Introduction

This manual is designed as a guide to service personnel in the 
performance of operation, after use, inspection, maintenance, service 
and recharge of Kidde dry chemical hand portable fire extinguishers.

These instructions are written and intended to be used by those 
personnel already familiar with standard industry fire extinguisher safety 
procedures and practices. All fire extinguishers should be installed, 
inspected and maintained in accordance with the National Fire Protection 
Association Standard titled “Portable Fire Extinguishers” (NFPA-10) and 
all the requirements of the local authority having jurisdiction.

The instructions appearing in the National Fire Protection Association 
standard for portable fire extinguishers (NFPA-10), the Code of Federal 
Regulations,  and in the Compressed Gas Association (CGA) pamphlets are 
not generally repeated in this manual, except where they may emphasize 
or clarify a point. Hydrostatic testing of fire extinguisher cylinders for 
example is amply covered in NFPA-10 and CFR-49 part 180.209, which 
reference procedures in CGA pamphlets C-1, C-2 and C-6.

NFPA   

Government Printing Office 

Compressed Gas Association

1 Batterymarch Park 

P.O. Box 371954 

1235 Jefferson Davis HWY

Quincy, MA 02269 

Pittsburgh, PA 15250-7954 

Arlington, VA 22202

(617) 770-3000 

(202) 512-1802 

(703) 412-0900

www.nfpa.org 

www.bookstore.gpo.gov 

  www.cganet.

com

General Information

These Kidde extinguisher models are stored pressure hardware designs, 
which utilize steel and Aluminum agent cylinders. These models are 
charged with various types of Kidde dry chemical agents that  include 
Regular (Sodium Bicarbonate), Purple-K (Potassium Bicarbonate) and 
Multipurpose (Mono-Ammonium Phosphate). The extinguishers should 
only be pressurized with nitrogen. 

Never attempt to recharge a Kidde dry chemical fire extinguisher with 
any other dry chemical agent other than that specified on the original 
nameplate. 

Descriptions

The Kidde dry chemical extinguishers are “stored pressure” hardware 
designs that contain both the agent and expellant charge within the 
same cylinder. The extinguishers are engineered to effectively discharge 
the contents of the dry chemical charge.

These extinguishers consist of the following basic parts:

1.  Agent cylinder

 - contains the dry chemical agent and expellant    

  charge.

 

 

3

Содержание Pro 10 RM-4

Страница 1: ...2 lb 20 lb Agent Capacity Service Manual Stored Pressure Dry Chemical Hand Portable Fire Extinguishers Pro Line...

Страница 2: ...re to follow the instructions contained herein may result in property damage and or personal injury Important Notice Important Notice Any time an unusual extinguisher discrepancy is noticed or the spe...

Страница 3: ...eference procedures in CGA pamphlets C 1 C 2 and C 6 NFPA Government Printing Office Compressed Gas Association 1 Batterymarch Park P O Box 371954 1235 Jefferson Davis HWY Quincy MA 02269 Pittsburgh P...

Страница 4: ...her carrying handle transport the unit to a safe position upwind of the fire 4 Remove the hose nozzle from the retention clip if equipped and while keeping the extinguisher in a vertical position aim...

Страница 5: ...nitially placed into service and there after at approximately 30 day intervals When circumstances require more frequent intervals may be necessary Any time an inspection reveals a discrepancy maintena...

Страница 6: ...isher is installed in its proper location and that it is readily accessible Most Kidde dry chemical extinguisher models are approved for temperature ranges between 40 F to 120 F 2 Remove extinguisher...

Страница 7: ...ul not to accidentally discharge the extinguisher pull and remove the ring pin breaking the visual inspection seal to ensure the ring pin functions freely and is not bent damaged or corroded Re instal...

Страница 8: ...miliar with the contents of this manual to recognize any equipment conditions or discrepancies that might prohibit the recharge of the extinguisher or direct further equipment maintenance or repair 1...

Страница 9: ...discoloration or contaminants If necessary remove extinguisher from service and replace 10 Add the proper type and quantity of Kidde dry chemical agent specified on the extinguisher nameplate recharg...

Страница 10: ...sher surfaces Note Prior to placing recharged dry chemical extinguishers back into fire protection service Kidde recommends the extinguisher pressure gauge reading be re verified a minimum of 24 hours...

Страница 11: ...hen be flushed clean dried and visually re examined after testing The discharge valve assembly should be removed prior to hydrostatic testing of the cylinder Refer to Note in Step 5 of Recharge instru...

Страница 12: ...eads outside green area Check ambient temperature correlation De pressurize and recharge or replace Pressure gauge damaged De pressurize and replace Gauge operating pressure differs from label De pres...

Страница 13: ...Pro 2 75 RM 5 Pro 2 75 RM 5 Pro 4 TCM 4 Pro 4 TCM 4 Pro 4 TCM 4 Part Number 466227 466227 466228 466228 466228 466288 1 320337 320337 320338 440310 2 21005736 21005736 21005736 21005737 3 21005739 210...

Страница 14: ...10 Hose strap Model Pro 10 TCM 5 Pro 10 TCM 6 Pro 20 RM Pro 20 RM Pro 20 RM 4 Pro 20 RM Pro 20 RM Pro 20 RM 5 Part Number 466204 466204 46620 46620 466207 7 7 466207 1 440329 440329 440127 440127 2 21...

Страница 15: ...ing 4 O ring kit includes valve o ring syphon tube o ring stem assembly stem assembly spring 5 Wall hanger 6 Retention bracket 7 Pull pin 8 Pressure gauge 9 Hanger loop and screw 10 Hose strap Model P...

Страница 16: ...Kidde Residential and Commercial 1394 South Third Street Mebane NC 27302 9711 Phone 1 800 880 6788 Manual P N 300290 Copyright Kidde 2005...

Отзывы:

Похожие инструкции для Pro 10 RM-4