Heater Location Instructions: 

Arrange the heater so the hot discharge air is: 
1. Free of interference from any items that could block or disrupt the 
airflow reaching the farthest point of the area being heated. 
2. Direct the airflow  along the coldest part of the garage area without 
blowing the heat directly at the wall or warming the items in any way. 
Typically  a distance of 3 to 4 feet is away from walls or cabinets is 
acceptable.  
3. Do not blow directly on stationary people in the room or work  
areas. 
 4. Smaller rooms will be comfortably heated with one unit. Larger 
rooms may require multiple heaters Moves the air in a circular, wall 
wiping pattern around the room. This configuration aids in pre-
heating the incoming air of the next heater and will raise the room 
temperature faster. See Fig 3.4 and 3.5 

Thermostat: 

The inbuilt thermostat has a range of 40 to 90 degrees F and when 
set will keep the room at a comfortable temperature. We recommend 
experimenting with settings to determine ideal room temperature 
while occupied and unoccupied. Once those ideals are identified, 
mark the settings on the label with a felt tip marker. 
 If a remote line voltage thermostat is used it should be rated for 
higher than the amp load of the heater connected.  Locate the ther-
mostat 5 ft. (1.5 m) above the floor on an interior wall away from cold 
drafts, cold steel posts, outside walls, hot water pipes, hot lights and 
away from the discharge air stream of the heater. 
 

 

Ceiling Mount 

 

 

Mounting  Instructions

 

Wall Mount 

Typical garage with 2 or 3 outside walls 

Larger garage with all outside walls  

or colder climate 

Heater may be mounted to the wall or ceiling. For best performance and sat-
isfactory results the heater 

should not 

be mounted over 10 feet high off the 

floor. 

Minimum distance off the floor is 6 ft.

 per UL standards 2021. 

 For wall installation the bracket must have the hook end pointing up so if the 
heater were to loosen over time it would not fall out. See Fig 3.3  
  Wall stud and ceiling joists are typically wider than our mounting bracket 
which is 11 inches wide. The heater weighs 14 lbs. and should be mounted 
onto at least one stud to be properly supported.  
  Your fasteners penetrating a stud is critical to supporting the weight. A gyp-
sum wall board fastener is not strong enough. But if your ideal location has no 
solid backing. You can fasten with large screw fasteners a 2 x 6 across the 
studs or ceiling joists  and attach the heater then to the 2 x 6. This works for 
ceiling or wall mounting. Attach with appropriate lag bolts with proper depth 
for the 14 lbs. Install hex fasteners into both sides of heater with washer on 
the outside of the bracket and star washer between the heater and bracket. 
 

Minimum clearances from walls and ceiling 
6 inches / 

15.24 cm  

to the side 

5 inches / 

12.7 cm  

from the back 

2 inches / 

5.08 cm  

from ceiling  

Never point heater at ceiling 
Maintain clearance of at least 3 ft. in front of heat outlet 

Fig 3.3  

Fig 3.1  

Fig 3.4  

Fig 3.5  

Fig 3.2  

UP 

SAVE THESE INSTRUCTIONS 

After bracket is mounted, place washers 
on bolts and then in heater sides. Drop 
onto bracket slots placing lock washer 
between heater and bracket and washer 
between bracket and bolt. Adjust to the 
preferred angle and tighten bolts to 30 ft. 
lbs. of torque minimum.  

Mounting bolt 
 
Flat washer 
outside bracket 
 
Star Washer 
Inside bracket 