3P05-PCR-LE 3

Connecting the Load

For detail of handling the terminal block tray and OUTPUT termi-
nal block, see the PCR-LE series setup guide.
The PCR-LE Series OUTPUT terminal block (not included on the 
PCR500LE) is wired after you first pull out the terminal block tray. 
The terminal box covers ensure that you don’t touch the unwired 
terminals.

WARNING

Risk of electric shock.
• Before you connect cables to the OUTPUT terminal 

block, be sure to turn the POWER switch off, and then 

remove the power plug from the outlet or turn off the 

switchboard.

• Do not use the terminal block with the terminal cover re-

moved.

CAUTION

Risk of malfunction. 
• Do not connect the PCR-LE series in a delta wiring configura-

tion.

• If you are grounding the output, make sure that the isolation 

voltage does not exceed 300 V.

- Note -
If the neutral point is omitted, there are cases in which it will not be 

possible to produce the rated power.

Use noncombustible wires that have diameters that correspond to 
the output current to connect to the load.

Requirements of single-core wires that are used to connect to 

the load

Nominal cross-
sectional area[mm

2

]

AWG (reference cross-

sectional area; mm

2

)

Allowable current* 
(A; at Ta = 30 °C, 86 °F)

0.9

18

(0.82)

17

1.25

16

(1.31)

19

2

14

(2.08)

27

3.5

12

(3.31)

37

5.5

10

(5.26)

49

8

8

(8.37)

61

14

6

(13.3)

88

22

4

(21.15)

115

*1.  Excerpt from Japanese laws related to electrical equipment.

The values vary depending on conditions such as the wire cov-
ering (insulator), the wire material (allowable temperature), and 
whether there are multiple cores in the cable. For cables other 
than those specified in this table, consult with a qualified engineer.

Load

L

U (R)

N

V (S)

W (T)

L

L

N

N

N

Load

L

U (R)

V (S)

W (T)

L

L

N

N

N

Load

Load

Do not connect the PCR-LE series in a delta wiring configuration.

Load

U (R)

V (S)

W (T)

PCR-LE series (3 units)

When the load is connected 

in a star wiring configuration

When the load is connected 

in a delta wiring configuration

PCR-LE

V phase

PCR-LE

V phase

PCR-LE

V phase

PCR-LE series (3 units)

PCR-LE series (3 units)

PCR-LE

U phase

PCR-LE

W phase

V phase

V phase

U phase

U phase

W phase

W phase

PCR-LE

W phase

PCR-LE

W phase

PCR-LE

U phase

PCR-LE

U phase

PCR–LE

OUTPUT

G N L

V

(S)

U

(R)

W

(T)

G

OUTPUT

G N L

OUTPUT

G N L

PCR–LE

OUTPUT

G N L

V

(S)

U

(R)

N W

(T)

G

OUTPUT

G N L

OUTPUT

G N L

Содержание 3P05-PCR-LE

Страница 1: ...r sync cable 1 m 2 pcs 91 80 5099 Connecting cable 75 cm 2 pcs Cable 91 80 9919 Core 96 00 0530 Setup Guide This guide 1 pc V and W phase boards one each The indications V and W on the panel part of each board Firmware version of PCR LE When using the 3P05 PCR LE the PCR LE must be required with the firmware version of 2 00 or later If the firmware ver sion of the PCR LE is 1 99 or previous versio...

Страница 2: ...ow the same procedure to install the other two boards This completes installation of the phase board When a 3P05 PCR LE has been inserted into the slot1 of a PCR LE series that power supply can be used only in a three phase system To use the power supply in a single phase system the phase board must be removed from the slot1 Connecting the bords Use the connecting cable to connect the boards Conne...

Страница 3: ...ngle core wires that are used to connect to the load Nominal cross sectional area mm2 AWG reference cross sectional area mm2 Allowable current A at Ta 30 C 86 F 0 9 18 0 82 17 1 25 16 1 31 19 2 14 2 08 27 3 5 12 3 31 37 5 5 10 5 26 49 8 8 8 37 61 14 6 13 3 88 22 4 21 15 115 1 Excerpt from Japanese laws related to electrical equipment The values vary depending on conditions such as the wire cov eri...

Страница 4: ...rminal Master U phase W phase 2 m or less from the slave unit s L N to the master unit s L N 2 m or less from the slave unit s L N to the master unit s L N 2 m or less from the slave unit s L N to the master unit s L N Relay terminal Relay terminal PCR LE OUTPUT G N L OUTPUT G N L OUTPUT G N L OUTPUT G N L V S U R N W T G OUTPUT G N L OUTPUT G N L ...

Страница 5: ...f the switchboard Power ON 1 Check that the POWER switches of PCR LEs are off 2 Use the power sync cable to connect the J1 connec tor and the J2 connector on the PCR LE rear panels Do not connect two J1 connectors to each other or two J2 connectors to each other Insert the cable firmly into the connectors until the are locked in place PCR LE Power sync cable V phase U phase W phase 3 Set the POWER...

Страница 6: ...ed when you are setting three phase output 环境保护使用期限 Environment friendly Use Period 该标记为适用于在中华人民共和国销售的电子信息产品的环境保护使用期 限 只要遵守有关该产品的安全及使用注意事项 从制造年月起计算 在 该年度内 就不会对环境污染 人身 财产产生重大的影响 产品的废弃请遵守有关规定 产品的制造年月可以在以下网址中确认 http www kikusui co jp pi 毒有害物质或元素名称及含有标示 Name of hazardous materials and symbol of elemet in the equipment and quantity 有毒有害物质或元素 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE 本表格依据 SJ T 11364...

Отзывы: