A
Page 8 / 14
User Manual
MD15-FTL-315
Datasheet 3.09-20.315-09-EN
Issue 2012-08-16
Technical Specifications
Technical Data
Nominal voltage
Battery-operated, 3 alkaline AA batteries (LR6 1.5 V 3,400 mAh)
Battery life
Approx. 3 years (depending on frequency and method of operation)
Measuring system
Integrated digital temperature sensor; 32 °F to 104 °; ± 32.9 ° at 77 °F
Interfaces
technoLink® wireless interface:
■
Radiogram: EnOcean radiogram
■
EEP A5-20-01 (Battery Powered Actuator)
■
Frequency: 315 MHz
■
Operating range: Approx. 32.808 inch in buildings (depending on building
structure)
■
Duty cycle: < 1 %
■
Transmission and reception interval: every 10 minutes
Motor switch-off
Actuator spindle: extending = load-dependant, retracting = path-dependant
Indicator
Status LED
Actuating noise
<31 dB (A)
Nominal stroke
Up to 0.118 inch
Travel time
0.59 inch/second
Positioning force
100 N (nominal)
Position indicator
Stroke range scale
Manual adjustment
Only when disconnected from the power supply
Socket for hexagon key under the actuator cover, key socket 0.157 inch
Housing
RAL 9010 pure white, battery compartment cover with mechanical locking
mechanism
Ambient temp.
32 °F to 392 °F
Degree of protection
IP40
Installation position
Anywhere from vertical to horizontal
Maintenance
Maintenance-free
Weight
6.35 oz