Architectural and Engineering
Specifications
The smoke alarm shall be Kidde model i12080 or approved equal. It shall be
powered by a 120VAC, 60Hz source along with a 9V battery back up. The unit
shall incorporate an ionization sensor with nominal sensitivity of .50 to .85%/ft.
The temperature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C)
and the humidity operation range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box,
up to a 4” octagon junction box. The electrical connection (to the alarm) shall be
made with a plug-in connector. A maximum of 24 Kidde devices can be inter-
connected in a multiple station arrangement. The interconnect system must not
exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices,
of which 12 can be smoke alarms. With 18 initiation devices (smoke, heat, CO,
etc.), interconnected, it is still possible to interconnect 6 strobe lights and or relay
modules. The unit shall provide optional tamper resistance that deters removal of
the unit from the wall or ceiling.
The alarm shall include a safety light that shall be powered by a 9V alkaline
battery. The safety light shall provide 15 minutes of light when the alarm is
sounding. The alarm shall include a test button that will electronically simulate
the presence of smoke and cause the unit to go into alarm. This sequence tests
the unit’s electronics, battery and horn to ensure proper operation.
The unit shall include a piezoelectric horn that is rated at 85dB at 10 feet.
The unit shall include Smart Hush
TM
feature that silences the unit for approximately
7 minutes if a nuisance condition occurs. The unit shall also include a low battery
warning utilizing a brief alarm chirp every 30-40 seconds for a minimum of
seven (7) days.
The unit shall incorporate red and green LED indicators. The green LED (when
illuminated) indicates the presence of AC power. The red LED (located under the
TEST/Hush button) has
four modes of operation:
Standby Condition:
The red LED will flash every 30-40 seconds to indicate that
the smoke alarm is operating properly.
Alarm Condition:
When the alarm senses
products of combustion and goes into alarm the red LED will flash one flash per
second. The flashing LED and pulsating alarm will continue until the air is cleared.
When units are interconnected, only the red LED of the alarm that senses the
smoke or is being tested (the originating unit) will flash. All other units in the
interconnected system will sound an alarm but their red LED’s will NOT flash.
Alarm Memory:
This smoke alarm is equipped with an alarm memory, which
provides a visual indication when an alarm has been activated. The red LED will
illuminate for about 1.5 seconds every 16 seconds to indicate the memory
condition.
Smart Hush
TM
Mode:
The red LED will illuminate for 1.5 seconds every
8 seconds, indicating the smoke alarm is in the Smart Hush
TM
Mode.
The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter
11), The State of California Fire Marshall, NFPA 101 (Oneand two family dwellings)
Federal Housing Authority (FHA), Housing and Urban Development (HUD).
It shall also include a 10-year manufacture’s limited warranty.
120V AC/DC Smoke Alarm
Safety Light
Part Number 21006379
Model i12080
Technical Specifications
Model:
i12080
UPC:
0-47871-40382-0
Power Source:
120VAC (
80mA),
60HZ, 9V battery backup
Sensor:
Ionization
Audio Alarm:
85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range:
5% - 95% relative humidity (RH)
Size:
5.6” in diameter x 1.55” depth
Weight:
.5lb
Interconnects:
Up to 24 Kidde devices
LED:
Green, receiving ac power
Red, 4 modes of operation
Warranty:
10 year limited
Installation of Smoke Alarm
The smoke alarm must be installed to comply with all local codes having jurisdiction in
your area. All wiring shall be in accordance with articles 210 and 300.3(B) of the US
National Electrical Code, ANSI / NFPA 70 and NFPA 72. The multiple station intercon-
nect wiring must be in the same raceway as the AC power wiring. In addition the
resistance if the interconnect wiring shall be a maximum of 10 ohms. Make certain all
alarms are wired to a single, continuous (non-switched) powerline, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft.of wire can be used in
the interconnect system. Use standard UL listed household wire as required by code.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First
Alarm
Additional
Alarms
5.6”
1.5”
Ordering Information
Ordering
Dimensions
Case/
Layers/
Skid
Number
UPC
I2F5
Pack Quantity
(w x d x h inches)
Weight Skid
Skid
Weight
N/A
0-47871-40382-0
N/A
individual*
5.75 x 1.5 x 5.75 0.5 lbs N/A
N/A
N/A
21006379
0-47871-40382-0
100-47871-40382-7
Cut Case (6 units)
6.5 x 13.25 x 6
3 lbs
147
7
441 lbs
*Not for sale by individual unit
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-i12080 sheet
rev. 01-2009