Power/Select” button for 5 second to enter Load Sense select mode, display shows current 
setting (“LS0” = Load sense is disable, “LS1” = Load Sense is disable). Press “Power/Select” 
button once to change setting. The unit will automatically exit the select mode after 5 seconds. 

6. TROUBLESHOOTING 

To troubleshoot the unit, please note the error code displayed on the main unit and review 
“Understanding the Error Codes” in section 4. 

Problem Possible 

Cause/Condition 

Solution 

The unit is off. 

Turn the unit ON (Press and hold the “Power/Select” 
button for a second until a beep is sounded) 

No AC Output. All 
the LEDs and the 
display are off. 

No power coming into unit. 

Check if the DC Fuse or the DC Disconnect switch (if 
installed) is either blown or turned OFF. 

Check error code on display 

Verify the error condition and make correction 

No AC Output. 
Status LED is in 
Amber 

GFCI on 120V model 
(SW2420) is tripped 

Check load for Ground Fault and reset the GFCI 

AC Output is 
turning ON and 
OFF every few 
seconds 

Load Sense function is 
enabled and Load connected 
to unit is less than the 
threshold setting. (<10W) 

Disable Load Sense function by changing the unit 
setting or increase the AC load connected to unit to 
>10W 

 

7. SPECIFICATIONS 

Note: Specifications are subject to change without notices. 

True Sine Wave Series 

Specification 

SW2420 SW2420i 

-EU,UK,AU 

Inverter 

  AC Output Power 

2000W 

  AC Output Current 

16.7A 

8.7A 

  AC Surge Power (Peak) 

4000W 

  AC Output Voltage / Frequency 

120 VAC / 60 Hz 

  230 VAC / 50 Hz 

  AC Output Waveform 

True Sinewave 

  AC Output Socket 

 2 pc ( 20A GFCI) 

2 pc 

  Nominal DC Input Voltage 

25.0 VDC 

  No Load battery draw 

< 0.6 ADC (with Load Sense OFF) 

< 0.1 ADC (with Load Sense ON) 

  DC Input Voltage operating range 

21.0 – 31.0 VDC 

  Under Voltage Alarm 

22.4 VDC 

  Under Voltage Shutdown  

21.0 VDC 

  Under Voltage Recovery 

23.6 VDC 

  Over Voltage Shutdown 

31.0 VDC 

  Load Sense 
  ‘ON’ Threshold 

>10W 

  ‘OFF’ Threshold 

< 3W 

USB 

   USB Port 

5V, 2.1 A 

Safety and Environmental 

  Conformance 

cETLus 

CE EMC & LVD 

  Agency Markings 

ETL 

CE 

  Operating Temperature 

0°C to 40°C (32°F to 104°F) 

  Storage Temperature 

-20°C to 60°C (-4°F to 140°F) 

  Relative Humidity 

5-90% noncondensing 

  Operating Altitude 

Up to 9,843ft (3000m) above sea level 

Weights and Dimensions 

  Weights 

11.5 lbs. (5.2 kg) 

  Dimensions 

16.3 x 9.1 x 4.3” ( 41.4 x 23 x 11 cm) 

Содержание SW2420

Страница 1: ...24V Input 2000W True Sinewave Power Inverter SW2420 120V model SW2420i 230V model Owner s Manual...

Страница 2: ...e Important Please be sure to read and save the entire manual before using your KISAE True Sinewave Power Inverter Misuse may result in damage to the unit and or cause harm or serious injury Read manu...

Страница 3: ...Page 3 Table of Contents 1 INTRODUCTION 4 2 PRODUCT DESCRIPTION 5 3 INSTALLATION 5 4 UNIT OPERATION 8 5 TROUBLESHOOTING 9 6 SPECIFICATIONS 10 7 WARRANTY 11...

Страница 4: ...imum of 15 minutes and seek medical attention Batteries produce explosive gases DO NOT smoke or have an open spark or fire near the system Keep unit away from moist or damp areas Avoid dropping any me...

Страница 5: ...ian or electrician to ensure adherence to the applicable electrical safety wiring regulations and installation codes Failure to follow these instructions can damage the unit and could also result in p...

Страница 6: ...8cm from the battery positive terminals DC Disconnect Switch Use a 24V or higher rated DC Disconnect Switch with the same or higher rating as the selected fuse or circuit breaker Use ignition protecte...

Страница 7: ...ng screws Drill the 4 mounting holes and place the Power Inverter in position and fasten the unit to the mounting surface Important Field wiring DC terminals tightening torque 12 13 Nm Chassis Groundi...

Страница 8: ...lay will then show the measured battery voltage and output power alternatively Status LED will turn green 5V USB and AC output are available Press Power Select button to turn unit off Remote ON OFF Sw...

Страница 9: ...er power Inverter is required for these appliances Estimated Run time Following run times are estimates for reference It is based on using different battery bank sizes Actual run times may vary Estima...

Страница 10: ...Load connected to unit is less than the threshold setting 10W Disable Load Sense function by changing the unit setting or increase the AC load connected to unit to 10W 7 SPECIFICATIONS Note Specificat...

Страница 11: ...ail store After speaking to a customer service representative if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of original purcha...

Страница 12: ...Page 12 Service Contact Information Email info kisaetechnology com Phone 1 877 897 5778 www kisaepower com Printed in China...

Отзывы: