PERIODIC MAINTENANCE
PRE-TRIP
Verify the Protection Panel’s green ‘SYSTEM OK’ indicator is illuminated and that all
other indicators are OFF.
Press the TEST/RESET Switch. The following should occur:
o
All indicators and switches on the Protection Panel should illuminate.
o
An audible alarm should sound.
EVERY 3000 MILES OR MONTHLY (WHICHEVER OCCURS FIRST)
General
Verify neither the protected equipment nor the hazard has changed
Verify no obvious physical damage or condition exists that might prevent system
operation
Protection Panel
Verify all warning indicators and the audible alarm are operational by pressing the
‘TEST/RESET’ button
Manual Activation Switch
Verify tamper seal is intact and access to switch is unobstructed
Fire Detectors
Spot Thermal Detector
Verify there is no obvious physical damage and the device is free of excess
contamination (dirt, oil, grease, etc). If necessary, clean using water soaked non-
abrasive towel.
Gas Leak Detectors
Verify status indicator on the detector is on solid green
Verify there is no obvious physical damage and that unit is free of excess contamination
(dirt, oil, grease, etc) - if necessary, clean using water soaked non-abrasive towel.
CAUTION: DO NOT USE CHEMICAL CLEANERS
Verify no silicone based materials have been used near detector
Electrical Harness
Verify electrical connectors and electrical wiring have no visible damage and all
connectors are securely seated