Safety Warnings

WARNING:  INSTALLATION AND MAINTENANCE MUST BE CARRIED OUT 

BY SUITABLY QUALIFIED AND COMPETENT PERSONEL ONLY. 

HAZARDOUS VOLTAGES MAY BE PRESENT ON THE CONNECTION 

TERMINALS.

INSTALLATION

Install this product in accordance with local regulations, codes and instructions.

All fuses must be 0.5A / 250V Type F with a breaking capacity of 35A or greater.

All conductors carrying hazardous voltage must have external switching or 

disconnect mechanisms fitted that provide at least 3 mm of contact separation in all

poles.

Signal cables connected to this device must not exceed 30 metres long.

If signal cables are routed outside the building, install extra surge-protection

devices.

Failure to install or operate the unit in accordance with the 

above requirements may impair the electrical safety of the unit.

MAINTENANCE 

Before cleaning, inspection or maintenance, isolate all power sources to the unit.

There are no user-serviceable parts inside this unit. Never open the case.

Inspect all external wiring connections at regular intervals. Replace any damaged

wiring and tighten any loose connections.

To clean the unit, use a dry cloth to wipe the casing.

Take great care connecting the supply. If you connect power to the wrong terminals, 

it may destroy the unit.

Содержание APM-PROC

Страница 1: ...APM PROC Process Meter Quick Start Guide 990374 06 03 16 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 649 7100 Fax 732 649 7099 http www kep com...

Страница 2: ...al cables connected to this device must not exceed 30 metres long If signal cables are routed outside the building install extra surge protection devices Failure to install or operate the unit in acco...

Страница 3: ...10 C to 60 C 14 F to 140 F Temperature storage 40 C to 70 C 40 F to 158 F IP rating from the front IP65 NEMA4 POWER SUPPLY Nominal Input AC or DC 12 24 VAC VDC DISPLAY Number of digits 4 Digit height...

Страница 4: ...0 500 1000 I F 9 0001 Current 0 750 1500 I F 10 1001 Voltage 0 90 180 RPM 11 0101 Voltage 0 90 180 RPM 12 1101 Voltage 180 0 180 RPM 13 0011 Current 0 50 100 I C 14 1011 Current 0 75 150 I C 15 0111...

Страница 5: ...4V DC PSU RST SP1 SP2 Measured Current 0 50mA 12 to 24V DC PSU Fuse ON 1 2 3 4 0V V input Measured Voltage 0 10V Max Voltage 1 5V Referenced to COM Terminal COM I input 12 24V AC PSU RST SP1 SP2 Measu...

Страница 6: ...onto a Windows based PC It is not intended to install over a network or run from a server The APM Configurator software needs A PC or laptop running Windows XP Vista 7 or 8 operating system 32 or 64 b...

Страница 7: ...rm 1 Setup APM Configurator Software The first tab is used to setup values and functions for Alarm 1 Alarm 2 Setup APM Configurator Software The second tab is used to setup values and functions for Al...

Страница 8: ...Configurator Software The third tab is used to setup color and brightness for the Backlight Response Setup APM Configurator Software The fourth tab is used to setup the Response time for the display...

Страница 9: ...7 Scale Setup APM Configurator Software The fifth tab is used to setup the Scale Up to 20 input output pairs can be entered...

Отзывы: