2-12 Before Using the Unit
PAS SERIES
Next, let's consider the case when the output terminal is grounded.
Fig.2-11 shows the case when the + (pos.) output terminal is con-
nected to the chassis terminal. In this case, the + (pos.) output termi-
nal is at ground potential. Therefore, the cable and load that are
connected to the output terminal (including the sensing terminal) only
require an insulation capacity that is greater than the maximum out-
put voltage of the unit with respect to the chassis.
The same holds true when the - (neg.) terminal is connected to the
chassis terminal. The cable and load require an insulation capacity
that is greater than the maximum output voltage of the unit.
Fig.2-11When the + (pos.) output terminal is grounded
For safety reasons, connect either output terminal to the chassis ter-
minal unless your application requires the output terminal to be float-
ing.
+
–
When remote sensing is not used:
Connect to - (neg.) output terminal
When remote sensing is used:
Connect to -S terminal of sensing
+
+S
–S
–
+
–
+
–
17
23
22
26
6
5
2
16
3
4
1
Chassis terminal wire
AC
INPUT
DC
OUTPUT
J1
SENS
L
N
Approx. the same potential
as the - (neg.) output terminal
Insulated
Load
Rext
PAS SERIES
Vext
Since the + (pos.) output
terminal is at ground
potential, the section
indicated in gray must have
an insulation capacity that is
greater than the maximum
output voltage of the unit
with respect to the chassis.
26 Approx. the same potential
as the - (neg.) output terminal
23 Approx. the same potential
as the + (pos.) output terminal
Содержание PAS 10-105
Страница 10: ...VIII PAS SERIES This page has been intentionally left blank ...
Страница 54: ...3 22 Basic Operation PAS SERIES This page has been intentionally left blank ...
Страница 78: ...4 24 Remote Control PAS SERIES This page has been intentionally left blank ...
Страница 131: ...PAS SERIES Specifications 8 13 This page has been intentionally left blank ...
Страница 137: ...PAS SERIES Specifications 8 19 This page has been intentionally left blank ...
Страница 145: ......