Installation Clearances
CLEARANCES FOR ROUND FIREPIT (FP2085T)
1.
The round firepit (FP2085T) cannot be built into a
combustible cabinet of any type.
Only non-
combustible materials may be placed around firepit.
(eg., bricks, concrete, river rock, etc.)
2. Clearance to combustible side wall is 24” minimum.
Non-combustible walls 14” to side wall.
3. Minimum clearance to any ceiling with no overhang is
to be 7 feet from top of firepit.
4. Clearance to a combustible floor is 0”.
CLEARANCES FOR RECTANGLE FIREPIT (FP2785T)
1. The rectangle firepit (FP2785T) may be built into a
combustible enclosure.
You must maintain minimum
enclosure dimensions of 32-1/2” x 39-1/2” I.D.
The
top of enclosure must be of a non-combustible
material such as concrete board or wonder board.
2. Clearance to combustible side wall is 24” minimum.
Non-combustible walls 14” to side wall.
3. Minimum clearance to any combustible ceiling
with no
overhang is to be 7 feet from top of firepit.
4. Clearance to a combustible floor is 0”.
FP2785T in a combustible enclosure.
Ceiling
Minimum
7 feet
to ceiling from
top of fire pit
Minimum 24” to
sidewall from
edge of fire pit
Minimum 24” to
sidewall from
edge of fire pit
Combustible materials
may be used only on
outer portion of cabinet.
Non-combustible
materials on top
of enclosure
Control Panel
Cutout size is
8-1/2” x 2-1/2”
Minimum of [2] 1” x 4”
Air Openings Required
7” MAX
on
Control Panel
Side