Operating & Maintenance
SEM & SE200ES Pressurisation
Set
7). Product Identification Code(s).
All KGN Pillinger SE200E pressurisation sets are identified by the below coding, each product will
have this clearly affixed to the set:
SE200 ES
TS
-
Twin Pump
Single System
Twin Pump
Dual System
SEM
Pressurisation
Set - Mini
8). Installation
➢
Prior to installation the pressurisation set should be thoroughly checked for any damage
during transportation and reported immediately to KGN Pillinger and not installed.
➢
The unit is required to be installed in a ventilated, dry frost-free position, allowing 0.5m
clearance on all sides and front to enable general maintenance.
➢
Connect the SE200ES pressurisation set water inlet
½”(right side of cabinet) to a suitable
water supply.
➢
Install an isolation valve (not provided by KGN) to aid maintenance.
➢
Connect to the overflow outlet (right hand side of unit) and position an overflow pipe to be
noticed and rectified (if required).
➢
Connect the 15mm compression discharge port (right hand side of cabinet) to the system
inlet.