6.2. Central heating circulation pump working parameters.

Temperature of central heating pump turn-on. [P 40]

– if the heating system is

not equipped with the accumulative tank ([ur 0], [ur 2] or [ur 3]), then the parameter

defines the level of the boiler water temperature at which the central heating pump

can be turned on. If it is set to ‘--‘, then too low temperature will not affect the pump

operation. However, it is turned on when the temperature of the boiler water exceeds

the [H 85] maximum temperature.

If the heating system is equipped with the accumulative tank ([ur 4])

– then the

parameter defines the value of the tank temperature at which the central heating

pump can be turned on. If it is set to ‘--‘, then the accumulative tank temperature will

not affect the pump operation.

Hysteresis of the central heating pump [Ph 2] –

the parameter determines by

how many degrees the temperature of the boiler water or the accumulative tank

must be decreased below the temperature of turn-on so that the pump should be

turned off.

Time of restarting the central heating pump [Pc 2]

– when the STOP mode is on

or the household thermostat circuit is opened, the pump is turned on for the period of

30 seconds so that the water of the heating circulation should be mixed. The

parameter determines the time of restarting the pump. The ‘--‘ value means turning

off the option.

6.3. The sensor and additional pump working modes settings.

The sensor and additional pump working modes [ur 0]

– the parameter

determines the working mode of the output controlling the additional pump and of

the additional sensor input.

The

[ur 0]

value indicates the shortage of a sensor and additional pump. The sensor

input may remain disconnected as it is not taken into account when testing failures.

The

[ur 1]

value indicates that the domestic water pump is connected to the

additional output and the domestic water sensor is switched to the additional input.

In the mode, the domestic water pump is turned on when the tank water temperature

decreases by the [uh 5] hysteresis value from the programmed [u 50] value. After

the tank water has been heated up to the temperature programmed in the [u 50]

parameter or when the temperature of the boiler water is lower than the one

measured in the tank, the pump is turned off. Also, when the boiler temperature

decreases below the [L 45] minimum value, the domestic water pump will be turned

off. In the [ur 1] mode the domestic water is prepared with priority, which means that

while topping up the domestic water tank, the central heating pump is turned off.

Содержание RK-2001W4

Страница 1: ...OPERATION MANUAL RK 2001W4 SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Wersja E128...

Страница 2: ...or u50 8 The temperature measured emissions 150 8 Parameter setting the service mode 8 Table 2 Service parameters list 9 Pressure fan work parameters 10 Central heating pump parameters 11 Settings of...

Страница 3: ...the regulator is shown in picture 2 CAUTION Before plugging in the controller first check if the wiring system is properly grounded and if the screw terminals of the output connector are tightened CA...

Страница 4: ...he boiler If the regulator is out of the user s mode the temperature of the boiler water is shown on the display and the last symbol indicates the working mode status 50 stands for the STOP mode 50 C...

Страница 5: ...rmostat input status If the exhaust gases sensor is connected then the central heating temperature equals the value set with the knob If the household thermostat is connected and its contacts are open...

Страница 6: ...ng pump to turn on After the reason for the alarm has been removed it can be cancelled with the STOP button The E 2 error indicates that the boiler overheating has occurred The error will induce the b...

Страница 7: ...eradication program u d u u50 Temperature measured with the additional sensor 150 The measured temperature of the exhaust gases End Exiting the user s mode The first column of the table shows the exem...

Страница 8: ...at night time when the water is not taken from the domestic hot water tank 5 4 The temperature measured with the additional sensor u50 the parameter presents the temperature of the accumulative tank...

Страница 9: ...1 C 2 A 99 Hysteresis of boiler temperature 90 99 1 C 99 Fd2h Fuel shortage testing time with burning 1 99 4h 1min 2h Fb2h Duration of fuel demand testing in working mode 1 99 4h 1min 2h Ar 0 Addition...

Страница 10: ...programmed one If the parameter is set to then the gradual regulation of rotational speed is not available and the blower works with the capacity set with the parameter Setting the parameter between...

Страница 11: ...of 30 seconds so that the water of the heating circulation should be mixed The parameter determines the time of restarting the pump The value means turning off the option 6 3 The sensor and additiona...

Страница 12: ...of the boiler water is equal to or lower than the accumulative tank water temperature or when the temperature of the boiler water decreases below the L 65 minimum value The additional pump operating...

Страница 13: ...nd in the working mode is activated when the temperature of the exhaust gases decreases below the c 90 value while the exhaust gases sensor is on or the temperature of the boiler water decreases below...

Страница 14: ...st gases decreases by the value of the set hysteresis the regulator will start to increase the blower speed gradually Blower speed jump while stabilizing the temperature of the exhaust gases c F10 the...

Страница 15: ...ler from the power supply remove the controller from the boiler chamber remove connectors and wiring from the regulator 8 Technical specification Power supply 230V 10 50Hz Power consumption blower and...

Страница 16: ...16 Picture 2 Schematics of connecting the RK 2001W4 unit Picture 3 Schematics of connecting the additional devices...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...rchased the product DECLARATION OF CONFORMITY Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 hereby declares that the product RK 2001W4 Controller is in con...

Страница 20: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: