KAL455 Manual Call Point Installation Sheet
EN RU
1
2
EN: Installation Sheet
Description
This document includes installation information for UTC Fire &
Security KAL455 manual call points. These manual call points
are designed for use in UTC Fire & Security Kilsen analogue
addressable fire alarm systems and include models for indoor
and outdoor use.
Installation
Caution:
This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect to the KAL455 connection block (Figure
2
) as follows:
1. Line in (positive)
2. Line out (positive)
3. Line in (negative)
4. Line out (negative)
Addressing
Use the DIP switch (Figure 1) to allocate a device address
from 128 to 252 (see page 4).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Voltage
22 to 35 VDC
Current
Standby
Alarm
max. 250 ųA
max. 2.5 mA
Cable size
Minimum
Maximum
0.8 mm
2
2.5 mm
2
IP rating
KAL455, KAL455-18
KAL455E, KAL455E-18
IP24D
IP67
Operating environment
Operating temperature
Storage temperature
Relative humidity
−10°C to +70°C
−20°C to +70°C
10% to 95% noncondensing
Dimensions (W x H x D)
KAL455, KAL455-18
KAL455E, KAL455E-18
89 x 93 x 27.5 mm [1]
97.5 x 93 x 27.5 mm [1]
Weight
187 g
[1] Excluding surface mount.