25
3.2
Alarm Output (roP) Setting Group Flow and Display
** After input the correct password, press
again to select the alarm output setting group screen
Display Screen
Default
Screen Name
Modify Parameters and Process Description
Alarm 1 action
direction setting
(ACt1)
1. Setting description:
Set HI to be higher than the set
value action. Set LO to be lower than the set value action
Modifiable range: Hi (
≧
alarm value action), Lo (
<
alarm
value action)
2. Press
to enter parameter modification, press
or
to modify the value.
3. After setting is completed, press ENT to save the
modified parameters and enter the next parameter setting
page.
Alarm 2 action
direction setting
(ACt2)
Alarm 1 action
hysteresis
percentage
setting value
(HYS1)
Setting description:
1. After setting the alarm HI action, to keep the alarm not
to shutdown, the displayed value must be lower than the
alarm set value - (alarm set value x hysteresis percentage
set value %).
Example description: Alarm setting:
≧
8000.00 start up, <
7800.00 shut down.
200.00
÷
8000.00 = 0.025
Alarm action hysteresis percentage setting value: 0.025%
2. After setting the alarm LO action, to keep the alarm not
to shutdown, the displayed value must be higher than the
alarm set value + (alarm set value x hysteresis percentage
set value %).
Example description: Alarm setting: < 8000.00 start up,
≧
8200.00 shut down.
200.00
÷
8000.00 = 0.025
Alarm action hysteresis percentage setting value: 0.025%
Modifiable range: 0.0000 ~ 1.0000%
3. Press
to enter parameter modification, press
or
to modify the value.
4. After setting is completed, press ENT to save the
modified parameters and enter the next parameter setting
page.
Alarm 2 action
hysteresis
percentage
setting value
(HYS2)
Alarm 1 action
delay set value
(dEL1)
Setting description:
1. Set 5 seconds; after the displayed value reaches the
alarm set value, it must take 5 seconds to operate.
Modifiable range: 0 ~ 99 (second)
2. Press
to enter parameter modification, press
or
to modify the value.
3. After setting is completed, press ENT to save the
modified parameters and enter the next parameter setting
page.
Alarm 2 action
delay set value
(dEL2)
Alarm start
delay range
setting value
(Sb)
Setting description:
1. Set 5; if the display value does not exceed 5, alarm
won’t act nor compare thereof. Modifiable range: 0 ~ 99
2. Set 5, if the display value exceeds 5, the alarm will act
after passing the time set by Sdt.
3. Press
to enter parameter modification, press
or
to modify the value.
4. Press ENT to save the modified parameters and enter the
next parameter setting page.
* This function is used to suppress excessive startup
current cause wrong action.