Architectural and Engineering 

Specifications

  The smoke alarm shall be Kidde model i12080 or approved equal. It shall be  
  powered by a 120VAC, 60Hz source along with a 9V battery back up. The unit 
shall incorporate an ionization sensor with nominal sensitivity of .50 to .85%/ft.  
The temperature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C) 
and the humidity operation range shall be 5% - 95% relative humidity.
  The smoke alarm can be installed on any standard single gang electrical box, 
up to a 4” octagon junction box.  The electrical connection (to the alarm) shall be 
made with a plug-in connector.  A maximum of 24 Kidde devices can be inter-
connected in a multiple station arrangement.  The interconnect system must not 
exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices, 
of which 12 can be smoke alarms.  With 18 initiation devices (smoke, heat, CO, 
etc.), interconnected, it is still possible to interconnect 6 strobe lights and or relay 
modules.  The unit shall provide optional tamper resistance that deters removal of 
the unit from the wall or ceiling.
  The alarm shall include a safety light that shall be powered by a 9V alkaline  
battery.  The safety light shall provide 15 minutes of light when the alarm is  
sounding. The alarm shall include a test button that will electronically simulate  
the presence of smoke and cause the unit to go into alarm. This sequence tests  
the unit’s electronics, battery and horn to ensure proper operation.
  The unit shall include a piezoelectric horn that is rated at 85dB at 10 feet.  
The unit shall include Smart Hush

TM

 feature that silences the unit for approximately 

7 minutes if a nuisance condition occurs. The unit shall also include a low battery 
warning utilizing a brief alarm chirp every 30-40 seconds for a minimum of  
seven (7) days.
  The unit shall incorporate red and green LED indicators. The green LED (when  
illuminated) indicates the presence of AC power. The red LED (located under the 
TEST/Hush button) has 

four modes of operation:

Standby Condition:

 The red LED will flash every 30-40 seconds to indicate that 

the smoke alarm is operating properly. 

Alarm Condition:

  When the alarm senses 

products of combustion and goes into alarm the red LED will flash one flash per 
second.  The flashing LED and pulsating alarm will continue until the air is cleared. 
When units are interconnected, only the red LED of the alarm that senses the 
smoke or is being tested (the originating unit) will flash.  All other units in the  
interconnected system will sound an alarm but their red LED’s will NOT flash.

 

Alarm Memory:

  This smoke alarm is equipped with an alarm memory, which  

provides a visual indication when an alarm has been activated.  The red LED will 
illuminate for about 1.5 seconds every 16 seconds to indicate the memory  
condition.  

Smart Hush

TM

 Mode:

  The red LED will illuminate for 1.5  seconds every  

8 seconds, indicating the smoke alarm is in the Smart Hush

TM

 Mode. 

  The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 
11), The State of California Fire Marshall, NFPA 101 (Oneand two family dwellings) 
Federal Housing Authority (FHA), Housing and Urban Development (HUD).  
It shall also include a 10-year manufacture’s limited warranty.

120V AC/DC Smoke Alarm

Safety Light

Part Number 21006379

Model i12080

Technical Specifications

Model: 

i12080

UPC: 

0-47871-40382-0

Power Source: 

120VAC (

80mA), 

 60HZ, 9V battery backup

Sensor: 

Ionization

Audio Alarm: 

85dB at 10ft

Temperature Range:  40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 

5% - 95% relative humidity (RH)

Size: 

5.6” in diameter x 1.55” depth

Weight: 

.5lb

Interconnects: 

Up to 24 Kidde devices

LED: 

Green, receiving ac power

 

Red, 4 modes of operation

Warranty: 

10 year limited

Installation of Smoke Alarm

The smoke alarm must be installed to comply with all local codes having jurisdiction in 
your area. All wiring shall be in accordance with articles 210 and 300.3(B) of the US 
National Electrical Code, ANSI / NFPA 70 and NFPA 72. The multiple station intercon-
nect wiring must be in the same raceway as the AC power wiring. In addition the 
resistance if the interconnect wiring shall be a maximum of 10 ohms. Make certain all 
alarms are wired to a single, continuous (non-switched) powerline, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft.of wire can be used in  
the interconnect system. Use standard UL listed household wire as required by code.

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L

N

First 

Alarm

Additional 

Alarms

5.6”

1.5”

Ordering Information

Ordering  

 

 

 

Dimensions 

 

Case/ 

Layers/  

Skid 

Number 

UPC 

I2F5 

Pack Quantity 

(w x d x h inches) 

Weight  Skid 

Skid 

Weight 

N/A 

0-47871-40382-0 

N/A 

individual* 

5.75 x 1.5 x 5.75  0.5 lbs  N/A 

N/A 

N/A

21006379 

0-47871-40382-0 

100-47871-40382-7 

Cut Case (6 units) 

6.5 x 13.25 x 6 

3 lbs 

147 

441 lbs

*Not for sale by individual unit

1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com

Distributed by:

P/N: KL-i12080 sheet 

rev. 01-2009