background image

 053119

228-1915

5

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

http://www.kepcopower.com   



 email: [email protected]

VII — INSTALLATION.

INPUT CONNECTIONS. 

 This power supply oper-

ates from single phase a-c mains power (or between
two phases of 3-phase a-c mains power), 230V, 50/
60Hz nominal (range: 176 - 264V, 47-63Hz) without
any need for range selection. The user must provide a
properly sized and rated mains lead (line cord) and ser-
vice with a current rating compatible with the antici-
pated input current.

LOAD CONNECTIONS. 

Power connections re-

quire wires that are properly rated for the nominal output
current of the unit. Connect the load to the OUTPUT
and COMMON power terminals on the BOP 2KW Out-
put Terminal Block on the rear panel (see Figure 9).
OUT S and COM S terminals of the Sense/Monitor Ter-
minal block are for connection of remote sensing leads
(after removing the factory-installed local sensing
links). 

NOTE: Output Sense lines must be con-

nected for proper operation, either locally, or at the
load (remote).

 Also use OUT S and COM S to monitor

voltage at the load using external equipment such as a
DVM, oscilloscope, etc. Use OUT MON and COM
MON to monitor voltage at the BOP output.

It is critical that configurations comprised of BOP, load,
and external programming devices, have a single
earth-ground point. Observe the following caution and
refer to the applicable BOP 2KW-MG Operator Manual
for earth-ground recommendations. 

Failure to

observe this caution will void the warranty!

CAUTION: Never connect both the load
terminal tied to the BOP COM terminal
and the programming device common
to earth-ground. This compromises
accuracy and will cause catastrophic
damage to the BOP if the connection
between BOP COM and the load termi-
nal tied to earth-ground is lost.

LOCAL SENSING (FACTORY DEFAULT). 

Unit is shipped with local sensing links installed: OUT S
connected to OUT MON and COM MON connected to
COM S at the BOP 2KW Sense/Monitor Terminal Block
(see Figures 7A and 9). 

REMOTE SENSING SELECT. 

First remove the

factory-installed local sensing links between OUT S
and OUT MON and between COM MON and COM S at
the BOP 2KW Sense/Monitor Terminal Block. Then
connect OUT S and COM S lines from the BOP 2KW
Sense/Monitor Terminal Block to the load (see Figure
7B) using #22 AWG wire, twisted pair. 

ANALOG I/O CONNECTIONS. 

The Analog I/O

Port connector, located on the control section rear
panel of the BOP 2KW power supply (see Figure 6),
provides access to analog programming inputs which
can control the mode of operation (voltage or current),
output voltage or current, and establish positive and
negative voltage and current limits. An output analog
corresponding to output current is also provided. Refer
to Operator’s manual for details. 

TRIGGER CONNECTIONS. 

 The Trigger Port

(see Figure 6) provides for an external trigger input for
use with SCPI *TRG and TRIG commands. Refer to
Operator’s manual for details. 

GPIB CONNECTIONS (MG SUFFIX). 

 Your

computer must have a GPIB interface card installed.
Connect the power supply to the computer’s GPIB
interface card. Use a standard GPIB interface cable at
the GPIB port on the rear panel (see Figure 6)

The default GPIB address is 6; refer to the Operator’s
Manual to change it.

LAN CONNECTIONS (ME SUFFIX ONLY). 

Connect the BOP 2KW to a Microsoft Windows-based
computer via the LAN connector (see Figure 6). Use a
standard ethernet cable whether using a router or hub,
or connecting the BOP 2KW directly to a computer.
The BOP 2KW-ME is Auto-MDI-X enabled and does
not require a crossover cable for direct connection. For
Unix and Safari connections see full Operator Manual
(refer to “Accessing Manuals.” on page 1).

FINDING KEPCO POWER SUPPLIES ON 

THE LAN. 

The PSfind utility can be downloaded

from the Kepco web site at:

www.kepcopower.com/drivers/drivers-dl3.htm#bop1k

 

This utility finds all operational Kepco power supplies
connected to the LAN and then shows the MAC and IP
addresses of the models found. 

To run the utility from your PC download the psfind.zip
file to your computer. Extract psfind.exe from the zip
file to a location of your choice, then double-click
psfind.exe to run the application. A separate window
opens as shown in Figure 2. Once the search is com-
pleted, all found units are displayed in the Select a Unit
window (the MAC address appears in parentheses). If
you do not see your device in the Select a Unit window
or if the icon to the left of the selected instrument is red
(not green), make sure it is turned on and connected to
the network, then click the Search Again button.

!

Содержание BOP 10-200ME

Страница 1: ...ing instructions including an Installation Operation Summary which includes hyperlinked references to detailed procedures but which can be printed as a handy reference The BOP 2KW MG ME Operator s Man...

Страница 2: ...ering many electrochemical reactions Models with L suffix have been optimized for exceptionally low current ripple and noise and improved stability drift and temperature making them ideal for driving...

Страница 3: ...th displayed voltage on LCD within 0 05 of rated maximum voltage VI ACCESSORIES See Table 3 TABLE 3 ACCESSORIES ITEM FUNCTION PART NUMBER Mating Connector Trigger Mates with Trigger port 142 0527 Kepc...

Страница 4: ...4 228 1915 053119 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Страница 5: ...Terminal Block Then connect OUT S and COM S lines from the BOP 2KW Sense Monitor Terminal Block to the load see Figure 7B using 22 AWG wire twisted pair ANALOG I O CONNECTIONS The Analog I O Port conn...

Страница 6: ...load exists contacts cannot be held closed by actuator When the power supply is turned on it per forms a brief self test that includes testing the three processors analog interface and dis play and an...

Страница 7: ...con figuration shown as a power up setting so the changes will not be lost when the unit is turned off APPLY EXIT applies the current changed setting without saving for power up and exits to the previ...

Страница 8: ...AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 4 BOP 2KW SERIES POWER BOOST SECTION FRONT PANEL CONTROLS AND INDICATORS FIGURE...

Страница 9: ...o incre ment or decrement the highlighted digit Pressing ADJUST while rotating adjusts the least significant digit If the output is on unit not in Standby changes made using the ADJUST control are imm...

Страница 10: ...channel is determined by the MODE key in local mode which alternately selects either Voltage mode or Current mode or by SCPI com mand in digital remote mode The protection channel is determined automa...

Страница 11: ...l are possible Otherwise the value entered is applied to both positive and negative protect channels NOTE The BOP can be configured to show the protection limits as either a single value that applies...

Страница 12: ...loads Table 4 indicates how the power supply responds to a command to go from Output ON to OFF When the output is disabled the unit is set to voltage mode voltage is set to zero and both current prot...

Страница 13: ...opened after the connections are complete and then the switch in series with the battery should be closed If the constant voltage type active electronic load is adjusted to zero before handling the p...

Страница 14: ...com mands via RS 232 GPIB or LAN ports opera tion via web pages Analog Remote Operation via Analog I O port Details about Protect Limits and Software controlled limits Storing Recalling Power Supply...

Страница 15: ...15 15 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 9 BOP 2KW OUTLINE DIMENSIONS Sheet 1 of 2 REAR VI...

Страница 16: ...NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 10 BOP 2KW WIRING DIAGRAM DETAIL A S MON OUT OUT MON COM GND GND NET OUT MON N C OUT S COM S CO...

Отзывы: