KEPCO RA 59 Скачать руководство пользователя страница 16

2-6

RA 59 051313

user must ensure that the requirements for each configuration stated above are met. If any
questions or problems arise, the user is encouraged to contact Kepco Applications Engineering
group for technical assistance.

2.8

BUS BAR LINK REMOVAL/INSTALLATION REFER TO FIGURE 2-4

BE SURE ALL POWER IS DISCONNECTED FROM

RACK ADAPTER BEFORE DISASSEMBLY.

Two bus bar links and the associated attaching hardware included in Kit 219-0429 (see Figure
2-4) are used to connect the (+) and (–) terminals of an adjacent pair of power supplies.

NOTE: To connect all four power supplies of the RA 59 rack adapter for parallel/redundant

operation, three Bus Bar Link Kits, P/N 219-0429, are required.

a. Remove eight screws (2) and eight lockwashers (1) securing the four l/O connector assem-

blies (10) to the chassis (9).

b. Remove 12 screws (8) from the top, bottom, and sides of chassis (9). Carefully separate

backplate assembly (3) from chassis (9) and swing down (with wires attached) to expose bus
bar links (4).

c. To install a bus bar link (4), use four screws (7), lockwashers (6), and flat washers (5) to

attach bus bar link (4) to backplate assembly (3).

d. To remove a bus bar link (4), remove four screws (7), lockwashers (6), and flat washers (5)

securing bus bar link (4) to backplate assembly (3).

e. Assemble backplate assembly (3) to chassis (9) (taking care that wires are not crimped)

using eight screws (2) and lockwashers (1).

f. Secure backplate assembly (3) to chassis (9) using 12 screws (8)

2.9

SHIPPING

Shipping of the rack adapter is recommended only after the HSP power supplies have been
removed from the rack adapter. Contact Kepco Applications Engineering if further assistance is
required.

WARNING

Содержание RA 59

Страница 1: ...the Kepco Docu mentation Office in New York 718 461 7000 requesting the correct revision for your par ticular model and serial number 3 The contents of this manual are protected by copyright Reproduc...

Страница 2: ......

Страница 3: ...rce Power Requirements 2 2 2 5 Cooling 2 2 2 6 Installation 2 3 2 7 Wiring Instructions 2 3 2 7 1 Safety Grounding 2 3 2 7 2 Source Power Connections 2 3 2 7 3 Source Power Configurations 2 4 2 7 3 1...

Страница 4: ...A 59 051313 1 1 RA 59 Rack Adapter iv 1 2 Mechanical Outline Drawing RA 59 Rack Adapter 1 3 2 1 Key Pin Location 2 1 2 2 Rear Panel Connections 2 2 2 3 Single Phase A C D C Source Power Wiring 2 4 2 4...

Страница 5: ...RA 59 051313 iii LIST OF TABLES TABLE TITLE PAGE 1 1 Accessories 1 2 2 1 Equipment Supplied 2 1...

Страница 6: ...iv RA 59 051313 FIGURE 1 1 RA 59 RACK ADAPTER...

Страница 7: ...rminations are provided for each of the four power supply mounting positions Internal power output configurations differ for the three models as follows Output power connections for all four positions...

Страница 8: ...configurations two links per kit See PAR 2 8 and Figure 2 4 for details SCREW 101 0456 Pan head phillips self forming 6 32 x 1 4 used to attach bus bar links SAFETY COVER DC 137 0135 Covers DC output...

Страница 9: ...RA 59 051313 1 3 1 4 Blank FIGURE 1 2 MECHANICAL OUTLINE DRAWING RA 59 RACK ADAPTER...

Страница 10: ......

Страница 11: ...ss the key and key way align The user can configure each power supply position of the rack adapter for the desired voltage in the desired position the factory default keying is for the 5 volt HSP modu...

Страница 12: ...pera tion from d c or three phase a c power is also available please contact factory 2 5 COOLING The HSP power supplies mounted within the rack adapter are maintained within their operating temperatur...

Страница 13: ...ly and its load are as critical as the interface between other types of electronic equip ment If optimum performance is expected certain rules for the interconnection of source power supply and load m...

Страница 14: ...s current 2 7 3 SOURCE POWER CONFIGURATIONS The following standard wiring configurations are recommended by Kepco as being compliant with national and international safety standards It is the user s r...

Страница 15: ...TE REGARDLESS OF OUTPUT CONFIGURATION OUTPUT SENSE LINES MUST BE PROPERLY CONNECTED FOR OPERATION REFER TO HSP OPERATOR S MANUAL 2 7 5 1 PARALLEL REDUNDANT OPERATION Adjacent positions of the RA 59 ra...

Страница 16: ...lockwashers 1 securing the four l O connector assem blies 10 to the chassis 9 b Remove 12 screws 8 from the top bottom and sides of chassis 9 Carefully separate backplate assembly 3 from chassis 9 and...

Страница 17: ...ost Kit P N 108 0203 3 Backplate Assembly 4 Bus Bar Link P N 172 0513 2 5 Flat washer 6 P N 103 0100 4 per bus bar link 6 Lockwasher Split 6 P N 103 0066 4 per bus bar link 7 Screw 6 32 x 1 4 PHPH sel...

Страница 18: ......

Отзывы: