2 / 4
P/N 3102667-EN • REV 002 • ISS 31AUG20
Figure 3: Strobe switch settings
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
Caution:
Electrical supervision requires that you break the wire run at
each terminal. Do not loop the notification circuit field wires around the
terminals.
To install the appliance:
1. Using the screws supplied with the wiring plate, attach the wiring
plate and, if used, the trim plate to the electrical box. See Figure 4.
Do not overtighten the screws.
The trim plate is ordered separately.
2. Connect the field wiring. Observe signal polarity for the appliance
to operate properly. See Figure 5.
3. Remove the shorting clip (Figure 5, item 5). Retain for future use.
4. Plug the appliance into the wiring plate by setting the appliance on
the top of the wiring plate, and then snapping the bottom into
place. See Figure 6.
To unplug the appliance, press the spring clip on the bottom, and
then lift the appliance away from the mounting plate.
5. Test the unit for proper operation.
Figure 4: Typical electrical box mounting
(1) Electrical box
(2) Trim plate (optional)
(3) Wiring plate (required)
(4) Machine screw (2X, supplied with wiring plate)
(5) Notification appliance
(6) Shorting clip
Figure 5: Typical surface box mounting
(1) Surface box
(2) Wiring plate (required)
(3) Machine screw (2X, supplied with wiring plate)
(4) Notification appliance
(5) Shorting clip
110
15
30
75
(3)
(4)
(2)
(1)
(5)
(6)
(1)
(2)
(3)
(5)
(4)
firealarmresources.com