3
16
Fd3
Evaporator’s fan operation during defrost the with evaporator’s sensor ON (parameter οS2 = 1)
0 = OFF and
starts with the compressor if the evaporator’s temperature is smaller than Fo1
1 =
ON when the evaporator’s temperature is smaller than Fo1
2 =
always ON in both types of defrost (electrical / hot gas)
If the evaporator’s sensor is OFF (parameter οS2 = 0), the fan is OFF during defrost and starts after timer
Fd4 has elapsed.
0
2
0
-
17
Co1
Compressor’s minimum time ON
0
15
0
minutes
18
CΡ2
Compressor’s minimum time OFF
0
15
2
minutes
19
CF3
Compressor’s operation in case of room’s sensor malfunction
-1 =
compressor OFF
0 =
compressor ON while defrost starts based on timer dFr and ends based on timer dd2 or temperature
dE5, whichever comes first.
1 to 150 min = compressor time ON
while defrost starts based on timer dFr and ends based on timer dd2 or
temperature dE5, whichever comes first.
-1
15
3
minutes
20
CF4
Compressor time OFF
in case of room’s sensor malfunction
1
150
3
minutes
21
SE1
Room sensor offset
-10.0
+10.0
0.0
°C/°F
22
SE2
Evaporator sensor offset
-10.0
+10.0
0.0
°C/°F
23
dLd
Door switch operation
0=OFF / 1=ΝC
contact.
If cabinet’s door is open during defrost for more than time tdo, defrost relay turns OFF and resumes once
door is closed. Defrost duration based on timer dd2 keeps counting from the beginning of defrost.
0
1
1= NC
-
24
LSP
Lower setting limit of SPo
-50.0
+110
-21.0
°C/°F
25
HSP
Maximum setting limit of SPo
-50.0
+110
-10.0
°C/°F
26
C_F
Temperature measurement unit: toggling between °C/°F do not adjust the SPo automatically, it must be
changed by the user
0 = °C / 1 = °F
0
1
0=°C
°C/°F
27
oS2
Evaporator’s sensor operation
0 = OFF sensor
1 = ON sensor
When the sensor is OFF, by pressing
it is displayed
“
S--
”.
For more information regarding the defrost without the evaporator’s sensor, check parameters dE5, dt6 and
Fd3.
0
1
1=
activated
-
28
tdo
Time delay in deactivating the compressor once the door is open
1
250
120
sec
29
dEC
Temperature indication as integer or decimal, where 0 = integer / 1 = decimal
0
1
1=
decimal
-
30
SEn
Sensor type NTC/PTC
0 = PTC / 1 = NTC
0
1
1=NTC
-
31
dt5
Time delay in restraining indication “dFr” (parameter dY4=-1) or indication SET POINT + diF (parameter
dY4=-2) on screen after defrost ends
Indication “dFr” disappears once room’s temperature is smaller than SET POINT + diF.
0
150
0
minutes
32
Add
Device address on network. To connect with Mini Logger enter Add=1.
0
255
1
-
33
trE
Response time of the device on network
5
100
40
msec
34
tAd
Time delay in activating door alarm “dor” once the door is open
tdo
99
0
minutes
35
tEd
Time delay in refreshing room temperature on screen once the door is open
0
255
0
minutes
36
Fd4
Time delay in activating the fan after defrost ends
and only if evaporator’s temperature is smaller than temperature Fo1 (check parameter Fd3).
0
255
0
minutes
ALARM’S TABLE
1
LF1
Room sensor malfunction
2
LF2
Evaporator sensor malfunction
3
ΑLo
Low room temperature
4
ΑHi
High room temperature
5
dοr
Open door alarm (when the cabinet’s door opens, the fan stop)
6
EEr
Error in memory RAM: re-enter the SPo (see ADJUSTING TEMPERATURE – SET POINT page 1)
The alarms are automatically deactivated once the cause of the alarm disappears.