KEY RK-2001E2 Скачать руководство пользователя страница 11

11

9. Notes.

Disp.

Parameter

User

Π100 Fan max work power or max power when Πr 0-10.

n 40 Minimum fan power.

Πh 2 Fan speed decrease coefficient.

Πr 1 Automatic fan speed control and time of fan start.

Πn 5 Fan work time.

Πu 6 Fan pause time.

P 42 Central heating pump launch temperature.

Ph 2 Central heating pump hysteresis.

Pc 2 The work mode and pause time of CH pump.

L 40 Minimum boiler temperature.

H 85 Maximum boiler temperature.

h 2

Boiler temperature hysteresis.

A 99 Boiler overheating temperature.

Fd60 Fuel shortage testing time with burning.

Fb30 Fuel shortage testing time in WORK mode and burning out.

Ar 0

Work mode of extra output:

0– output turning on extra boiler,

1– alarm output,

2– output controlling mixing valve,

3– output controlling emergency cooling system,

4– output controlling extra devices turning on during work of blow-in

fan.

Содержание RK-2001E2

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 Version 9A15 ...

Страница 2: ......

Страница 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CAUTION The maximum total power of devices connected to the controller mustn t exceed 450W CAUTION As additional option you can connect the UM 1 module...

Страница 4: ...iler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50º STOP mode 50ºC WORK mode 50ºc keeping fire in WORK mode 4 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change programmed ...

Страница 5: ...trolling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 outΠ Fan output testing outΠ out2 outr Additional output testing outr out3 End Exit the service mode In the table above the first column represents example display indications in the next columns there are par...

Страница 6: ...water in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch hysteresis Ph 2 this parameter defines what value should temperature decrease by below circulating pump launch temperature to turn the pump off The work mode and pause time of CH pump Pc 2 in STO...

Страница 7: ...to previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature of water in the boiler decreases below temperature set with the thermostat by hysteresis value and does not increase by 2 C in the programmed time the control process will be turned off and the disp...

Страница 8: ...s set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode By choosing End option on the display and pressing OK button you can quit service mode The device also quits service mode when no buttons are pressed for 1 minute 5 Additional functions In order to...

Страница 9: ...ed if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90 C may mean permanent damage of boiler temperature sensor e g if the boiler overheated above 150 C 7 Device removal In case of need to remove the controller from the system turn the master switch off...

Страница 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme ...

Страница 11: ... Pc 2 The work mode and pause time of CH pump L 40 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testing time with burning Fb30 Fuel shortage testing time in WORK mode and burning out Ar 0 Work mode of extra output 0 output turning on extra boiler 1 alarm output 2 output controlling mixing valve 3...

Страница 12: ...12 ...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohaterów Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl ...