Proper Electrode Location

Proper location of the electrode assembly is important for 
optimum system performance.  It is recommended that the
electrode assembly be mounted temporarily using clamps or other
suitable means to check the system before permanently mounting
the assembly.  The electrode assembly should be located so that
the tips are inside the flame envelope and about 1/2 inch (10 mm)
above the base of the flame.  See Figures 3a and 3b.

CAUTIONS:

1.

Ceramic insulators should not be in or close to the flame.

2.

Electrodes should have a gap spacing of 0.125± 0.031 inch 
(3.12 ± 0.81 mm).  If this spacing is not correct, the assembly
must be replaced or adjusted (see troubleshooting) 

3. 

Exceeding the temperature limits can cause 
nuisance lockouts and premature electrode failure.

4.

Electrodes must be placed where they are not exposed 
to the appliance user in normal operation.

Flame Sensing

Flame sensing is achieved using the principal of flame 
rectification.  Flame rectification relies on the current passing 
from ground through the flame to the sense rod. The minimum
flame current necessary to keep the system operating is 
1.0 microamperes.  

SINGLE SPARK AND SENSE

Figure 3a

REMOTE FLAME SENSE

Figure 3b

ITEM

#

1
2
3
4
5
6
7
8
9

DESCRIPTION

Mounting Bracket
1/4” Q.C. High Voltage Terminal
3/16” Q.C. Flame Sense Terminal
Spark, H.V. Ceramic Tube
Sense Electrode Ceramic Tube
Press Ring
Flame Sense Electrode
Ground Rod 
Spark Electrode, High Voltage

STANDARD 

MATERIAL

CSA rated at 1800°F

Steel Cu Flashed
Nickel Plated Steel
Nickel Plated Steel
L-3 Steatite 
L-3 Steatite
Spring Steel
Kanthal D
Kanthal D
Kanthal D

#

!

1

2

3

4

6

7

5

8

9

TYPICAL SPARK ELECTRODE 
WITH INTEGRAL REMOTE FLAME SENSE

Page 4

Series 35-71, 20 VAC Direct Spark Ignition Control

Figure 4

FLAME CURRENT CHECK:  SINGLE SPARK & SENSE AND
REMOTE SENSE

To measure flame current, disconnect the input voltage, and attach
the leads from a DC current meter with a microampere range to
FC+ and FC- terminals to the 35-70 flame sense test pins per
Figure 4.  Reconnect the input voltage and initiate a 
call for heat.  After sparking is complete and the flame is 
established the meter should read 1.0 microamperes DC or 
higher.  If meter reads below "0" on the scale, meter leads are
reversed.  Disconnect power and reconnect meter leads 
for proper polarity.

www.fenwalcontrols.com

1-800-FENWAL-1

Содержание FENWAL 35-71 Series

Страница 1: ...main burner flame to ensure safe system operation The on board diagnostics with LED output provide assistance with troubleshooting to ensure safe and efficient burner operation Agency Certifications R...

Страница 2: ...resumes If the burner fails to light after the third try the control will de energize the gas valve and go into lockout mode NOTE The Recycle feature option requires a special part number that is det...

Страница 3: ...to 175 F 40 C to 80 C 120 VAC 1 0 microamp minimum 0 8 seconds maximum Natural LP and manufactured Line frequency 50 60 Hz Conformal coated to operate to 95 R H See drawings on Page 8 Integral stand o...

Страница 4: ...on relies on the current passing from ground through the flame to the sense rod The minimum flame current necessary to keep the system operating is 1 0 microamperes SINGLE SPARK AND SENSE Figure 3a RE...

Страница 5: ...se electrodes are designed for on site customization Cut and bend these to fit your application and then send the formed electrode back for Fenwal to detail or send us a print and we will provide you...

Страница 6: ...anded PVC Gray Only 600 V UL CSA Listed 200 C 392 F 18 gage stranded PVC Electrode Assemblies continued REMOTE SENSE Part Number 05 129864 7XX Part Number 05 129864 8XX Part Number 22 100001 080 Part...

Страница 7: ...determined complete the part number by replacing the last two digits XX with the length in inches L dimension Standard wire lengths are 12 18 24 30 36 48 and 60 inches Example 05 129608 018 18 inches...

Страница 8: ...sense Thermostat power off reset 6 3 try remote sense Thermostat power off reset 7 3 try single spark and sense Automatic reset 8 3 try remote sense Automatic reset X X X 35 71 5 X X X 400 MAIN STREE...

Отзывы: