The ratio of the weather characteristics inclination [cF40]

– the parameter

determines the temperature of water in the central heating system when it is 0°C

outside. In the graph (picture 2) the relation between the outside temperature and the

temperature of water in the central heating system for ten examples of parameter

settings [cF ] has been shown.

Adjusting the weather characteristics of central heating circulation [cr 0]

– the

parameter determines by how many degrees the programmed temperature of central

heating water, calculating on the weather characteristics, will be revalued.

The minimum temperature of central heating circuit [cL20]

– this parameter

defines the minimum temperature of water in the central heating circuit. If the

temperature calculated from the weather curve, after shifting the curve by the heating

curve offset [cr 0], will be lower than this minimum temperature, then the target heating

circuit temperature willl be raised to the minimum temperature set by this parameter.

The maximum temperature of central heating circulation [cH75]]

– the parameter

defines the maximum programmed temperature of water in central heating circulation.

If temperature calculated on the weather characteristics, after considering the heating

curve change by value [cr 0], exceeds the maximum temperature, then the

programmed temperature of the central heating circulation will be limited to the value

set in this parameter. Protection from excessive increase of central heating circulation

temperature is of considerable significance in case of underfloor heating where the

temperature should not exceed 50°C.

CAUTION!

Additional guard protecting installation from excessive rise of temperature

should be used in underfloor heating systems regardless of the maximum program-

med temperature.

4.3 Mixing valve servomotor working parameters.

Hysteresis of mixing valve servomotor working [ch 2]

– the mixing valve

servomotor is stopped after achieving the programmed, calculated on the weather

characteristics, temperature of water in central heating circulation. When the rise in

temperature of water in central heating circulation is continued, the regulator closes

the mixing valve. The parameter determines the value by which the temperature of

central heating circulation needs to fall below the programmed one, so that the

regulator could proceed to open the valve.

Duration of pulse controlling the mixing valve actuator [cP 2]

– the parameter de-

fines the period of time during which the mixing valve is turned on when being opened

or closed. When fast actuators are applied, setting the short time control pulse is re-

commended.

Interval between impulses transmitted to control the servomotor [t 20]

– the

parameter determines the pause between impulses controlling the mixing valve

servomotor. The duration of the steering pulse is constant and equals 2 seconds. In

case of using fast servomotors, a longer break is recommended. Changing the

parameter to [t---] allows the servomotor to work continually.

Содержание UMS-4PS

Страница 1: ...OPERATION MANUAL UMS 4PS UNIVERSAL WEATHER COMPENSATING CONTROLLER Version HC22...

Страница 2: ......

Страница 3: ...ral heating pump should be connected to the appropriate sockets The outside temperature sensor may be connected parallelly to any given number of UMS UMP controllers bearing in mind that appropriate c...

Страница 4: ...e controller is in the WINTER mode In this mode the task of the controller is to maintain an appropriate temperature in the central heating system The temperature depends on the outside temperature or...

Страница 5: ...eans the regulator will switch to displaying water temperature of the central heating circulation when e g the user switches to viewing the outside temperature and during the period of 60 seconds will...

Страница 6: ...itch between the modes can be made manually 3 6 Temperature sensors damage The regulator tests functioning of measuring channels continually In case of detecting a damage the coded alarm is displayed...

Страница 7: ...9 9 1 C 0 cL20 The minimum temperature of heating circuit water 5 60 1 C 20 cH75 The maximum temperature of central heating circulation 40 90 1 C 75 ch 2 Mixing valve servomotor work hysteresis 1 9 1...

Страница 8: ...les the user to set the adequate inclination and change the weather characteristics The relation between the outside temperature or averaged outside temperature the set parameters and the programmed w...

Страница 9: ...alue set in this parameter Protection from excessive increase of central heating circulation temperature is of considerable significance in case of underfloor heating where the temperature should not...

Страница 10: ...ased upon the weather chara cteristics Changing the parameter to n results in the current outside temperature which is used to calculate the programmed installation water temperature CAUTION The memor...

Страница 11: ...Installation water temperature decrease input shall not be connected to any other UMP UMS inputs directly 5 2 Central heating turn off input Closing 7 8 contacts of UMS 4PS unit will turn off the cen...

Страница 12: ...the outdoor temperature sensor d 10 Value of decrease in installation water temperature LL10 Threshold temperature WINTER LH18 Threshold temperature SUMMER cF40 The ratio of the weather characteristi...

Страница 13: ...13 Picture 3 UMS 4PS controller and boiler configuration scheme...

Страница 14: ...14...

Страница 15: ...06 BS EN 61000 3 2 2007 EN 61000 3 3 2008 BS EN 61000 3 3 2011 Information on disposal This appliance is marked according to the European Directive 2002 96 EC on Waste Electrical and Electronic Equipm...

Страница 16: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: