background image

Minimum Clearances

Heater to Floor: heater may be mounted directly on fi nished 
foor or, if desired, above fl oor (such as above the baseboard). 
Up to 3/4 inch (19 mm) of carpeting may be installed up to and 
around heater as long as it does not obstruct the air fl ow.
Heater to Drapery: do not install heater where curtains or 
drapery will contact the heater. See Figure 2 for required mini-
mum clearances.

Furniture: maintain at least 6 inches (152 mm) space between
furniture and heater to allow for proper air fl ow.

UNPACKING HEATER

Check heater to make sure it has not been damaged in 

 

shipping. Do not install or attempt to operate the heater if 
damaged. Return to place of purchase or fi le claim with 
freight carrier.

INSTALLATION INSTRUCTIONS

1. Serious injury or death could result from electric shock.
Make sure electrical power supply circuit coming to heater 
is disconnected at main disconnect or service panel before 
installing this heater.
2. Wiring procedures and connections must be in accordance
with the National Electrical Code (NEC) and local codes. 
Refer to Wiring Diagrams Figure 5. Make sure all electrical 
connections are tight to prevent possible overheating. Use 
Copper Supply Wire Only.
3. Verify the electrical power supply voltage matches the
voltage rating as printed on the heater nameplate – see Fig-
ure 1.

  

TO REDUCE THE RISK OF FIRE AND ELECTRIC SHOCK
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

CAUTION - Never connect a heater to a voltage 
greater than the nameplate voltage as this will 
damage the heater and could cause a fi re.

4. Do not install the heater against combustible low-den-
sity cellulose fi berboard surfaces, against or below vinyl wall 
coverings, or below any materials that may be damaged by 
heat such as vinyl or plastic blinds, curtains, etc.
5. Do not install heater below an electrical convenience re-

ceptacle (outlet).
6. CAUTION – Heater Operates at High Temperatures. Keep
Electrical Cords (including telephone and computer cables), 
Drapes, and Other Furnishings Away From Heater. For effi -
cient and safe operation, we recommend maintaining a mini-
mum of 6 inches (152 mm) clearance above and in front of 
the heater at all times. See Figure 2 for minimum clearance 
requirements for drapery.
7. To reduce the risk of fi re, do not store or use gasoline
or other fl ammable vapors or liquids in the vicinity of the 
heater.
8. Do not install heater upside down or in any position other
than as shown in this manual. Caution label with word “TOP” 
must be at the top when heater is installed.
9. Do not recess heater in wall or install heater inside any
type enclosure as this will cause heater to overheat and 
could create a hazard.
10. When mounting heater, (see Figure 4), make sure screws
do not damage crossover wiring or the safety limit in the 
heater.
11. Do not remove or bypass the safety limit control as this
could allow heater to become a fi re hazard – see Figure 4.
12. When using Transformer Relay Accessory, supply wiring
provided in compartment where this accessory is installed, 
must be rated 90 °C minimum.

Important  Note:  Certain  fabrics  and  materials  discolor  or  may 

become  damaged  by  heat.  Therefore,  avoid  installing  heater 

against vinyl wall coverings or below plastic or vinyl items such 

as  blinds  or  vinyl  drapes  since  these  items  may  become 

damaged by the heated air flowing from the heater.

1. Remove wiring compartment cover at end of heater where

power supply cable is to enter (Figure 3). Determine desired 
mounting  location,  position  heater  to  wall  and  mark

 

wall 

(or fl oor) at location where power supply is to enter heater.

2. The  air  inlet  of  the  heater  cannot  be  obstructed  by  the

finished floor materials such as carpet, tile or hardwood. The 

installer, must make allowance for the finished floor materials 

when  installing  the  heater  during  rough-in  construction  on  a 

subfloor.  For  example  if  thickness  of  the  padding  and  carpet 

to be installed is 3/4", then the heater must be mounted 3/4" 

above the subfloor. 

Figure 3

Wiring compartment
cover

Front Cover

Screw

NOTE: For most effi cient operation locate heaters along out-
side wall under windows. Position heater so it can be secured 
to wall stud. Power cable must enter heater through built 
in cable clamp or one of the knockouts provided in wiring 
compartment. 

Figure 2: 
Clearance for 
Drapery

 and Finished 

Floor

2. Drill hole in wall (or fl oor) at desired location for power sup-
ply entry. Install power supply wiring to heater and thermostat 
location as determined by thermostat option selected. Allow 
approximately 10 to 12 in (254mm to 305mm) of wire at heater 
for connections.
3. If any accessories are to be used with this heater, refer to
installation instructions provided with the accessory for proper
installation and wiring. Visit www.king-electric.com for instruc-
tions on some common accessories.
4. Position heater at desired location and attach to wall using
good screws or appropriate hardware. Locate studs and drive 
screws into studs where possible. For heaters up to 6 feet (1.8 
m) in length, one screw at each end is adequate. For longer
units, an additional screw in center is required. Tighten screws 
and then loosen screws at least ¼ turn to allow heater to ex-
pand and contract during use. If unit is mounted above fl oor, 
two additional mounting holes are provided at each end below 
the heating element (see Figure 4). Install an additional screw 
at each end for stability making sure to loosen each screw at 
least ¼ turn.
5. Connect the supply cable grounding wire to the green wire
pigtail in wiring compartment.

WARNING

Содержание K Series

Страница 1: ...akes or ex haust in any manner Do not insert or allow foreign objects to enter any ven tilation or exhaust opening as this may cause an electric shock or fire or damage the heater Serious injury or death could result from electric shock Make sure electrical power supply circuit coming to heat er is disconnected at main disconnect or service panel before installing or servicing this heater 4 5 6 WA...

Страница 2: ...mounting heater see Figure 4 make sure screws do not damage crossover wiring or the safety limit in the heater 11 Do not remove or bypass the safety limit control as this could allow heater to become a fire hazard see Figure 4 12 When using Transformer Relay Accessory supply wiring provided in compartment where this accessory is installed must be rated 90 C minimum Important Note Certain fabrics a...

Страница 3: ...IRES HEATER WIRES SUPPLY WIRES HEATER WIRES Connection Diagram for Wall Mounted Single Pole Thermostat 1 Red thermostat wire to black power supply wire 2 Black thermostat wire to black heater wire 3 White power supply wire to white heater wire 4 Connect all bare groundwires together BLACK WIRE RED WIRE BARE GROUNDWIRE WHITE WIRE WIRE COLOR CHART Connection Diagram for Wall Mounted Double Pole Ther...

Страница 4: ... Improper calibration 2 Remove cover and adjust calibration screw Room Temperature swings from too hot to too cold 1 Defective or low quality thermostat 1 Replace with a better quality thermostat Anticipated thermostats are fairly accurate an electronic thermostat is the best Your heater will give you years of service and comfort with only minimum care To assure efficient operation follow the simp...

Отзывы: