Pages 25 Total 58
Shenzhen King Pigeon Hi-Tech Co.,LED
Ver 1.2
PLC Data acquisition protocol conversion gateway
-D225
5.1.3.2
The data configuration of collecting FX3U output Y is as
follows: collecting Y0-Y7
Operation instructions: (1) Because the data of Y is collected at the same time in the same project,
click the New File button (same as ideal for collecting multiple registers in the same project to
create as many files as you want, click on that file is right (2) Click on the newly created file, click
“Setup” to pop up the configuration box, (3) “Slave ID” defaults to “1”, because the data of Y is
Boolean, so the function code It is "01", (for details of the function code used to collect the PLC
register, please refer to
Appendix Mapping address of PLC register
) (4) The mapping address
corresponding to the collection Y0-Y7 is 5000-5007, so the starting address is filled in "5000", (PLC
The mapping address of the register corresponding to D225 is detailed in the
) (5) Y0-Y7, there are 8 in total, so the number is filled in: "8"
(6) Other setting items are default, and you can also modify the configuration according to
requirements , Click "OK" after the configuration is complete, so that the collected data of Y is
configured, click "Save" to modify the file name