Kieback&Peter BMA0804 Скачать руководство пользователя страница 8

Product Description

BMA0804

J

Page 8 / 12

2.60-80.804-01-EN | 2019-01-17

Fieldbus

When connecting the fieldbus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two wires, 
twisted to a pair with plastic insulation and an electrostatic shield with a wire diameter of at least 
0.8 mm. Use a stranded pair of wires for the data lines (+ and -) and another free wire for the ground 
connection (0).
At the end of the fieldbus (furthest point from the DDC controller), install a terminating resistor of 
about 180 ohms between both data lines (+ and -). The terminating resistor is included with the DDC 
controller.
The maximum cable length for the Fieldbus is 2000 m.

Mounting

WARNING

Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.

Removal

TH 35-7.5

1

2

3

4

1

2

3

4

5

6

7

Содержание BMA0804

Страница 1: ...log outputs In manual mode the output signal can be set in 10 increments 0 100 0 2 10 V DC LED displays for the operating states of the inputs and outputs Communication is controlled via LED Label car...

Страница 2: ...y with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the descri...

Страница 3: ...displaying bus communication See chapter LED displays page 11 4 manual automatic rotary switches for automatic and manual operation of analog outputs 0 100 0 2 10 V DC Address switch Two rotary switc...

Страница 4: ...re conductor 0 2 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 2 1 5 mm2 Conductor cross section fine wire conductor 0 25 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 25 1 5 mm2 Conductor cross section fine wire conduct...

Страница 5: ...DDC4000e connection 44 7 0 0 9 60 0 143 5 19 20 17 18 19 20 17 18 83 82 81 86 85 84 88 87 93 92 91 96 95 94 98 97 CAN 12 24V Can Can 0V 53 52 51 GND 10V AI1 56 55 54 GND AI2 10V 59 58 57 GND AI3 10V...

Страница 6: ...uctors CAUTION 3 wire and 4 wire applications may not be mixed AO1 AO4 24V 24V 0V 24V 0V Y AI1 AI8 24V 24V 0V 24V 0V A 0 10VDC KP10 GND NTC 500k AO1 AO4 24V 24V 0V 24V 0V Y GND 0V AI1 AI8 24V 24V 0V 2...

Страница 7: ...by the commissioning technician NOTE The input output module can be connected to an existing fieldbus or switch cabinet bus Further information can be found in the DDC4000 project planning documentat...

Страница 8: ...d and another free wire for the ground connection 0 At the end of the fieldbus furthest point from the DDC controller install a terminating resistor of about 180 ohms between both data lines and The t...

Страница 9: ...ing to the sensor type table Setting range of the analog outputs 2 10V DC or 0 10 V DC Default value for the outputs in the event of bus failure or failure of the automation station NOTE Parameterizat...

Страница 10: ...planning documentation Before switching on the supply voltage check the electric installation and the device connections After configuring the device and switching on the supply voltage check the func...

Страница 11: ...hts up red LED status combination LED Meaning Cause off Module not in operation No operating voltage or operating voltage too low Yellow on green LED and red LED on Module in operation but there is a...

Страница 12: ...Product Description BMA0804 J Page 12 12 2 60 80 804 01 EN 2019 01 17...

Отзывы: