![Kewtech KT62 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/kewtech/kt62/kt62_instruction-manual_1959985008.webp)
Specification
6
Measurement Specification
Function Open Circuit
Voltage (DC)
Short Circuit
Current
Range
Accuracy
Function Open Circuit
Voltage (DC)
Rated
Current
Range
Accuracy
Function
Rated
Voltage (AC)
Nominal Test
Current at 0
Ω
External Loop
Range
Accuracy
Continuity
Greater than
6V
Greater than
200mA as per
BS7671
20/200/2000
Ω
Auto-Ranging
±(1.5%rdg
+3dgt)
250V+40%
-0%
1mA or greater
@ 250k
Ω
as per
BS7671
20/200M
Ω
Auto-Ranging
±(1.5%rdg
+3dgt)
500V+30%
-0%
1mA or greater
@ 500k
Ω
as per
BS7671
20/200M
Ω
Auto-Ranging
±(1.5%rdg
+3dgt)
1000V+20%
-0%
1mA or greater
@ 1M
Ω
as per
BS7671
20/200M
Ω
Auto-Ranging
±(1.5%rdg
+3dgt)
Insulation
Resistance
230V+10% -15% 50Hz
230V+10% -15% 50Hz
230V+10% -15% 50Hz
Loop
Impedance
25A
15mA
15mA
±(3%rdg+4dgt)
±(3%rdg+8dgt)
±(3%rdg+4dgt)
20
Ω
200
Ω
2000
Ω
230V+10%
-15% 50Hz
Prospective
Short Circuit
Current
(PSC)
15mA
25A
25A
PSC accuracy is
derived from
measured loop
impedance
specification
and measured
voltage
specification
200A
2000A
20kA