tdo
Time delay in deactivating the compressor once the door opens
and activate the door alarm
. Once the door
closes, the compressor is activated and the alarm turns off.
0
99
0
min
DEFROST
18
dFr
Time between two successive defrost
, where if dFr = 0 or the relay is in heating mode, defrost is
deactivated.
0
50
6
hours
19
dd2
Defrost duration (manual and automatic)
1
90
18
min
20
dE5
Defrost end temperature - room temperature - terminals sensor 5-6
The defrost shut-off temperature is the temperature of the room, regardless of whether we have connected
the heat exchanger sensor. Above this room temperature the automatic defrost stops.
Manual defrosting starts regardless of the room temperature and is of duration dd2.
In case of fault (LF1) of the room sensor, the end of defrost temperature is not checked and is completed
after the selected time dd2.
0
25.0
10.0
°C/°F
21
dY4
Display indication during defrost
0 = room temperature is displayed
1 to 40 minutes = “dFr” is displayed from 1 to 40 minutes from the initiation of defrost
0
99
20
min
22
dP3
Dripping time, where the compressor is OFF after defrost
0
10
0
min
23
tdH
Time delay in activating high temperature alarm "AHi" after defrost.
The "AHi" alarm is not activated during defrost.
0
99
0
min
SMART DEFROST (more details page 2)
24
dSE
Smart defrost function
0 = NO
1 = YES
0
1
0
-
25
dSb
Starts a defrost cycle at the start of the device
0 = NO
1 = YES
0
1
1
-
26
dS2
Minimum time between two consecutive smart defrosts
40
255
60
min
27
dS1
Time constants, the steadier the increase, the harder it is to start smart defrosting
1
20
3
min
28
dSt
Temperature constant, the higher the constant, the harder it is to start smart defrosting
0.5
3.0
1.0
°C/°F
COMPRESSOR
29
CP2
Compressor’s minimum time OFF
0
4
3
min
30
CF3
Compressor’s operation in case of room’s sensor malfunction LF1
and in cooling mode, the compressor
operates as follows
:
0 = 40% ΟΝ compressor (3 minutes ΟΝ, 4 minutes OFF) / 1 = ΟΝ constantly the compressor.
In heating mode with parallel sensor malfunction (LF1), the relay switches off.
0
1
0
-
RELAY
31
rHC
Relay operation mode, where 0 = cooling / 1 = heating / 2 = heating with countdown based on timer
Hod
0
2
0=cooling
-
32
Ηοd
Countdown timer when the relay is in heating mode with countdown, adjust also parameter
rHC = 2
1
255
1
min
NETWORK - GENERAL SETTINGS
33
Add
Device address on network
0
255
1
-
34
trE
Response time of the device on network
5
100
40
msec
35
bAU
Baud rate: 2 = 9600
-
-
2=9600
-
36
Pro
Cabinet’s program (factory settings) is displayed – no access
-
-
1
-
37
tPE
Unique product number – no access
-
-
45
-
ALARM TABLE
1
LF1
Room sensor malfunction
2
LF2
Evaporator sensor malfunction
3
ΑLo
Low room temperature
4
ΑHi
High room temperature
5
dοr
Open door alarm
6
EEr
RAM error: re-enter the SPo (see Setting the device temperature - SET POINT previous page)
The alarms are automatically deactivated once the cause of the alarm disappears.
Made in Greece
.
The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician.
The guarantee covers only the replacement or the service of the device. KIOUR PC implements a Quality Management System according to EN ISO 9001:2015 Standard with registration number
01013192.