Product Description

RPW404P-FTL

Datasheet 1.10-65.030-01-EN

Issue 2017-04-03

“Test installation location” function

The room control module provides assistance in selecting the optimum installation location.

This function is active after switching on the device (see the “Switching the Device On/
Off” section page 11), provided a radio partner has not been registered (for a 
maximum of 15 minutes).
The text “

InSt

” is displayed.

Switch on the room control module, see p. 11.
The display switches on. Symbols "Sun“ and "Occupancy“ and the text "

InSt

" are displayed. The 

occupancy sensor and the solar cell are active.

Position the room control module at the potential installation location.

Check the “Sun” icon on the display.

Move about in the room and check the “Occupancy” icon.

Once a suitable installation location has been found, the room control module can be mounted 
and commissioned.

NOTE

If a radio partner has not been taught-in after 15 minutes, the room control module automatically 
switches off.

NOTE

If the energy storage unit is empty, the “Sun” icon will not appear even if the location is good. The 
energy storage unit must be charged first. Charge the energy storage unit by placing the room control 
module in a source of light for two hours (day light or artificial light, but not direct sun light).

Occupancy sensor

The room control module automatically detects a presence in the room with its occupancy sensor. 
Depending on the distance, the range of movement in the detection area is important. The further a 
person is away from the occupancy sensor, the greater the movement must be.

Evaluation

Display

Installation location 
good

The “Sun” icon is permanently displayed and
the “Occupancy” icon switches from “Person inside the house” to “Per-
son outside the house” and back again

Installation location 
bad

The “Sun” icon is not displayed or
the “Occupancy” icon does not switch to “Person inside the house” and 
remains unchanged.

0 m

1 m

2 m

3 m

4 m

5 m

8 m

7 m

9 m

6 m

1,5 m

Содержание RPW404P-FTL

Страница 1: ...s interface and algorithm for self learning of utilization time profiles heating profiles in rooms Application Solar powered self learning room control module with LCD and smart commu nication managem...

Страница 2: ...2 Teaching in the MD15 FTL radio partner on the RPW404P FTL 13 Mounting 14 Removal 16 Operating level 16 Setting the initial display 16 Setting the setpoint 16 Manually switching between comfort and e...

Страница 3: ...he applicable local regulations must be observed when installing and using the device Meaning of the symbols WARNING Indicates a hazard of medium risk which can result in death or severe bodily injury...

Страница 4: ...NOTE This device contains a humidity sensor This humidity sensor is influenced by chemical substances in the air that can be produced for example due to the evaporation of cleaning and care products...

Страница 5: ...tal sensor Integrated PIR Passive infrared sensor Measuring range 0 C to 50 C Measuring tolerance Typically 0 3 K Display LCD display room temperature date or time as selected Status indicators Contro...

Страница 6: ...he room control module and the radio partner is interrupted an internal resynchronization algorithm starts automatically Radio interference is indicated on the screen by corresponding icons see page 2...

Страница 7: ...ion shafts fire doors etc must be taken into consideration during planning CAUTION Elevated humidity increases natural signal damping NOTE Recommendation Plan radio paths horizontally on a single leve...

Страница 8: ...404P FTL the selected installation location can be changed and optimized at any time without additional effort The installation location must have sufficient lighting using the device in unlit rooms s...

Страница 9: ...the housing For selecting the service level see p 24 06 Directional button down To set reduce value 07 Shift button For selecting the display or menus 08 Occupancy button Switching between comfort mo...

Страница 10: ...test installation location detected pres ence absence and vacation mode 09 Auto Learned utilization time profile is active automatic mode 10 Bars Displays the field strength quality of the receiving w...

Страница 11: ...ting the installation location NOTE The Test installation location function remains active as long as the text InSt is displayed see page 12 The room control module switches off again if a radio partn...

Страница 12: ...E If a radio partner has not been taught in after 15 minutes the room control module automatically switches off NOTE If the energy storage unit is empty the Sun icon will not appear even if the locati...

Страница 13: ...x 15 seconds following completion of the teach in process Once all wireless small actuators have synchronized successfully after the teach in process the antenna symbol is also displayed after a furth...

Страница 14: ...ope of delivery of the room control module WARNING Flush mounted cabling and piping at the installation location electricity gas water Cabling and piping can be damaged by drilling Check the installat...

Страница 15: ...ounting Flexible screw mounting 1 bar 2 adhesive numbers Wall mounting Flexible adhesive mounting with double sided transparent adhesive strips NOTE For a permanent connection remove any dust and grea...

Страница 16: ...urrent setpoint manually Briefly press the or button The setpoint to be set flashes Set the required setpoint using the or button The new selected value flashes for approx 5 seconds It is then automat...

Страница 17: ...then active again and the Auto icon appears on the display Example 1 Comfort temperature 20 C economy temperature 16 C Room used 6 00 AM 9 00 AM and 3 00 PM 9 00 PM Absence set manually by pressing th...

Страница 18: ...necessary to adequately ventilate the room To save on heating costs there is also an option to have the wireless small actuator close the valve Press and hold the button for 5 seconds The window icon...

Страница 19: ...repeatedly or the button to select the Conf function Hold down the Occupancy button for 5 seconds Release the Occupancy button The Set vacation menu item appears in the display Hold the Occupancy butt...

Страница 20: ...Briefly press the Occupancy button repeatedly or the button to select the Conf function Hold down the Occupancy button for 5 seconds The Set vacation menu item appears in the display Briefly press th...

Страница 21: ...European Time Setting the 12 24 hour display Hold down the Occupancy button for 5 seconds The text Menu briefly appears on the display followed by SETP Release the Occupancy button Briefly press the O...

Страница 22: ...peatedly or the button to select the Conf function Hold down the Occupancy button for 5 seconds The Set vacation menu item appears in the display Briefly press the Occupancy button repeatedly or the b...

Страница 23: ...ake any other actions the display will return to the initial display after 5 seconds Status message The status message is displayed For more information see page 28 Display of the taught in radio part...

Страница 24: ...uired setpoint The setpoint for comfort mode continues to flash while settings are being made Default setting Comfort mode 22 C Economy mode setpoint Briefly press the Occupancy button or the or butto...

Страница 25: ...or the button and the aforementioned functions will be offered one after the other If you do not take any other actions the display will return to the initial display after 5 seconds Teaching in the...

Страница 26: ...ible to connect to a Building and Energy Management System BEMS This makes it possible to generate additional functions such as Visualizing operating states Displaying trend curves e g for the room te...

Страница 27: ...fault settings and switch off room control module function will run The room control module switches off The display disappears NOTE The taught in radio partners are then deleted and the room control...

Страница 28: ...menu InSt On Test installation location evaluation function is active Antenna Flashes Possible to register wireless small actuators Antenna Er01 On On Radio connection partly interrupted 1 hour At le...

Страница 29: ...s must be carried out by an authorized service technician Please contact your supplier Rapid temperature drop If the room control module detects a rapid drop in temperature e g a window has been opene...

Страница 30: ...ian NOTE If the transmission function on the room control module malfunctions the MD15 FTL enters self controlled mode emergency mode The temperature is controlled to a fixed setpoint of 20 C using th...

Отзывы: