5-4 Single-phase Parallel Operation
OT01-PCR-LA/2
9.
Check for an alarm from “Ad. 1” to the last Ad. number (the last Ad.
number will differ by model) in the same way as in step 5.
If there is no alarm, the AC power supply can continue to be used.
Ad. Numbers to be displayed by SELF TEST
Table 5-1
Ad. Numbers
“Ad.” indicates the number of a power unit in the AC power supply. The power units
are numbered sequentially from the top down.
Numbers in the No. area indicated by SELF TEST
Table 5-2
Err Numbers and Remedies (The section to be referred
to in the Remedy column indicates the section number
in the PCR-LA AC Power Supply Operation Manual.)
Ad.
Model concerned
0
All PCR-LA power supplies
1–2
PCR2000LA master unit
1–4
PCR4000LA master unit
1–6
PCR6000LA master unit
11–12
PCR2000LA slave unit
11–14
PCR4000LA slave unit
11–16
PCR6000LA slave unit
No.
Remedy
0
No alarm
1
The internal circuit protection has activated.
Contact your Kikusui
distributor/agent.
2
The internal temperature is expected to be abnormally high.
Wait
approx. 10 minutes with the power ON.
If the alarm continues, perform the procedure speci
fi
ed in
2.5, Input Connections. If the alarm goes off, the power sup-
ply may be installed improperly. Check the description in
“2.2 Precautions on Installation”.
If nothing wrong is found in either of these steps, immedi-
ately stop using the power supply and contact your Kikusui
agent.
3
The internal semiconductor protective function has activated.
See “8.5
Overload Protective Functions”.
4
The internal circuit protective function has activated.
Immediately
stop using the AC power supply and contact your Kikusui
distributor/agent.
5
6
The current limiting function has activated.
See “8.5 Overload Pro-
tective Functions”.
Содержание OT01-PCR12000LA/2
Страница 10: ...VIII Contents OT01 PCR LA 2 ...
Страница 16: ...1 6 General OT01 PCR LA 2 ...
Страница 44: ...2 28 Installation and Preparation for Use OT01 PCR LA 2 ...
Страница 56: ...4 8 Part Names and Functions OT01 PCR LA 2 ...
Страница 64: ...5 8 Single phase Parallel Operation OT01 PCR LA 2 ...
Страница 82: ...6 18 Single phase Three wire Operation OT01 PCR LA 2 ...
Страница 94: ...1 2 Index OT01 PCR LA 2 ...
Страница 95: ......
Страница 96: ...OUTPUT EXPANSION KIT OT01 PCR LA 2 OPERATION MANUAL ...