Switchboard breaker requirements
• Rated current: 30 A (100 V system) / 15 A (200 V system)
(for safety, breakers whose rated current exceeds the specified current cannot be used)
• Only use the breaker with this product.
• Keep the breaker readily accessible at all times.
• Indicate that the breaker is dedicated for use with this product and that it is used to
disconnect the product from the AC power line.
Necessary cable
Vinyl cabtire cable (VCTF): Nominal cross-sectional area 5.5 mm
2
, 3 core
Finished diameter: 12.1 mm or less
Rated voltage: 250 V or higher
Input terminal end: Ring terminal 5.5-4 (5.5 mm
2
M4)
WARNING
Risk of electric shock.
• Before you connect the power cord, turn off the switchboard breaker (a switch that
cuts off the power supply from the switchboard).
Risk of fire.
• Be sure to have a qualified engineer make the connection to the switchboard.
• The switchboard breaker must meet the requirements shown below.
CAUTION
Inside the product, protective circuits are connected to match the polarity of the input
terminal. Be sure to connect the L, N, and
(GND) terminals of the product to the
matching terminals on the switchboard.
• We recommend that you use one of the optional specialized power cords to connect to the
AC power line. If you will not use one of these power cords, use an appropriate power cord
with a length of 3 m or less that has been selected by a qualified technician. If obtaining a
power cord is difficult, contact your Kikusui agent or distributor.
• In an emergency, turn off the switchboard breaker to disconnect the product from the AC
power line.
PWX1500ML
Switchboard
N
L
N
L
Breaker indication example
For the
PWX1500ML only
Power cord
PWX1500ML
dedicated breaker
Содержание PWX1500H
Страница 10: ...10 PWX This page is intentionally blank...
Страница 26: ...26 PWX This page is intentionally blank...
Страница 88: ...88 PWX This page is intentionally blank...
Страница 89: ...Maintenance This chapter explains how to perform cali bration DELETE...
Страница 92: ...92 PWX This page is intentionally blank...
Страница 93: ...Specifications This chapter contains the specifications and gives the dimensions of the PWX series...
Страница 120: ...120 PWX This page is intentionally blank...
Страница 121: ...Appendix A Options B Troubleshooting...
Страница 128: ...128 PWX This page is intentionally blank...