Page 2 of 2
3940 Dr. Martin Luther King Drive
St. Louis, MO 63113
P/N 00912257 FORM NO. K1203 R11/12 ECO-6-065-12
Before installing, be sure to read and be familiar with
the following instruction procedures. All installations
must comply with applicable local, National Electrical
Codes and/or Canadian Electrical Code.
1. DIRECTION FOR INSTALLATION
WARNING: Electrical power supply MUST
BE OFF Before and during installation and
maintenance.
1. Disassemble the existing Crouse-Hinds fixture
from the mount by un-tightening the screw and
disconnecting field wire leads connectors.
2. Make sure that the mount and its gasket joint
surface is free from damage. Inspect the field
supply leads and ground wire for safe wiring
connections to the new fixture leads.
3. Install the adapter onto Crouse-Hinds existing
mount by locating the adapter hinge pin on the
hook. Refer to Figure A.
4. Next swing the adapter up and fasten the
existing mount by tightening the screw
provided. (Standard box-end wrench is
recommended). Make sure that the mount and
adapter are secured properly with .032 inch
max. gap as detailed in Figure B (Do not over
tighten).
5. Connect the ground lead of the adapter to the
ground lead of the mount. The other ground
screw in the adapter is for attaching the ground
lead supplied with the new fixture. Refer to
Figure C.
6. For installation of the new fixture housing, refer
to the separate instruction sheet supplied with
the Killark VM series fixture.
NOTE
: These adapters are to be used with
Crouse-Hinds VMV, DMV, and LMV Series
Fixture mounting covers (CM2, CM3, TWM2
& TWM3). Save this instruction sheet for
maintenance and future reference.
Figure B
Figure C
(VIEW LOOKING UP)
Figure A