KAL455 Manual Call Point Installation Sheet 

EN  RU   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN: Installation Sheet 

Description 

This document includes installation information for UTC Fire & 

Security KAL455 manual call points. These manual call points 

are designed for use in UTC Fire & Security Kilsen analogue 

addressable fire alarm systems and include models for indoor 

and outdoor use. 

Installation 

Caution: 

This product must be installed by qualified personnel 

adhering to the CEN/TS 54-14 standard and any other 

applicable local authority laws. 

Electrical connections 

Connect to the KAL455 connection block (Figure 

2

) as follows: 

1.  Line in (positive) 

2.  Line out (positive) 

3.  Line in (negative) 

4.  Line out (negative) 

Addressing 

Use the DIP switch (Figure 1) to allocate a device address 

from 128 to 252 (see page 4). 

Maintenance 

Basic maintenance consists of a yearly inspection. Do not 

modify internal wiring or circuitry. 

Specifications 

 
Voltage 

22 to 35 VDC 

Current 

 

Standby 

 

Alarm 

 

max. 250 ųA 

max. 2.5 mA 

Cable size 

 

Minimum 

 

Maximum 

 

0.8 mm

2

 

2.5 mm

2

 

IP rating 

 

KAL455, KAL455-18 

 

KAL455E, KAL455E-18 

 

IP24D 

IP67 

Operating environment

 

Operating temperature 

 

Storage temperature 

 

Relative humidity 

 

−10°C to +70°C 

−20°C to +70°C 

10% to 95% noncondensing 

Dimensions (W x H x D) 

 

KAL455, KAL455-18 

 

KAL455E, KAL455E-18 

 

89 x 93 x 27.5 mm [1] 

97.5 x 93 x 27.5 mm [1] 

Weight 

187 g 

[1] Excluding surface mount. 