background image

A

Page 2 / 10

Product Description

BMR410

Datasheet 2.70-10.411-01-EN

Issue 2011-04-27

Important Information Regarding Product Safety

Safety Instructions

This data sheet contains information on installing and commissioning the product "BMR410". Each 
person who carries out work on this product must have read and understood this data sheet. If you 
have any questions that are not resolved by this data sheet, you can obtain further information from 
the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device.  Within the EU, these 
include regulations regarding occupational safety and accident prevention as well as those from the 
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other 
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified 
technicians. Qualified technicians are persons who are familiar with the described product and who 
can assess given tasks and recognize possible dangers due to technical training, knowledge and 
experience as well as knowledge of the appropriate regulations.

Legend

WARNING

Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.

CAUTION

Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.

!

NOTICE

Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not 
avoided.

NOTE

Indicates additional information that can simplify the work with the product for you.

Notes on Disposal

For disposal, the product is considered waste from electrical and electronic equipment (electronic 
waste) and must not be disposed of as household waste. Special treatment for specific components 
may be legally binding or ecologically sensible. The local and currently applicable legislation must be 
observed.

Содержание BMR410

Страница 1: ...I Tool or the PS4000 Additional main features of the BMR410 Native BACnet in accordance with DIN EN ISO 16484 5 BACnet server functionality facilitates communication with the BMS by Ethernet or modem...

Страница 2: ...o comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the...

Страница 3: ...ade plug For connecting a BMF400 input output module CAN Fieldbus DC 12 V 6 W module power supply 2 000 m 20 kBd RS232 Modem connection for fax SMS and BMS with BACnet in accordance with DIN EN ISO 16...

Страница 4: ...ML2 50 to 150 C BMRTool Configuration tool for BMR Z179 Cascade plug Replacement for power supply and bus cables Connection with cascade plug on the BMR one BMF A386KD Lithium battery with increased...

Страница 5: ...switch cabinet door Installation space one row 144 mm 8 HP 1 BMR for example Z63 Adapter frame for BMR modules Format 19 Installation space one row 288 mm 16 HP 1 BMR and 2 FBU for example Z62 Adapter...

Страница 6: ...on FBS51 04 maximum 1 can be installed on the BMR410 Room control modules DDC110 3 DDC110S DDC110 3S1 DDC110 4 Connection 1 DC 12 V for fieldbus power supply 2 Z179 cascade plug for power supply and c...

Страница 7: ...e ground connection 0 At the end of the fieldbus furthest point from the DDC controller install a terminating resistor of about 180 ohms between both data lines and The terminating resistor is include...

Страница 8: ...supplies you can use a fieldbus length of up to 2000 m Fieldbus Power Supply DC 12 V 6 W NOTE The BMF does not require any additional power supplies as it is supplied over the cascade plug and not fro...

Страница 9: ...anger of death by electrocution Mount or remove only when power is switched off Opening the Housing When mounting or connecting the fieldbus module it may be necessary to open the housing of the BMR41...

Страница 10: ...A Page 10 10 Product Description BMR410 Datasheet 2 70 10 411 01 EN Issue 2011 04 27 Removal WARNING Danger of death by electrocution Mount or remove only when power is switched off 1 2 3 4 5 6...