Architectural and Engineering 

Specifications

The smoke alarm shall be Kidde model i12020 or approved equal.It shall 

be powered by a 120VAC, 60Hz source. The unit shall incorporate an ion-
ization sensor with nominal sensitivity of 0.50 to .83%/ft. The temperature 
operation range shall be between 40˚F (4˚C) to 100˚F (38˚C) and the humid-
ity operating range shall be 5% - 95% relative humidity.

The smoke alarm can be installed on any standard single gang electrical 

box, up to a 4” octagon junction box. The electrical connection (to the 
alarm) shall be made with a plug-in connector.  A maximum of 24 Kidde 
devices can be interconnected in a multiple station arrangement. The 
interconnect system must not exceed the NFPA (National Fire Protection 
Association) limit of 18 initiating devices, of which 12 can be smoke alarms.  
With 18 initiating devices (Smoke, heat, CO, etc.), interconnected, it is still  
possible to interconnect 6 strobe lights and or relay modules. The alarm shall 
provide optional tamper resistance that deters removal of the unit from the 
wall or ceiling. 

The alarm shall include a piezoelectric horn that is rated at 85 decibels at 

10 feet. The unit shall include Smart Hush

TM

 feature that silences the unit for 

approximately 7 minutes if a nuisance condition occurs. The unit shall incorpo-
rate red and green LED indicators. The green LED (when illuminated) indicates 
the presence of AC power. The red LED (located under the TEST/Hush but-
ton) has 

four modes of operation:

Standby Condition:

 The red LED will flash every 30-40 seconds to indi-

cate that the smoke alarm is operating properly. 

Alarm Condition:

  When 

the alarm senses products of combustion and goes into alarm the red LED 
will flash one flash per second.  The flashing LED and pulsating alarm will 
continue until the air is cleared.When units are interconnected, only the red 
LED of the alarm that senses the smoke or is being tested (the originating 
unit) will flash.  All other units in the interconnected system will sound an 
alarm but their red LED’s will NOT flash. 

Alarm Memory:

  This smoke alarm 

is equipped with an alarm memory, which provides a visual indication when 
an alarm has been activated.  The red LED will illuminate for about 1.5  
seconds every 16 seconds to indicate the memory condition.  

Smart Hush

TM

 

Mode: 

 The red LED will illuminate for 1.5 seconds every 8 seconds,  

indicating the smoke alarm is in the Smart Hush

TM

 Mode. 

The unit shall at a minimum meet the requirements of UL217, NFPA72, 

(chapter 11), The State of California Fire Marshall, NFPA101 (One and two 
family dwellings), Federal Housing Authority (FHA, Housing and Urban 
Development (HUD).

120V AC Wire-In Smoke Alarm

For Basic Use

Part# 21006374  
Model i12020

Technical Specifications

Model: 

i12020

UPC: 

0-47871-40379-0

Power Source: 

120VAC (

80mA)

Sensor: 

Ionization

Audio Alarm: 

85dB at 10ft

Temperature Range:  40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 

5%-95% relative humidity (RH)

Size: 

5.6” in diameter x 1.55” depth

Weight: 

.5lbs

Interconnects: 

Up to 24 Kidde devices

LED: 

Green, receiving ac power

 

Red, 4 modes of operation

Warranty: 

10 year limited

Installation of Smoke Alarm

The smoke alarm must be installed to comply with all local codes having jurisdic-
tion in your area. All wiring shall be in accordance with articles 210 and 300.3(B) 
of the US National Electrical Code, ANSI / NFPA 70 and NFPA 72. The multiple 
station interconnect wiring must be in the same raceway as the AC power wiring. 
In addition the resistance if the interconnect wiring shall be a maximum of 10 
ohms.  Make certain all alarms are wired to a single, continuous (non-switched) 
power line, which is not protected by a ground fault interrupter. A maximum of 
1000 ft. of wire can be used in the interconnect system. Use standard UL listed 
household wire as required by code.