Routings for Power-Limited and Non-Power-Limited Wiring
P/N 06-237058-001
E-1
February 2012
APPENDIX E
ROUTINGS FOR POWER-LIMITED AND NON-POWER-
LIMITED WIRING
This appendix provides guidelines for power-limited and non-power-limited wiring requirements.
The following wiring requirements shall be observed:
•
Power-limited and non-power-limited wiring must be physically separated within the control unit
enclosure.
•
All power-limited wiring must be separated by at least 1/4-inch (6 mm) from any
non-power-limited wiring.
•
Non-power-limited wiring must be placed inside a conduit.
•
Power-limited and non-power-limited wiring cannot enter and exit the control unit enclosure
through the same knockout or conduit.
•
Cables from switching power supply units must be kept a minimum of 1/4-inch (6 mm) away
from field wiring coming into the Main Controller Board (MCB) and any installed Expansion
Cards.
•
Location of expansion cards in the Expansion Card Cage, combined with configuration of their
output circuits (available optionally for either power-limited or non-power-limited applications),
MUST take into consideration maintaining minimally 1/4-inch of separation between wiring to
these circuits.
Figure E-1 and Figure E-2 show examples of typical wiring for power-limited and non-power-limited
circuits in a 3-Tiered Enclosure and location of enclosure knockouts. Figure E-3 shows typical
wiring for power-limited and non-power-limited circuits in a 2-Tiered Enclosure with location of
knockouts also noted.
Figures E4 through E6 are photographs of an ARIES NET
Link
control unit where standard electrical
tie wraps and clamps, in addition to the enclosure’s standoffs, brackets and card cage frame, are used
to properly dress power-limited and non-power-limited wiring with the required 1/4-in. minimum
separation.
Содержание ARIES NETLink
Страница 2: ......
Страница 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 78: ...Installation February 2012 2 22 P N 06 237058 001 Figure 2 17 Installing the Expansion Card Cage ...
Страница 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 166: ...Configuration and Programming February 2012 3 54 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 203: ...Networking P N 06 237058 001 5 9 February 2012 Figure 5 5 Processing Group 0 Networked Control Unit Interactions ...
Страница 222: ...Testing and Maintenance February 2012 6 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...List of Agency Listed Compatible Devices February 2012 C 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 270: ...FM Rules for Preaction Deluge Systems February 2012 D 2 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 286: ...ARIES NETLINK For City Of Chicago Applications February 2012 G 6 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 293: ......