background image

„Installation and operation manual for fireplace insert”                        

KFDECOENG1.1562012

 

 

18 

Then, push the door ajar, leaving a small gap (of a few centimetres). This stage of lighting up 
requires  constant  control  of  fire  by  the  user,  allowing  determination  of  the  right  moment  to 
add  thick  chunks  of  wood  and  to  close  the  door.  From  now  on,  the  process  of  lighting  up 
proceeds  with  the  air  inlet  (bottom  lever)  open  to  the  maximum  and  with  open  chimney 
damper (top lever). The fireplace may burn at these settings for a few up to over ten minutes, 
until  fire  spreads  over  all  fuel  in  the  furnace.  By  then,  the  turbine  pushing  hot  air  into 
particular  rooms  should  be  activated  automatically,  if  the  hot  air  distribution  system  is 
equipped with a turbine. Now, add a full load of fuel (5 kg of wood 

– several finer chunks with 

the  length  of  33  cm)  and  close  the  chimney  damper.  From  now  on,  control  the  combustion 
rate exclusively by the supply of air (handle at the bottom of the furnace). The position of the 
adjustment handle and, consequently, the combustion rate are to be set so as not to exceed 
the combustion rate of 4 kg of wood per hour (in most cases, this corresponds to the central 
position  of  the  bottom  handle).  Greater  combustion  rate  involves  emission  of  power 
exceeding rated power of the insert, and involves the risk of thermal overloading. From now 
on,  the  fireplace  does  not  require  the  user’s  intervention  except  for  adding  wood.  the 
Chimney  damper  must  be  opened  whenever  the  door  of  the  furnace  is  to  be  opened, 
otherwise,  smoke from the furnace will come out  to the room. The frequency of  adding  fuel 
depends  on  several  factors:  position  of  adjustment  elements,  quality  of  used  wood  and 
chimney draught which also depends on the weather. 
An  excessive  quantity  of  wood  and  an  excessive  quantity  of  combustion  air  may  cause 
overheating and, consequently, damage to the fireplace insert. 
When the door of the fireplace insert is being opened (for lighting up and adding of fuel), the 
chimney damper of  the fireplace insert must be opened. Otherwise,  smoke will  come out to 
the  room  where  the  fireplace  is  installed.  During  normal  operation  of  the  fireplace,  the 
chimney  damper  ought  to  be  closed.  To  avoid  smoking  of  the  room,  fuel  should  only  be 
supplemented during the final stage of combustion, i.e. when only a layer of embers remains 
in the furnace. The furnace door is to be opened slowly to equalise the pressures and avoid 
smoking, and it is to be closed immediately after adding fuel. 
If fuel  is added at  longer  intervals,  when  there  is  only  a  layer  of embers  in  the furnace,  the 
lighting up process ought to be divided into two stages. During the first stage, add only 1 or 2 
small  chunks  of  wood  into  the  furnace  when  the  chimney  damper  and  air  inlet  are  open. 
Once  fire  spreads  over  the  chunks,  in  stage  two  add  the  right  quantity  of  fuel  and  set  the 
adjustment levers appropriately. 
If  a  large  quantity  of  wood  is  placed  over  a  layer  of  embers  (in  particularly,  fine  pieces  of 
wood with thick bark), this may result in sudden production of considerable quantities of gas 
in the furnace and its ignition. To eliminate that hazard, fuel ought to be added in a manner 
preventing “stifling” of the flame and accumulation of  gases.  Combustion of  gases ought to 
take  place  on  an  ongoing  basis,  i.e.  the  user  should  aim  at  keeping  at  least  a  small  flame 
visible inside the furnace. 

Apart  from  adjustment  of  combustion  air  inlet  (bottom  lever),  intensity  of  the  combustion 
process and, as a consequence, thermal efficiency of the fireplace insert depend as well on 
chimney parameters. In case of insufficient negative pressure (draught), the chimney damper 
(top  lever)  may  be  opened  when  the  fireplace  is  lit  up;  in  that  case,  position  of  air  supply 
adjustment  lever  (bottom  lever)  is  to  be  adjusted  accordingly.  However,  this  is  not 
recommended as it involves reduction of fireplace thermal efficiency. 

In  order  to  light  up  the  fireplace  insert  properly  for  the  first  time  (the  product  is  processed 
using lacquers resistant to high temperatures), please remember that: 

  construction materials used for building the fireplace are not homogeneous: steel and 

chamotte elements are used, 

Содержание ECO 70

Страница 1: ...Installation and operation manual for fireplace insert KFD ECO i70 KFD ECO 70 KFD ECO 70 L R ...

Страница 2: ...l regulations ought to be observed 1 Construction of the fireplace 4 1 1 Placement of the fireplace 4 1 2 Chimney 5 1 3 Tip of the chimney 9 1 4 Ventilation conditions for KFD ECO fireplace insert installation 10 1 5 Supply of outdoor air 10 1 6 Installation of the fireplace enclosure 11 1 7 Connection of hot air distribution pipes in the hood 13 1 8 Protection of the beam in the fireplace enclosu...

Страница 3: ... fireplace insert KFDECOENG1 1562012 3 3 Selection of chimney parameters chart 24 4 List of materials recommended for construction of the fireplace 25 5 Tables 26 6 Troubleshooting 28 7 Drawings of the KFD ECO inserts 31 8 Inspection log 32 ...

Страница 4: ...ot contain any combustible materials or non heat resistant materials electrical or hydraulic installations the fireplace must not be installed in a room with mechanical exhausts ventilation If the fireplace can be installed in a room with mechanical ventilation please observe local regulations floor under the fireplace and 60 cm in front of the fireplace must be made from incombustible materials e...

Страница 5: ...eliminates the insert movement phenomenon due to tensions caused by thermal expansion if immovable connection elements are used Moreover if immovable connections are installed thermal compensation of the expanding pipe needs to be insured and ducts must have inspection holes allowing access through openings in the fireplace enclosure e g grids in the hood KFD ECO inserts require installation of an...

Страница 6: ...hould not be concerned with Please observer appropriate EN norms and local regulation which concern the chimney Figure 4 presents regulatory requirements related to height of the chimney with respect to the roof ridge Basic requirements for chimneys to be used for connection of fireplace inserts stipulate that the chimney should have a circular section or another appropriate section as required by...

Страница 7: ... 89 B 10425 a flat roof covered with any material b steep roof with easily ignitable covering c steep roof with non ignitable incombustible and flash resistant covering d situation of the chimney nearby another building Note 4 5 o m a k s i m u m 2 m Fasada wkładu Przewód dymowy 1 8 m 0 6 m 12 o 0 6 m 12 o 0 3m 12 o 1m 3m 3m 1 5m 0 3m 0 3m 12 o a b c d Chimney Façade of the insert Maximum 2m ...

Страница 8: ...s X Brick chimney 160 Combustible elements Figure 5 Safe distance of the chimney from combustible elements dimensions in mm Safe distance for conducting the connecting pipe combustion gas pipe through a combustible wall is at least 20 cm Figure 6 Method of conducting the combustion gas pipe through a combustible wall dimensions in mm 200 200 200 Ściana palna Rura spalinowa Wypełnienie lekki beton ...

Страница 9: ...on gas outlet is to be twice the size of the chimney diameter it ought to protect the chimney against adverse weather rain snow and foreign bodies it ought to be easily accessible for maintenance and cleaning of the chimney in case of two adjacent chimneys tip of one chimney ought to be located at least 50 cm above the other one in order to avoid mutual interference of produced negative pressure f...

Страница 10: ...ied to fireplace inserts Pursuant to data specified in table 4 section area of the air inlet ought to be 200 cm2 The following conditions must be observed while constructing the installation air is to be supplied from the direction of prevailing winds air is not to be supplied from the direction of the street a damper is to be installed to allow cutting off air supply while the fireplace is not in...

Страница 11: ...ent of mineral wool below 0 09 W mK measured at the temperature of 200 C is required This is crucial as unrestricted air flow of a sufficient quantity in compliance with local regulations is needed ensuring required cooling the insert and important to further efficiency of the whole air heating system 5 cm is to be measured between external ends of radiators and insulation of the enclosure Enclosu...

Страница 12: ...ęp 5 cm Izolacja Dopływ powietrza z zewnątrz śr 160 Obudowa Izolacja Kratki wylotu powietrza konwekcyjnego Kratki wentylacyjne komory dekompresyjnej Izolowana pólka dekompresyjna Dopływ powietrza konwekcyjnego Insulation Gap of 5cm Insulated decompression shelf Ventilation grates of the decompression chamber Convection air outlet grates Insulation Enclosure Convection air supply Outdoor air supply...

Страница 13: ...openings previously cut out in the separating shelf Ensure thorough sealing of connections figure 17 However if air is to be distributed by a turbine because of significant distances forced circulation termination of the pipe sucking hot air from the hood ought to be located app 15 cm below the bottom edge of outlet grates in the hood to prevent possible suction of cold air through outlet grates f...

Страница 14: ...on manual for fireplace insert KFDECOENG1 1562012 14 Figure 17 Connection of gravitational distribution to the hood Dystrybucja grawitacyjna rura o min średnicy 150 mm Gravitational distribution pipe with min diameter of 150mm ...

Страница 15: ...n the one hand consider proximity of the beam to external walls of the fireplace insert and on the other hand radiation of the furnace glazed door which is usually located very close to the fireplace beam Remember that both the internal surfaces and the bottom surface of the beam are made from combustible materials and may not be in contact with a temperature above 65 C Figure 19 presents several ...

Страница 16: ...ever please remember that heating capabilities of the fireplace insert are also influenced by other factors including quality of wood used humidity and calorific value climate conditions ambient temperature chimney draught properly constructed installation of the fireplace insert properly constructed installation of hot air distribution time of heating the rooms by means of the fireplace insert pr...

Страница 17: ...ert jacket through the fireplace hood and grate heat is released to the surroundings b radiation heat is given off through the glass pane and steel body of the device 2 2 Lighting up NOTE If the KFD ECO fireplace insert is not used for a prolonged time before lighting up check if the chimney is passable The fireplace heating system you have purchased is an ecological economical and efficient syste...

Страница 18: ...mney damper of the fireplace insert must be opened Otherwise smoke will come out to the room where the fireplace is installed During normal operation of the fireplace the chimney damper ought to be closed To avoid smoking of the room fuel should only be supplemented during the final stage of combustion i e when only a layer of embers remains in the furnace The furnace door is to be opened slowly t...

Страница 19: ...g manual 3 repeat the procedure at least 4 5 times if possible 4 gradually increase the quantity of fuel in compliance with guidelines contained in the operating manual and maintain the device in operation for as long as possible avoid short cycles of lighting up and extinguishing the fireplace insert at least during the initial stage 5 during the first cycles of lighting up do not place any objec...

Страница 20: ...se of insufficiently effective adjustment of combustion rate usually caused by excessive negative pressure in the chimney the flow of smoke should be reduced by means of the damper 2 4 Maintenance The way of using the fireplace and the quality of wood used for combustion are crucial to the phenomena occurring inside the furnace This requires periodic inspections and maintenance of the fireplace an...

Страница 21: ... particular attention to correct fitting i e keeping proper expansion distances At the end of inspection grease movable elements of the insert including the damper levers closures of the door and door lifting mechanism if installed To do that a heat resistant lubricant should preferably be used recommended by the fireplace insert manufacturer do not allow excess lubricant flow out of the insert Af...

Страница 22: ...t contain sulphur chlorine or other harmful chemical substances Exhaust gases contain only water and carbon dioxide whereas ash is an excellent natural fertiliser because it contains all mineral salts needed by plants The furnace should contain no more than 2 3 chunks with the length of app 33 50 cm and diameter of 10 15 cm Prohibited fuels include coal briquettes waste remainders of bark or lamin...

Страница 23: ...r extinguishing In case of occurrence of a fire in the fireplace or in the chimney i close the fireplace insert door ii close the supply of combustion air iii extinguish the fire using carbon dioxide extinguishers CO2 dry power extinguishers iv immediately call the fire brigade Never light up the fireplace insert if vapours of gases or combustible dusts are present in the room e g after lacquering...

Страница 24: ...e door Height of the chimney is to be measured from the point of connection of the furnace Dh hydraulic diameter 4 area circumference Furnace open on one side Area a h m Minimum reduced hydraulic diameter for the fireplace insert may not be smaller than 150 mm if chimney height is observed in compliance with figure 18 MINIMUM CHIMNEY HEIGHTS SECTION AREA OF FIREPLACE DOOR OPENING m2 CHIMNEY HEIGHT...

Страница 25: ...oat fire resistant mineral wool with Alu foil FIREROCK Upper part of the enclosure hood natural stone brick stone beam wood e g oak wooden beam sheet brass wooden beam shield steel profiles 30 x 28 fire resistant gypsum board fire resistant mineral wool with Alu foil self adhesive Alu tape Alu flex Ø 100 125 or Ø 160 pipes degreased structural plasterwork gypsum finishing coat outlet grates withou...

Страница 26: ...70 70LR 12 20 200 cm2 or 10 m3 h 1kW 650 cm2 1300 cm2 910 cm2 1820 cm2 Section areas of convection air inlets and outlets Opening without mesh The effective section area is equal to the area of grate opening F a b Opening with grid The effective section area is equal to half of the area of the grate opening F a b 2 The section area of the grate opening is reduced by the section area of the grate i...

Страница 27: ...of 12 March 2009 amending the regulation on technical conditions to be met by buildings and their situation PN 89 B 10425 Flues exhaust gas ducts and brick ventilation ducts Technical requirements and inspection upon acceptance PN EN 13229 Fireplace inserts with open solid fuel fireplaces Requirements and tests December 2002 AMENDMENT TO THE POLISH NORM PN EN 13229 2002 A1 March 2005 AMENDMENT TO ...

Страница 28: ...3 03 13 03 13 03 verage smoke temperature at smoke outlet C 243 243 243 minimum chimney draft Pa 12 12 12 weight kg 135 120 125 6 Troubleshooting PROBLEM REASON SOLUTION I Poor control of fire in the furnace 1 Excessive quantity of combustion air 1 Reduce the quantity of combustion air using the adjustment lever in the fireplace insert 2 Open chimney damper 2 Close the chimney damper 3 Excessive q...

Страница 29: ...spection door in the chimney and connection of the connecting pipe 3 Excessive negative pressure in the room in which the fireplace is installed 3 Supply fresh air to the room in which the fireplace is installed e g open the window 4 Fresh air inlet is not passable 4 Check if the duct supplying fresh air to the fireplace is passable 5 Air inlet is installed at the leeward side 5 Change location of...

Страница 30: ... of the fireplace insert 2 Close combustion air inlets 3 Extinguish the fire using carbon dioxide extinguishers CO2 dry powder extinguishers Never extinguish fire inside the chimney using water 4 Call the fire brigade immediately VII No power supply water module option No power supply 1 Do not add more fuel open the chimney damper and door of the fireplace insert ...

Страница 31: ... Installation and operation manual for fireplace insert KFDECOENG1 1562012 31 7 Drawings of the KFD ECO inserts KFD ECO i70 KFD ECO 70 L R ...

Страница 32: ... Installation and operation manual for fireplace insert KFDECOENG1 1562012 32 KFD ECO 70 ...

Страница 33: ... Installation and operation manual for fireplace insert KFDECOENG1 1562012 33 The inspection ought to be performed once a year by an Authorised KFD Fitter Date Performed work Company Signature ...

Страница 34: ... Installation and operation manual for fireplace insert KFDECOENG1 1562012 34 Date Performed work Company Signature ...

Страница 35: ... Installation and operation manual for fireplace insert KFDECOENG1 1562012 35 Date Performed work Company Signature ...

Страница 36: ...FDECOENG1 1562012 36 ver KFDECOENG 20181123 COPYRIGHT 2018 BY KFD Sp z o o v This publication may not be reproduced in part or in whole without the written permission of KFD Sp z o o KFD reserves the right to make changes in materials construction and design ...

Отзывы: