Modbus to MQTT IoT Gateway
-BL101
Alarm and Events Configuration
Item
Description
Name
Name of Alarm Point
MQTT Flag
MQTT flag of alarm point, can be randomly set
Association Point
Name
Select alarm point and click Add. Datapoint box will pop up. Click
the point to be set for alarm and click OK to confirm. Double click
datapoint to enter datapoint attribute page
High Limit
High Limit alarm value of numeric datapoints
Low Limit
Low limit alarm value of numeric datapoints
Digital Alarm Type
Select from digital alarm mode: Normally Open or Normally Close
Alarm ACK Time
Within alarm acknowledge time, if data will recover to normal
value, no alarm will be triggered. Otherwise it will generate alarm
OK
Confirm alarms and events setting
Cancel
Cancel alarms and events setting
4.2.6.2 Alarm Event Configuration
Right click Alarm Trigger Action box and click Add to enter Event configuration box
for setting actions to be performed when alarm is triggered. Right click Alarm
Release Action box to set actions to be performed when alarm is released