4. Device operation modes.

Table 1. Operation mode list.

Operation mode.

Description

STOP

Boiler control stopped. Controller maintains central heating and domestic

water pump operation, but automatic ignition does not follow.

STAND-BY

Controller maintains central heating and domestic water pump operation. In

case of heat demand automatic ignition of boiler follows.

IGNITION

Controller carries out automatic ignition of boiler.

MAX. POWER

Fan and fuel feeder operates to reach boiler max. power.

MODUL. POWER

Controller reduces fuel feeding as much as boiler water temperature

corresponds to the desired setting.

MINIMUM POWER

Fan and fuel feeder operation is minimize to maintain fire.

SCAVENGE

(AIR PURGING)

Controller activates blower to ensure removal of accumulated gases.

EXTINCTION

(SHUT DOWN)

No heat demand or ash removal needed. Controller shuts down boiler

operation.

CLEANING

Burner cleaning.

AUGER (MANUAL)

REFILLING

Manual operation of fuel auger. Boiler control stopped. Controller maintains

central heating and domestic water pumps operation, but automatic ignition

does not follow.

AUGER EXTINCT

(EMERGENCY

SHUT DOWN)

Fuel ignition in auger channel. The controller empties ignited fuel from the

auger channel until temperature drops.

ALARMS

Safety and temperatures sensors failure alarms.

STOP.

Controller maintains central heating and domestic water pumps operation only to

protect the boiler against overheating and auger channel ignition. Room thermostat

contacts closing(call for heat) and domestic water temperature drop do not result in

any action. Pressing START button will result in switching the controller to

STAND-BY mode.

STAND-BY.

In this mode controller does not carry out any additional operation, until room

thermostat contacts close (call for heat) or domestic water temperature drop, the

boiler operation will focus on maintenance of temperature according to thermostat

setting programmed with the knob. If preheating of domestic water tank is necessary

and the desired boiler temperature setting is higher from domestic water

temperature setting the controller will follow higher setting. Pressing the STOP

button () will result in switching to STOP mode.

IGNITION.

Boiler controller is switched into IGNITION mode if demand for heat follows, and if

the controller did not detect the flame. During ignition the controller activates fan,

auger and igniter. Fuel and air feeding rate is adjusted by the technician. IGNITION

mode follows till flame is detected. If the flame is not detected within the specified

time, the controller activates „Out of fuel alarm”. Pressing STOP button, exceeding

time limit for cleaning, thermostat contacts opening or if water temperature in

domestic water tank is obtained during operation in IGNITION mode will result in

switching of the controller into EXTINCTION (SHUT DOWN) mode.

Содержание RK-2006LPG

Страница 1: ...OPERATION MANUAL RK 2006LPG Pellet fuel burner fitted boiler temperature controller Version 6A25...

Страница 2: ...on burner work 15 Alarms cancellation 15 Setting the parameters service mode 15 Table 3 Table service parameter 16 Language selection 18 Brightness saturation contrast of the display 18 Service settin...

Страница 3: ...locations that shall be dry Figure presents the electrical connection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Befor...

Страница 4: ...et the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If you enter the room th...

Страница 5: ...5 Boiler water temperature 6 Feeder work indicator 7 CH pump work indicator 8 Burner capacity indicator the higher the capacity the brighter the flame 9 Cleaning device work indicator 10 Blower 11 Sto...

Страница 6: ...tains central heating and domestic water pumps operation only to protect the boiler against overheating and auger channel ignition Room thermostat contacts closing call for heat and domestic water tem...

Страница 7: ...ER OPERATION MODE Depending on desired parameters the controller may gradually reduce fuel and air rate feeding to reduce burner power as much as boiler water temperature corresponds to the programmed...

Страница 8: ...e auger manual refilling function When device is in STOP mode press START and hold button for 5 seconds to start refilling Refilling follows according to the time programmed by the technician or until...

Страница 9: ...the technician Out of fuel alarm will be activated To turn on the controller again first refill fuel cancel the alarm with STOP button and begin setting up process by pressing START button Emergency a...

Страница 10: ...troller its damage will result in activation of the alarm and switching into STAND BY mode Protection against overheating and overheating of the boiler RK 2006LPG is protected against overheating of t...

Страница 11: ...the controller turns off the domestic water pump and activates alarm CAUTION This alarm does not require cancellation The alarm is deactivated automatically if repairs are made Return water temperatur...

Страница 12: ...perature 30 C 60 C 1 6 Domestic water heating priority NO YES 1 7 Domestic water tank bacterial flora liquidation program NO YES 1 8 Measured domestic water temperature 1 9 Measured return water tempe...

Страница 13: ...heating priority this parameter specifies operation of central heating and domestic water pumps during hot water preheating When priority is selected during operation and hot water preheating the con...

Страница 14: ...ing pump and return temperature sensor this option enables view of the return water temperature Otherwise this option in unavailable Flame optical detection parameters These parameters specify operati...

Страница 15: ...our of the device at maximum or minimum power 1 16 Burner start up counter Reading of this counter defines start number of the ignition attempts 1 17 Boiler on the parameter informs the user if the bo...

Страница 16: ...the device A list of all service parameters presented in the table Table 3 Table service parameter Lp Parameter Min Max 2 x Overall 2 1 Language see description 2 2 Brightness of the display 2 3Satur...

Страница 17: ...Duration of the CH pump cyclic work 1min 99min 7 3 Interval duration in the CH pump operation 1min 99min 8 x HTW pump 8 1 Domestic water path OFF ON MIXING PUMP 8 2 Domestic water heating hysteresis...

Страница 18: ...oller it is possible to test various output devices This feature is available in service mode only if the adjustment process is stopped ie The regulator before entering the service mode was in STOP mo...

Страница 19: ...with speed according to the selected Min fan speed during boiler start setting After time expire the controller will increase fan speed up to the selected Max fan speed during boiler start setting 3...

Страница 20: ...tching on of the fan during burner operation for the purpose of removal of accumulated gases 3 11 Fan scavenge air purging blow time this parameter specifies blow time This setting is unavailable if F...

Страница 21: ...auger operation cycle includes fuel feeding and feeding pause This parameter specifies the time of the whole cycle The desired value specifies all burner work modes which require fuel feeding ignition...

Страница 22: ...tion to the time of whole work cycle 4 7 Stoker work mode This parameter defines the operation of the internal tray stoker OFF the burner without the stoker CYCL stoker is switched on periodically reg...

Страница 23: ...uring extinguishing of feeder feeding initial fuel dose portion and during burner shut down This setting is unavailable if the stoker is switched off 4 12 Auger ignition test this parameter provides f...

Страница 24: ...2 sensor In case of higher temperatures PT 1000 sensor shall be used For flame brightness measurement FD 1 optical detector shall be used 5 2 Indication correction of flame optical detector only when...

Страница 25: ...of the burner If flame is not detected within the time programmed in this parameter the controller will repeat ignition cycle 5 7 Ignition try count this parameter specifies how many times ignition m...

Страница 26: ...ogrammed in this setting This function ensures combustion of all fuel remains and burner cool down 6 x Cleaning mechanism 6 1 Furnace cleaning mode this parameter specifies the way the cleaning mechan...

Страница 27: ...ally cleaning involving extinguished hearth start cleaning mechanism at the time set in the parameter TIME OPENING THE MECHANISM and run the fan with the power specified in the parameter SPEED FAN THE...

Страница 28: ...UTO mode or COMBI and determines which in turn goes off to start the procedure of cleaning 6 8 Minimum operating time without cleaning this parameter is available only when the cleaning mechanism oper...

Страница 29: ...he option of turning the CH pump occasionally to mix the water in the heating circuit The pump is turned on for the duration defined in the parameter TIME DURATION of CH PUMP WORK The option is availa...

Страница 30: ...s available if domestic water path EXISTS setting was selected 8 3 Increase temperature during domestic water heating Closing thermostat contacts means that boiler operation will follow according to t...

Страница 31: ...ion In this case after working for the hot water boiler water temperature may be higher than the temperature required to heat the rooms This may result in extinction of the burner due to exceeding the...

Страница 32: ...ler that can be programmed with thermostat s knob 9 2 Maximum boiler temperature this parameter specifies boiler max programmed temperature setting which can be programmed with thermostat s knob It is...

Страница 33: ...r water temperature corresponding to the programmed setting 9 8 Burner power modulation factor this parameter specifies degree setting when the controller will reduce burner power before boiler water...

Страница 34: ...case the boiler will operate continuously maintaining the set temperature of the boiler thermostat knob 9 10 The time constant of adaptation this parameter is available when the ther mostat is workin...

Страница 35: ...ol 10 2 MODBUS device number 1 247 allows the user to determine the number of the device attributed to your controller and to avoid errors when a number of devices are switched to the bus Default valu...

Страница 36: ...ERVICE changing all of the parameters is possible 10 6 Terminal access level defines to what extent access can be obtained through the remote terminal NO no access through the remote terminal READ OUT...

Страница 37: ...wer Supply 230 V 10 50 Hz Power consumption without fan and pump 4 VA Burner temperature measurement range KTY 81 210 9 109 C 1 C Temperature measurement range KTY 81 210 9 109 C 1 C Burner temperatur...

Страница 38: ...38...

Страница 39: ...PN EN 61000 3 3 2011 EN 55022 2010 PN EN 55022 2011 Information on disposal This appliance is marked according to the European Directive 2002 96 EC on Waste Electrical and Electronic Equipment WEEE Th...

Страница 40: ...Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: