Additional Scaling Parameters

Note

The programming instructions below are only

available when purchasing a loop powered unit. Battery pow-

ered units will not see these programming choices.

BK2800 Simplified 4-20mA Programming Instructions

FLOW 4mA SETTING

 – When the loop powered option is

ordered, the flow rate that corresponds to 4mA must be set.

Zero is default flow rate for this setting. If the current selection

is correct, press the 

ENTER

 key once to advance to the

next parameter. If adjustment is required use the 

RIGHT

 arrow

key to select the position of the number you wish to

change, then, use the 

UP

 arrow key to increment the number.

Once you have completed this step, press the 

ENTER

 key to

advance to the next parameter.

FLOW 20mA SETTING

 – The flow rate that corresponds to

20mA must be set next. The turbine meter’s maximum flow

rate is the default value. If the current selection is correct,

press the 

ENTER

 key once to advance to the next parameter.

If adjustment is required use the 

RIGHT

 arrow key to select

the position of the number you wish to change, then, use the

UP

 arrow key to increment the number. Once you have completed

this step, press the 

ENTER

 key to advance to the next

parameter.

4-20mA CALIBRATION

 – When ordered with a 4-20mA

option this menu item allows the fine adjustment of the 4-

20mA output. The 4mA setting is typically between 35 and

50. To set the 4mA value, connect an ammeter in series with

the loop power supply. At the 

4mA OUT

 prompt, adjust the

4mA value to obtain a 4mA reading on the ammeter. The 

UP

arrow key increments the value and the 

RIGHT

 arrow key

decrements the value. When a steady 4mA reading is obtained

on the ammeter, press the 

ENTER

 key to lock in this value and 

move to the 20mA adjustment. The 20mA  adjustment is performed using 

the same procedure as the 4mA adjustment. 4-20mA TEST – The monitor 

contains a diagnostic routine that allows the simulation of mA values 

between 4 and 20 to check output tracking. At the 4-20TEST prompt the 

arrow keys change the simulated mA output in increments of 1mA. The 

ammeter should track the simulated mA output.  If a 4- 20mA test in not 

necessary, pressing the ENTER key once will escape the testing at any 

time.

Note

If your BK2800 flow monitor was ordered with a

Kimray Turbine flow meter, the 4-20mA was programmed

and factory calibrated.

Typical Ammeter Connection

Содержание BK2800

Страница 1: ...All B2800 flow monitors come pre calibrated from the factory if ordered with a Kimray Flow Meter If required however it can easily be re configured in the field The monitor s large 8 digit by 75 nume...

Страница 2: ...I III Div 1 Groups C D CE IEC 61326 1 Specifications Operating the Monitor The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode Both the run mode and the program mod...

Страница 3: ...orrect flows and totals Note Unless otherwise specified Kimray turbine flow meters are supplied with K factors measured in pulses per gallon PUL GAL which will automatically convert to your desired un...

Страница 4: ...the arrow keys to scroll to the desired display mode and press ENTER to save the choice A TEST function is also available in the Display Function sub menu With the test function selected the display a...

Страница 5: ...ean fresh battery to insure continued trouble free operation It is recommended that the total be saved to memory before the battery is removed See STORE TOTAL in the programming section of this manual...

Страница 6: ...Programming Installation Manual 6 Kimray is an ISO 9001 certified manufacturer Kimray quality assurance process maintains strict controls of materials and the certification of parts used in Kimray ele...

Страница 7: ...ty Try disconnecting the pick up from the monitor pig tail This should stop the noise If not then try re orientating the meter to a new location Flow Rate Indicator Bounces This usually indicates a we...

Страница 8: ...Programming Installation Manual 8 Kimray is an ISO 9001 certified manufacturer Kimray quality assurance process maintains strict controls of materials and the certification of parts used in Kimray ele...

Страница 9: ...next parameter If adjustment is required use the RIGHT arrow key to select the position of the number you wish to change then use the UP arrow key to increment the number Once you have completed this...

Страница 10: ...rogramming Installation Manual 10 Kimray is an ISO 9001 certified manufacturer Kimray quality assurance process maintains strict controls of materials and the certification of parts used in Kimray ele...

Страница 11: ...only The default is gallons per minute All contents of this publication including illustrations are believed to be reliable And while efforts have been made to ensure their accuracy they are not to be...

Страница 12: ...cation including illustrations are believed to be reliable And while efforts have been made to ensure their accuracy they are not to be construed as warranties for guarantees express or implied regard...

Отзывы: