background image

 

2 / 4 

 

P/N 3102550-EN • REV 002 • ISS 03APR18 

Figure 2: Light and sound output settings 

 

(1)  Constant, low dB 
(2)  Constant, high dB 
(3)  T3 temporal, low dB 
(4)  T3 temporal, high dB 

 (5) 

75 

candela 

(6) 30 candela 
(7) 15 candela 

Installation 

Install and wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

Caution: 

Electrical supervision requires that you break the wire run at 

each terminal. Do not loop the signaling circuit field wires around the 
terminals. 

Note: 

Do not use Genesis EG1 Series strobe and horn-strobe 

signaling appliances in applications where signal power is cycled on 
and off, such as coded or private mode signaling systems. 

To install the appliance: 

1.  Remove the appliance cover. 

2.  Connect the field wiring. Observe signal polarity for the appliance 

to operate properly. See Figure 3. 

3.  Attach the appliance and, if used, the trim ring backplate to the 

electrical box. Do not overtighten the screws. See Figure 4. 

4.  Replace the cover by hooking it to the top of the appliance, and 

then snapping the bottom into place. See Figure 1. 

5.  Test the unit for proper operation. 

Figure 3: Wiring 

 

(1)  Horn/strobe circuit in (signal polarity shown in the active condition) 
(2)  Horn/strobe circuit out 

Figure 4: Mounting on a 1-gang electrical box 

 

(1) Electrical box 
(2)  EG1 Series signaling appliance 
(3) Captive screw (2X) 
(4) Appliance cover 

Note: 

Using a trim ring is optional except when installing the signaling 

appliance on electrical boxes greater than three inches wide. For 
installation instructions when using a trim ring, see 

Genesis EG1 

Series Trim Ring Installation Sheet 

(P/N 3102552-EN).  

Maintenance and testing 

Caution: 

Equipment damage hazard. To maintain the required agency 

listings, do not change factory-applied finishes. 

This unit is not serviceable or repairable. Should the unit fail to 
operate, contact the supplier for replacement. 
Perform a visual and operational inspection in accordance with 
applicable codes and standards or as directed by the local authority 
having jurisdiction. 
Input wiring test points are available on the front of the appliance when 
the cover is removed. The test points let you easily spot-check the field 
circuit wiring without the need to remove the appliance from the wall. 
See Figure 5. 

Figure 5: Test points 

 

Note: 

Marking indicates signal polarity when the circuit is active. 

(1) (2) (3) (4)

(6)
(7)

(5)

+

+

(1)

(2)

(1)

(2)

(3)

(4)

Содержание Genesis EG1 Series

Страница 1: ...strobe white no marking Genesis EG1 Series signaling appliances feature Field configurable horn and strobe outputs See Figure 2 Enhanced synchronization circuitry to comply with the latest requirements of UL 1638 and CAN ULC S526 Input wiring test points on the front of the appliance when the cover is removed Note Synchronized operation requires a separately installed synchronization device See th...

Страница 2: ...unit for proper operation Figure 3 Wiring 1 Horn strobe circuit in signal polarity shown in the active condition 2 Horn strobe circuit out Figure 4 Mounting on a 1 gang electrical box 1 Electrical box 2 EG1 Series signaling appliance 3 Captive screw 2X 4 Appliance cover Note Using a trim ring is optional except when installing the signaling appliance on electrical boxes greater than three inches w...

Страница 3: ...WR 15 30 75 24 mA 32 mA Table 6 Operating current at 16 to 33 VDC horn strobe models Strobe setting Sound setting 16 to 33 VDC 16 to 33 VFWR 15 30 75 C LOW T LOW 35 mA 43 mA C HIGH T HIGH 45 mA 55 mA Table 7 Sound output horn and horn strobe models Sound setting Reverberant UL 464 Anechoic CAN ULC S525 C LOW T LOW 80 dBA 86 dBA C HIGH T HIGH 86 dBA 92 dBA Table 8 Sound pattern ULC Axis Angle Chang...

Страница 4: ...ubject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Industry Canada compliance This Class A digital apparatus complies with Canadian ICES 003 Environmental class Indoor dry Contact information For contact information see www kiddelifesafety com H W D...