 

  For 1000W Unit, select a fuse or circuit breaker with a minimum of 150 Adc 

  For 2000W Unit, select a fuse or circuit breaker with a minimum of 300 Adc 

  For 3000W Unit, select a fuse or circuit breaker with a minimum of 450 Adc 

  Based on the size of your 12V Battery Bank, determine the overall short circuit current rating of 

the battery bank from the battery manufacturer. The fuse or circuit breaker chosen has to be 
able to withstand the short circuit current that may be generated by the battery bank 

  For Marine application, the over-current protective device needs to be installed within 7 inches 

(17.8cm) from the battery positive terminals. 

 
DC Disconnect Switch: 

  Select a DC Disconnect Switch with the same or higher rating of the selected fuse or circuit 

breaker. 

  The DC Disconnect Switch is used to disconnect the DC power between the unit and the battery 

bank during service, maintenance or trouble shooting. 

 
DC Input Cable Size: 

  All DC cables require insulated multi-strand low resistance cable. 

  The DC cables must be copper and must be rated 105

Ԩ

 minimum. 

  For 1000W Unit, use minimum #2 AWG wire with maximum cable length of 5 feet. 

  For 2000W Unit, use minimum #2/0 AWG wire with maximum cable length of 5 feet. 

  For 3000W Unit, use minimum #4/0 AWG wire with maximum cable length of 5 feet. 

Important: Use of smaller gauge cable or longer cable length may cause the inverter to 
shutdown under heavy load and may also melt the cable insulation and catch fire and can result 
in death or serious injury. 

 
Grounding Cable Size: 

Important: The unit is grounded through the ground stud located near the DC Input terminal and 
the chassis of the unit has to be grounded properly before use. 

  For Marine application, the DC grounding cable size may be one size smaller than the minimum 

size conductor required for the DC current-carrying conductors and the conductor is no smaller 
than #10AWG.  

  For Recreational Vehicle or Caravan application, the unit has to be grounded to the vehicle 

chassis with a minimum #8 AWG copper conductor. 

 

Inverter with 

Transfer Switch 

Unit 

DC Disconnect 

Switch 

DC Fuse or 

Circuit Breaker 

 
 
12 V Battery Bank 
 
 

 

AC Output 

Ports & 

USB Output  

 

AC Input 

 

AC Input 

Source 

Содержание SWXFR1210

Страница 1: ...Sinewave Inverter with Transfer Switch 1000W 120V SWXFR1210 2000W 120V SWXFR1220 3000W 120V SWXFR1230 1000W 230V SWXFR1210i 2000W 230V SWXFR1220i Owner s Manual...

Страница 2: ...arm or serious injury Product Numbers 120V model SWXFR1210 Sinewave Inverter 1000W with Transfer Switch US Socket NEMA 5 15 SWXFR1220 Sinewave Inverter 2000W with Transfer Switch US Socket NEMA 5 20 S...

Страница 3: ...Page 3 Table of Contents 1 INTRODUCTION 4 2 PRODUCT DESCRIPTION 5 3 INSTALLATION 5 4 UNIT OPERATION 10 5 FEATURE SETTING 12 6 TROUBLESHOOTING 14 7 SPECIFICATIONS 15 8 WARRANTY 16...

Страница 4: ...g using and servicing the battery connected to the inverter Wear eye protection and gloves Avoid touching your eyes while using this unit Keep fresh water and soap on hand in the event battery acid co...

Страница 5: ...tems list below Inverter with transfer switch base unit with detachable Remote Panel Remote Panel Cable Owner s Manual Rating Series Model No Inverter Transfer Switch AC Output SWX 1210 1000W 30A 15A...

Страница 6: ...Output Status Indicator Display On Off button Select button AC Output Port 1 AC Wiring Compartment AC Output Port 2 3 AC Output strain relief AC Ground AC Input strain relief AC Input port USB Output...

Страница 7: ...selected fuse or circuit breaker The DC Disconnect Switch is used to disconnect the DC power between the unit and the battery bank during service maintenance or trouble shooting DC Input Cable Size A...

Страница 8: ...nnect Switch or disconnect the DC input cables to disconnect the DC power from the battery before working on any circuits connected to the unit Failure to follow these instructions can result in death...

Страница 9: ...AC compartment cover Model SWXFR1210 SWXFR1220 SWXFR1230 SWXFR1210i Series SWXFR1220i Series AC Input Branch Breaker 30A 16A Connect the AC Input L LIVE or H HOT wire between the unit s AC Input port...

Страница 10: ...ower to the unit Switch the AC Branch circuit breaker to ON to provide AC Input power to the unit The LED on display will turn on If AC input source is available Status LED turns green This indicates...

Страница 11: ...h button function during normal operation A beep sound will occur every time when the Power or Select button is triggered Power button function Turns inverter On Off during Battery Mode Press and hold...

Страница 12: ...imates for reference based on using different battery bank sizes Actual run times may vary Important Power Drain From DC Battery Bank Please noted that when the SWXFR1230 is running in AC Bypass mode...

Страница 13: ...Vdc Under voltage alarm recovery 12 3 Vdc Under voltage shutdown 11 8 Vdc Under voltage recovery 12 6 Vdc Alarm Setting AL0 Fault and warning audible alarm is disabled Display panel only shows error c...

Страница 14: ...ew Understanding the Error Codes in section 4 Problem Symptom Solution The unit is off Turn unit ON by following the instruction in Section 4 to turn unit ON No output voltage Status LED is off No pow...

Страница 15: ...Output Waveform Sinewave 3 THD Nominal DC Input Voltage 12 5 VDC No Load battery draw 1 5 ADC DC Input Voltage operating range 10 5 15 5 VDC Under Voltage Alarm 11 0 12 1 VDC Under Voltage Alarm Recov...

Страница 16: ...blems with your unit please contact our customer service department at info kisaetechnology com or Phone 1 877 897 5778 before returning product to retail store After speaking to a customer service re...

Отзывы: