V — INSTALLATION

MOUNTING THE POWER SUPPLY.  

Refer to Fig-

ure 2 and insert power supply into selected slot of RA 19-
(X)B Rack adapter until power supply front panel is flush
with rack adapter chassis and secure with front panel Phil-
lips head mounting screw. 

CONNECTIONS. 

All connections are made at the rear

panel of the RA 19-(X)B Rack Adapter (see applicable RA
19-(X)B Operator Manual). Connect the load to the appli-

cable ± DC OUTPUT terminals. AC input power to each
slot is applied via two INPUT POWER terminal blocks as
indicated on the rack adapter rear panel. Make sure to
connect the AC input Neutral, Line and Ground wires to
the respective terminals of the terminal blocks.

REMOVAL. 

To remove a power supply, first use the

POWER switch to turn off the unit. Then loosen the
mounting screw and extract the unit from the RA 19-(X)B
Rack Adapter.

VI — OPERATION     

Turn the unit on using the front panel POWER switch (see
Figure 5)

CAUTION: DO NOT repeatedly toggle the

POWER on/off switch as this may cause unit to fault. 

When output voltage is available, the green VDC ON LED
is on. While monitoring output voltage at the front panel
test points, the Output Voltage Adjust trimmer allows
adjustment of the output voltage. 

FIGURE 5.  COMPONENT LOCATIONS

Master/slave parallel configurations of one or more power
supplies are covered in the applicable RA 19-(X)B Rack
Adapter manual. 

The MASTER ON LED (amber) goes on under any of the
following three conditions:

• Independent operation.

• Operation in a parallel master/slave configuration

to indicate which unit is the master

• Operation in a parallel master/slave configuration

to indicate that a slave unit is no longer within the
proper specifications for paralleled units. Slave 1
should be optimally adjusted to 40mV less than
master, slave 2 adjusted to 40mV less than slave
1, etc. The maximum allowable difference
between paralleled units is 250mv. The minimum
allowable difference between paralleled units is
25mV. If a slave exceeds these limits, the MAS-
TER ON light goes on.

NOTES:

1.

MASTER ON LED not used on 3.3V model: always
OFF.

2.

HSF models also share current when all units are
adjusted to the same output voltage, however MAS-
TER ON indicator may be lit on all units in parallel.

Additional information for various parallel and alarm con-
figurations can be found in the applicable RA 19 Rack
Adapter manual referenced on page 1.

Содержание HSF 12-13PFC

Страница 1: ...page 4 standard models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency and less weight C PFCC offers current monitoring via an integral current sensing resistor includes option T X PFCX offers remote on off includes option T and Y PFCY includes options C X and T II FEATURES FRONT PANEL ACCESS The front panel provides a power ON...

Страница 2: ...line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts are rated for 1A at 30V d c and 0 5A at 125V a c These contacts may be used to configure close on failure or open on failure alarm cir cuits see Figure 3 for typical alarm circuits Refer to the applicab...

Страница 3: ... each other and each unit must be operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see load effect specifications this indicates that forced current share is no longer working units are simply in automatic current share mode If forced current sharing at less than 10 nominal current per su...

Страница 4: ... 265V a c Load Effect 10 100 load change 0 5 typ 1 5 max except 3 3V model 1 typ 2 max Temperature Effect Range 10o to 71o C 0 5 typ 1 0 max Combined Effect includes source load and temperature effects 0 9 typ 1 8 max except 3 3V model 1 typ 2 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max TABLE 1 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 150W SERIES STANDARD NO SUFFIX MODEL HSF 3 3 30PFC HS...

Страница 5: ...ient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 23 mA typ 0 35 mA max 120V a c 60Hz 0 45 mA typ 0 7 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 U S UL 60950 3rd Ed Canada CAN CSA 22 2 No 60950 00 3rd Ed ambient temp 50 C 150W units are CE marked per the Low Voltage Directive LVD EN60950 The standards do not apply with DC input operation...

Страница 6: ...2 PFCC PFCT PFCX PFCY HSF 15 10 PFCC PFCT PFCX PFCY HSF 24 6 3 PFCC PFCT PFCX PFCY HSF 28 5 3 PFCC PFCT PFCX PFCY HSF48 3 1 PFCC PFCT PFCX PFCY OUTPUT VOLTS d c NOMINAL 3 3V 5V 12V 15V 24V 28V 48V ADJUSTMENT RANGE 2 8 3 4V 4 3 5 3V 9 8 13 0V 12 8 16 3V 19 2 26 0V 23 0 30 2V 40 0 52 2 OVERVOLTAGE SETTING 1 2 3 4 4 6V 5 2 6 5V 13 2 15 2V 16 8 18 8V 26 5 30 3V 31 5 34 8V 54 5 59 8V OUTPUT CURRENT NOM...

Страница 7: ...00V a c for one minute Between input and case ground 2KV a c for one minute INSULATION RESISTANCE Between input and ground output and ground input and output 500V d c 15 to 35 C ambient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 29 mA typ 0 45 mA max 120V a c 60Hz 0 40 mA typ 0 65 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 2001 U S UL ...

Страница 8: ...o fault When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel test points the Output Voltage Adjust trimmer allows adjustment of the output voltage FIGURE 5 COMPONENT LOCATIONS Master slave parallel configurations of one or more power supplies are covered in the applicable RA 19 X B Rack Adapter manual The MASTER ON LED amber goes on under a...

Страница 9: ...ANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 081721 228 1550 REV 17 9 FIGURE 6 HSF PFC 150W INCLUDING SUFFIX C T X AND Y POWER SUPPLY OUTLINE DRAWING ...

Отзывы: