56
DSI1020/ DSI3020
Appendix A AC Power Supply Connection Diagram
PCR-LE2 series
One PCR-LE2 series (with OUTPUT 1P2W terminal block) + DSI1020
INPUT
G N L
OUTPUT
G N L
OUTPUT 1P2W
G N L
PCR-LE2 Series AC Power Supply
DSI1020 Dip Simulator
SLOT3
AUX
PHASE IN
To the PC
(GPIB, USB, or LAN)
To the PC (RS-232C)
SLOT4
Connect to the EUT
or relay terminals.
1
2
3
4
Install the control board supplied
with this product in SLOT3.
To use the GPIB, USB, or LAN interface, install
the appropriate board in SLOT4.
To use RS-232C, use the RS-232C terminal on
the front panel.
Connectable EUT input circuits
1P2W
Start point
End point
Cable
1
Signal connector (PCR-LE2, SLOT 3) PHASE IN connector (DSI1020)
Control cable (supplied with this product)
2
Output terminal L (PCR-LE2)
1
Input terminal L (DSI1020)
Single-core wire
2
3
Output terminal N (PCR-LE2)
Input terminal N (DSI1020)
Single-core wire
4
Output terminal G (PCR-LE2)
Input terminal G (DSI1020)
Single-core wire
1
Terminal of the OUTPUT 1P2W terminal block
2
This product does not include wires for connecting devices or crimping terminals for the wires. Check the screw sizes
of the I/O terminals of devices in use, and use appropriate single-core wires and crimping terminals. (See
.) We recommend that you use wires with a nominal cross-sectional area of at least 8 mm
2
(AWG8).