“Power/Select” button for 5 second to enter Load Sense select mode, display shows current
setting (“LS0” = Load sense is disable, “LS1” = Load Sense is disable). Press “Power/Select”
button once to change setting. The unit will automatically exit the select mode after 5 seconds.
6. TROUBLESHOOTING
To troubleshoot the unit, please note the error code displayed on the main unit and review
“Understanding the Error Codes” in section 4.
Problem Possible
Cause/Condition
Solution
The unit is off.
Turn the unit ON (Press and hold the “Power/Select”
button for a second until a beep is sounded)
No AC Output. All
the LEDs and the
display are off.
No power coming into unit.
Check if the DC Fuse or the DC Disconnect switch (if
installed) is either blown or turned OFF.
Check error code on display
Verify the error condition and make correction
No AC Output.
Status LED is in
Amber
GFCI on 120V model
(SW2420) is tripped
Check load for Ground Fault and reset the GFCI
AC Output is
turning ON and
OFF every few
seconds
Load Sense function is
enabled and Load connected
to unit is less than the
threshold setting. (<10W)
Disable Load Sense function by changing the unit
setting or increase the AC load connected to unit to
>10W
7. SPECIFICATIONS
Note: Specifications are subject to change without notices.
True Sine Wave Series
Specification
SW2420 SW2420i
-EU,UK,AU
Inverter
AC Output Power
2000W
AC Output Current
16.7A
8.7A
AC Surge Power (Peak)
4000W
AC Output Voltage / Frequency
120 VAC / 60 Hz
230 VAC / 50 Hz
AC Output Waveform
True Sinewave
AC Output Socket
2 pc ( 20A GFCI)
2 pc
Nominal DC Input Voltage
25.0 VDC
No Load battery draw
< 0.6 ADC (with Load Sense OFF)
< 0.1 ADC (with Load Sense ON)
DC Input Voltage operating range
21.0 – 31.0 VDC
Under Voltage Alarm
22.4 VDC
Under Voltage Shutdown
21.0 VDC
Under Voltage Recovery
23.6 VDC
Over Voltage Shutdown
31.0 VDC
Load Sense
‘ON’ Threshold
>10W
‘OFF’ Threshold
< 3W
USB
USB Port
5V, 2.1 A
Safety and Environmental
Conformance
cETLus
CE EMC & LVD
Agency Markings
ETL
CE
Operating Temperature
0°C to 40°C (32°F to 104°F)
Storage Temperature
-20°C to 60°C (-4°F to 140°F)
Relative Humidity
5-90% noncondensing
Operating Altitude
Up to 9,843ft (3000m) above sea level
Weights and Dimensions
Weights
11.5 lbs. (5.2 kg)
Dimensions
16.3 x 9.1 x 4.3” ( 41.4 x 23 x 11 cm)